Functions
Notes:
•
*
Since NPST-GR Ver. 2.4 does not support FP10 or FP10S, some instructions, that are supported only
by FP10 or FP10S, are not included in the table.
•
**
The availability of the functions depends on the type of programmable controller and the CPU version.
For details about functions available for the FP1 CPU version 2.7, refer to page 245, “8-7. FP1 CPU
Version 2.7”.
Item
Programmable controllers
supported
Instructions
*
Modem communication
settings
**
Error clear function
**
Battery error disregarding
function
**
NPST-GR Ver. 2.4 (AFP266528)
FP1:
FP1/FP-M:
FP1/FP-M:
FP3:
FP3/FP-C:
FP5:
36 comparison instructions
(ST=, AN <, etc.) not available
Not available.
Modem communication parameters
cannot be set. (System register
416 for the RS232C port and 411
for the RS422 port cannot be set
using NPST-GR Ver. 2.4.)
Not available.
Operation without backup battery
cannot be selected. (System
register 4 cannot be set using
NPST-GR Ver. 2.4.)
NPST-GR Ver. 3.1 (AFP266538)
FP1:
FP1/FP-M:
FP1/FP-M:
FP3:
FP3/FP-C:
FP5:
FP10/FP10S:
FP10:
All the instructions of an FP1 with
CPU version 2.7 can be programmed.
Available.
Modem communication parameters
can be set. (System register 416 for
the RS232C port and 411 for the
RS422 port)
Available.
Operation without backup battery can
be selected. (System register 4 can
be modified.)
36 comparison
instructions
**
0.9 k
2.7 k
5 k
10 k
16 k
16 k
0.9 k
2.7 k
5 k
10 k
16 k
16 k
30 k
60 k