3-1. Installation
1. Panel Mounting
Mount the Control Unit, Expansion Unit, FP1 A/D Converter Unit, FP1 D/A Converter Unit, and FP1 I/O Link Unit
on the mounting panel with M4 size screws.
Mounting Hole Dimensions
2. DIN Rail Mounting
To mount the Control Unit, Expansion Unit, FP1 A/D Converter Unit, FP1 D/A Converter Unit, and FP1 I/O Link
Unit on a DIN rail, use the DIN rail attachment lever which is attached to the mounting panel.
• To detach the unit from the DIN rail, pull the lever
down with a slotted screwdriver.
• Align the unit with the mounting rail groove and push
the unit down to install it.
Control Unit
Expansion Unit
Intelligent Unit
Link Unit
W (mm/in.)
110/4.331
110/4.331
180/7.087
250/9.843
250/9.843
290/11.417
70/2.756
110/4.331
110/4.331
180/7.087
250/9.843
110/4.331
110/4.331
110/4.331
110/4.331
40/1.575
C14 series
C16 series
C24 series
C40 series
C56 series
C72 series
E8 series
E16 series
E24 series
E40 series
FP1 A/D Converter Unit
FP1 D/A Converter Unit
FP1 Transmitter Master Unit
FP1 I/O Link Unit
C-NET Adapter S1 Type
H (mm/in.)
71/2.795
71/2.795
86/3.386
86/3.386
110/4.331
110/4.331
71/2.795
71/2.795
71/2.795
86/3.386
86/3.386
71/2.795
71/2.795
71/2.795
71/2.795
71/2.795
(except E8
Triac output type)
E8 Triac output
type
Unit
Control Units (C14 and C16 series)
Expansion Units (E8 and E16 series)
FP1 A/D Converter Units
FP1 D/A Converter Units
FP1 I/O Link Units
Control Units (C24, C40, C56, and C72 series)
Expansion Units (E24 and E40 series)
2-M4 or 2-dia. 5
W
H
4-M4 or 4-dia. 5
W
H
2-M4 or 2-dia. 5
W
H
C-NET Adapter S1 type
3-1. Installation
Claw
DIN rail
DIN rail
Slotted screwdriver
DIN rail
attachment lever
DIN rail attachment lever
Summary of Contents for FP1
Page 1: ...PROGRAMMABLE CONTROLLER FP1 is a global brand name of Matsushita Electric Works Hardware ...
Page 28: ...20 ...
Page 98: ...90 ...
Page 150: ...142 ...
Page 208: ...200 ...
Page 226: ...218 ...
Page 280: ...272 ...