7. Wiring the FP1 Transmitter Master Unit
Connect the RS485 interfaces on the FP1 Transmitter Master Unit and on the other Programmable Controller with a
communication cable. When connecting the communication cable, be sure to connect positive (+) to positive, and
negative (-) to negative of the RS485 interface.
8. Wiring the FP1 I/O Link Unit
Connect the RS485 interfaces on the FP1 I/O Link Unit and on the other Programmable Controller with a
communication cable. When connecting the communication cable, be sure to connect positive (+) to positive, and
negative (-) to negative of RS485 the interface.
1) Cable Specifications
Vinyl Cabtyre Cable (VCTF): 2-conductor
Conductors
Insulation
Molding
jacket
• Conductor
Size:
Min. 0.75 mm
2
(AWG18 or lager)
Resistance:
Max. 25.1
Ω
/km (at 20˚C/68˚F)
• Cable
Insulation thickness:
Max. 0.6 mm/0.24 in.
Molding jacket diameter: Approx. 6.6 mm/2.60 in.
+
–
F.G.
F.G.
+
–
RS485 Interface of an FP1 I/O Link Unit
RS485 Interface of the other
Programmable Controller
Communication cable
• Conductor
Size:
Min. 1.25mm
2
(AWG16 or lager)
Resistance:
Max. 16.8
Ω
/km (at 20 ˚C/68 ˚F)
• Cable
Insulation material:
Polyethylene
Insulation thickness:
Max. 0.5 mm/0.020 in.
Jacket thickness:
Approx. 8.5 mm/0.335 in.
Conductors
Insulation
Jacket
+
–
F.G.
F.G.
+
–
RS485 Interface of an FP1 I/O Link Unit
RS485 Interface of the other
Programmable Controller
Communication cable
55
3-3. Wiring