Register Definitions (Coils, Floats, Words, and Longs)
Coil Map
Float Register Map
Controller Coil Registers
Address
Min
Max
Units
Notes
Control Relay 1 - TRASAR
00000
1
0
1
On/Off
Control Relay 2 - TAG POLYMER
00000
2
0
1
On/Off
Control Relay 3 - BIO-REPORTER
00000
3
0
1
On/Off
Control Relay 4 - OXID BIOCIDE
00000
4
0
1
On/Off
Control Relay 5 - NONOX BIOCIDE
00000
5
0
1
On/Off
Control Relay 6 - BLOWDOWN
00000
6
0
1
On/Off
Control Relay 7 - pH CONTROL
00000
7
0
1
On/Off
Alarm Relay
00000
8
0
1
On/Off
Digital In 1 - No Flow
000013
0
1
On/Off
Digital In 2 - Interlock
000014
0
1
On/Off
Digital In 3 - Spare
000015
0
1
On/Off
Digital In 4 - Spare
000016
0
1
On/Off
Controller Input Float Registers
Address
Min
Max
Units
Notes
Product 1 Dosage (TRASAR)
3000
40
0.0
300.0
ppm
Product 2 Dosage (TAG Polymer)
3000
42
0.0
300.0
ppm
Rz
3000
44
0.0
300.0
ppb
Rs
3000
46
0.0
300.0
ppb
Turbidity
3000
48
0.0
200.0
ntu
Background
3000
50
0.0
300.0
ppm
Cell Fouling
3000
52
0.0
100.0
pct
Conductivity
3000
54
0.0
10,000.0
uS/cm
pH
3000
56
0.0
14.00
-
ORP
3000
58
-1,000.0
1,000.0
mV
Corrosion 1 (Right side of controller)
3000
60
0.0
Note 1
mpy
Corrosion 2 (Left side of controller)
3000
62
0.0
Note 1
mpy
Sample Temperature
3000
64
32.0
150.0
deg F
Nalco Bio-Index
3000
66
-999
999.0
-
Nalco Scale Index
3000
68
-999
999.0
-
Polymer Consumption
3000
70
0.0
100.0
pct
HTI
3000
72
0.0
999.0
hours
System Volume Average
3000
74
0.0
9,999,999.0
gal
Blowdown Rate
3000
76
0.0
999.0
gpm
Makeup Rate
3000
78
0.0
999.0
gpm
Heat Rejected
3000
80
0.0
999,999.0
kBTU/day
Recirculation Rate
3000
82
0.0
999.0
gpm
Analog Input 1
3000
84
-99,999
99,999.0
-
Analog Input 2
3000
86
-99,999
99,999.0
-