521-OM0108.88
Copyright
2009 Nalco Company
Technical Help
(630) 305-CHEM
F-4
3D TRASAR Starter NCM Corrosion Measurement
Upgrade Procedure
This procedure details the steps required to complete the 3D TRASAR Starter NCM Corrosion
Measurement upgrade. All steps
must
be completed in order to begin using the features of the
NCM.
1. Order Upgrade and NCM probes.
Order the 3D TRASAR Starter NCM Corrosion Measurement Upgrade,
P/N 060-TR3205.88
along
with required probes (sold separately.) Order through Nalco customer service, or through the Order
Wizard.
2. Unpack and Identify Components
The 3D TRASAR NCM technology upgrade includes the following:
•
Patented NCM technology upgrade procedure
•
2 NCM probe restraints
•
2 NCM probe fittings
•
Upgrade confirmation sticker
Verify that you have all four components before proceeding.
Note!
Corrosion probes must be ordered separately.
3. Register New Hardware (http://web.3dtrasar.com/upgrade)
Register new hardware at the 3D TRASAR upgrade website (http://web.3dtrasar
.com/upgrade). In
order to complete the registration, you will need the following information: controller serial number
,
and sales order and SAP Sold to numbers that appear on upgrade order
.
!
!
Important!
Registration
must
be completed
48 hours
before proceeding to next step.