3D TRASAR
5500 - Installation & Operation Manual
521-OM0108.88
Copyright
2009 Nalco Company
2-31
Technical Help
(630) 305-CHEM
2.6.5 NCM Corrosion Probe Installation (con’t)
STEP 3
-
Insert the mild steel probe in location #1
as indicated in Section 2.6. Probe tips
must be parallel to the ground. Two
raised dots on the probe end cap can be
used to orient the tips.
Install probes
Install probes and attach
connectors as shown.
Tighten swage fitting fully.
ORP Probe
Install probes
Install probes and attach
connectors.
STEP 4
-
Insert the copper probe in location #2 as indicated in Section 2.6. Probe tips must be
parallel to the ground. Two raised dots on the probe end cap can be used to orient
the tips.
STEP 5
-
Tighten the swage fittings fully (finger tight plus 1¼ turn)
STEP 6
-
Connect the corrosion probe cables to either of the two controller inputs (there is one
input connection on each side of the controller). The 3D TRASAR controller
automatically recognizes the probe metallurgy – no calibration is required.