3D TRASAR
5500 - Installation & Operation Manual
521-OM0108.88
Copyright
2009 Nalco Company
2-45
Technical Help
(630) 305-CHEM
2.7.13 Analog I/O Connections
(User Wired in Controller Box or Junction Box)
There are (2) 4-20ma inputs and (8) 4-20ma outputs
available in the 3D TRASAR controller. Both are
non-isolated
.
The analog inputs must be externally powered. They can be used to control conductivity
, pH, and
ORP. Refer to Appendix I for information on the halogen analyzer.
The analog outputs are internally powered for a max. load of 600 ohms. The analog outputs can be
used to transmit any of the following variables:
TRASAR product dosage, Tag Polymer product
dosage, Cell Fouling, Nalco Scale Index, Nalco Bio-Index, Conductivity, pH, ORP, Corrosion
#1, Corrosion #2, and Sample Water Temperature
.
Connection
Description
Controller Box
Board Reference
Controller Box Terminal
(Removable
Connector)
Junction Box
Terminal
4-20ma Input 1
TB16
1+
AI1 (+)
TB16
1-
AI1 (-)
4-20ma Input 2
TB16
2+
AI2 (+)
TB16
2-
AI2 (-)
4-20ma Output 1
TB17
1+
AO1 (+)
TB17
1-
AO1 (-)
4-20ma Output 2
TB17
2+
AO2 (+)
TB17
2-
AO2 (-)
4-20ma Output 3
TB17
3+
AO3 (+)
TB17
3-
AO3 (-)
4-20ma Output 4
TB17
4+
AO4 (+)
TB17
4-
AO4 (-)
4-20ma Output 5
TB17
5+
AO5 (+)
TB17
5-
AO5 (-)
4-20ma Output 6
TB17
6+
AO6 (+)
TB17
6-
AO6 (-)
4-20ma Ouput 7
TB17
7+
AO7 (+)
TB17
7-
AO7 (-)
4-20ma Output 8
TB17
8+
AO8 (+)
TB17
8-
AO8 (-)
Wiring