Start-up system
Enter Set Points
You are up and running!
!
2.9
STEP 9 - Start-up System
The following is an overview of the steps required to start up
your 3D TRASAR system. The remainder of the manual pro-
vides details for each step listed below.
STEP 1
- Upload configuration (refer to help screens (F1) in
Configurator program).
IMPORTANT
: Every 3D TRASAR controller is
configured uniquely for each application through
Nalco’s “Configurator” software. Your Nalco
representative will have created your system
configuration prior to installation.
STEP 2
- Verify control settings, setpoints and alarms.
• Through the controller keypad, verify that all of the new settings from the “Configurator”
have been accepted into the controller.
STEP 3
- Activate “System Start-up” mode (refer to Section 4.10.11).
• The “System Start-up” mode allows you to temporarily suppress alarms for a user defined
period of time. This prevents false alarming and relay time-outs from occurring until the
cooling system has reached chemical equilibrium.
STEP 4
- Initiate 3D TRASAR scale control (refer to Section 5).
• 3D TRASAR scale control is an available upgrade for 3D TRASAR Starter systems.
STEP 5
- Initiate 3D TRASAR bio-control (refer to Section 6).
• 3D TRASAR bio-control is an available upgrade for 3D TRASAR Starter systems.