For a 1-point calibration
Tip
√
A 1-point conductivity calibration can be performed when conductivity
has drifted, or changed <+/- 10% of the second point value of the previ-
ous 2-point calibration
STEP 1
- Leave probe in the Tee with water flowing (probe should have been
installed at least 15 minutes for equilibrium.) Select
1-point
calibration.
STEP 2
- Using a handheld instrument of known accuracy, locally sample the
process water and determine the conductivity value.
STEP 3
- Enter this value.
4.10.6 Conductivity Calibration Screens (con’t)
Control
Settings
Alarm
Settings
Preferences
System
Info
Network
Information
Manual
Relay
Actions
Menu
Alarms
Firmware Version 8.0
Firmware Version's 6.0 and prior
Curve Setting Calibration
2-Point
3-point
1-point calibration offset
Yes
Yes
Standard Solutions
No
(Need true conductivity value)
Yes
TemCoEff Access
Yes
No
Data Weighted Filter
Yes
No
Recommended Range
500-99,999 uS/cm
500-15,000 uS/cm
Built-in Instructions
Yes
Yes
Comparison of Conductivity Calibrations