4.10.10 Slug Feed Biocide Screens
Control
Settings
Alarm
Settings
Preferences
System
Info
Network
Information
Manual
Relay
Actions
Menu
Alarms
There are three options for slug feeding biocides. Each choice will follow the pre-bleed and lockout
conditions setup in the configuration.
1. Use
Hand Feed Nonox
to physically add a non-oxidizer by an operator to the cooling system.
Note
: If feeding Glutaraldehyde the configured oxidizing feed will be suspended for 8 hours.
2. Use
Hand Feed Oxidizer
to physically add an oxidizer by an operator to the cooling system.
3. Use
Relay Feed Oxidizer
to energize the oxidizer relay.