The control device drives the fan based on the highest of values sent by the bound wireless sensor(s).
When you start the timer mode from this device, the ventilation will be active for 30 minutes.
4. CO
2
setpoint
The device continuously measures the level of CO
2
in the air and compares the measured value to a configured
setpoint value. The device controls the ventilation accordingly to keep the measured CO2 level below the
requested level. When in Comfort mode, the requested level is equal to the configured value. In Eco mode,
the requested level is 250 ppm above the configured value.
NOTE:
The device stores the configured fan speed values in the control device, and requests them from there.
The device stores the CO
2
setpoint itself, and does not communicate this with any other device.
!
5. Visual signals
Startup
Status LED
Mode LEDs
System status
White
Continuous
Eco
Comfort
On
On
On
On
On
Green
Continuous <800ppm
Yellow
Continuous 800-1900ppm
Red
Continuous >1900ppm
1 flash
Com. error
2 flashes
Dirty filter
3 flashes
Fan error
4 flashes
CO
2
sensor error
5 flashes
Low battery
Selecting
Off
Away mode
•
Home mode
•
Timer mode
•
Eco mode (Auto)
•
Comfort mode (Auto)
•
9
ALNOR
®
ventilation systems
is a legally protected trademark and technical patent. All rights reserved.
w
w
w
.al
nor
.com.
pl
User's manual
HRQ-PremAIR-SENS-CO2