NAPCO Security Systems
Freedom F-64 Programming Instructions
Page 35
WI1502A 9/06
Continued
RELAY EVENT OPTIONS
RELAY #
AREA
TIMEOUT
EVENT ID
COND.
See
Step 1 below
See
Step 2 below
See
Step 3 below
See
Step 4 below
See
Step 5 below
To program, follow the 5 steps below.
STEP 4
EVENT ID CODES:
Each relay event can be assigned any of the available event IDs from
Table 4
.
Select 2-digit
Event ID
from
Table 4
(on next page); enter in corresponding address locations (left and right digit).
STEP 5
RELAY EVENT CONDITION OPTIONS:
Each relay event can be assigned an alarm type; and an activation condition; also,
select a timeout type for each. Enter 5A in left area, enter 5B in right area.
5A. Select
Alarm Type
and
Timeout Type
from
Table 5A
(on next page); enter in corresponding left address location.
5B. Select
Activation Conditions
from
Table 5B
(on next page); enter in corresponding right address location.
STEP 2
AREA OPTIONS:
Each relay event can be assigned to Area 1, 2, 3 and / or 4.
Select the
area
from
Table 2
(on next page); enter in corresponding address location.
STEP 1
RELAY # OPTIONS:
The F-64 supports 16 external relays from Relay Module RM3008. Multi-
ple events may be "mapped" to each relay, up to a maximum of 32
events.
Select the
relay number
from
Table 1
(next page); enter in corresponding address location.
STEP 3
TIMEOUTS:
Each relay event can be assigned a timeout depending on Alarm Type option.
If Alarm Type is selected for timeout in minutes or seconds, enter the 3-digit
timeout duration
in correspond-
ing address location. To choose seconds or minutes, see step 5A below. 254 is maximum entry.
DI
RECT A
D
DRESS PROGRA
M
MODE