background image

1

GEM-RS232

Control Panel / Computer Converter

INSTALLATION INSTRUCTIONS

R

333 Bayview Avenue

Amityville, New York 11701

For Sales and Repairs, (800) 645-9445

For Technical Service, (800) 645-9440

© Napco 1999

WI966 6/99

GENERAL DESCRIPTION

The GEM-RS232 Control Panel/ Computer Converter is

an interface module which allows the NAPCO GEM-P9600
control panel to be connected to a computer which may be
used to display system status. The GEM-RS232 is
approved by Underwriters Laboratories for  supplemental
use only. It provides signal and ground isolation between
the control panel and the computer and will protect the
control panel from shorts, transients and surges which may
emanate from the computer or the associated cabling.

The GEM-RS232 has been designed to be permanently

mounted inside the cabinet of the GEM-P9600 and can be
connected to the computer in several different fashions
(see CONNECTION).

SPECIFICATIONS

Input Power: 12 V DC nominal, 60 mA (supplied by control
panel connections)

• 

Note: Reduce available panel combined auxiliary current
by 60 mA)

Dimensions: 11/16” x 2 9/16” x 2 9/16” (HxWxD)
Range: 50 feet using RS232 serial cable

100 feet using Cat5 cable

ORDERING INFORMATION

1. GEM-RS232

• 

RS232 Converter

• 

6 conductor Modular to Modular (RJ12 Style) cable

• 

1 SE-AUTOMATION  EPROM

2. GEM-RS232KIT

• 

RS232 Converter

• 

6 conductor Modular to Modular (RJ12 Style) cable

• 

8 Pin Modulator (RJ45 Style) to DB9 Male Adapter

• 

8 Pin Modulator (RJ45 Style) to DB9 Female
Adapter

• 

1 SE-AUTOMATION  EPROM

SYSTEM REQUIREMENTS

The following system hardware is required:

• 

Gemini GEM-P9600 Control Panel

• 

SE-AUTOMATION  EPROM Upgrade must be
installed in control panel.

MOUNTING INSTRUCTIONS

1 Open GEM-RS232 case using screwdriver.
2 Drill hole in the center of the base of the case

(side without label) using a 1/8” drill bit.

3 Drill hole in housing using a 1/8” drill bit
4 Mount securely using nut and screw provided

CONNECTION

• 

Refer to the wiring diagram. Connect the 6-conductor 

modular cable (supplied) to J1 (RJ12 style) of the 
control panel and then plug into the module (RJ12 
style) plug on the RS232 converter.

• 

For direct connection to serial port of computer or              

automation system, plug male DB9 connector of    
serial cable (NOT supplied) into the DB9 connector 
of the RS232 converter and connect other end to     
serial port of computer.

• 

For CAT 5 wiring to computer or automation system, 

plug male DB9/CAT5  connector (supplied with  
GEM-RS232KIT) into the DB9 connector of the 
RS232 adapter and connect female DB9/CAT5    
connector (supplied with GEM-RS232KIT) to         
automation system DB9 connector. Use CAT5 
cable terminated with standard RJ45 connectors 
(not supplied).

NAPCO Security Systems, Inc.

333 Bayview Avenue, Amityville, New York 11701

For Sales and Repairs, call toll free: (800) 645-9445

For direct line to Technical Service, call toll free: (800) 645-9440

Internet: http://www.napcosecurity.com