background image

 

X

  GEM-P1664EX Programming Instructions 

L

 NAPCO Security Systems 

 

Page 18

 

WI1387  7/05 

 
 
 
 
 
 
 
 
 
 
 
 

Key Fob Transmitters 

(Press 

R

 

to set cursor). 

Keyfobs can be programmed as “Arm/Disarm” devices (refer to WI752).  
For each Key Fob Transmitter, enter: 

The Key Fob Transmitter number (01–08). 

Area number to which transmitter is assigned (1 - 4); enter 0 to disable keyfob. 

The 6-digit RF ID # printed on the transmitter (enter all numbers and/or letters, including 

leading “0”s, if any). 

1-digit checksum number printed on the transmitter (enter all numbers and/or letters, including leading “0”s, if any). 

Aux-1 Option (see key fob aux 1 & aux 2 options). 

Aux-2 Option (see key fob aux 1 & aux 2 options). 

Press 

U

 to save.  Press the NEXT/YES button to proceed. 

 

 
 
 
 
 
Note:

  If the Key Fob is converted for Two Button “Emergency Use” (by cutting an internal 

jumper), both top or bottom buttons must be depressed to activate an alarm.  In this case, the 
Aux-1 and Aux-2 cannot be programmed.   
 

Key Fob Transmitters as Zone Input Devices 

(refer to display above: press the PRIOR/NO 

button to go backwards). 

Each of the 4 key fob buttons can be assigned to a zone.  For example, On button = point 1; Off 
button = point 2; A1 = point 3; A2 = point 4.  Up to 64 key fobs (using 1 button) or 32 key fobs 
(using 2 buttons) or 16 key fobs (using all 4 buttons) or any combination up to a maximum of 64 

controlled zones can be assigned, providing multiple wireless panic buttons on a system, each reporting to the Central Station or a 
pager and/or annunciating on a keypad the key fob zone number with description/location.  

To assign a key fob to a zone:  

program the key fob as you would a transmitter, entering the key fob's ID code, check sum and point number at the appropriate 
zone.  The “Quick Method” is not allowed.  The zone may be hardwired to a sensor as well as assigned to a key fob (either one will 
activate the zone alarm output).  

NOTE: 

 If assigning a key fob to a zone, the “ON/OFF” buttons on the key fob will no longer arm/

disarm the system. The key fob is converted to a “panic only” device.  
 
 
 
 
 

NOTE: Key fobs 1-8 report 
openings and closings as 
Users 57-64. 

 

DATA 

ENTRY 

AUX 1/AUX 2 

OPTIONS 

None 

Relay Group 1 Toggle 

Relay Group 2 Toggle 

Panic 

Auxiliary 

Instant 

PGM2 Output Toggle 

Access on PGM2 

Output 

Arm Stay 

Interior Button 

GEM-RP3DGTL/GEM-K3

DGTL A

N

GEM-RP4RFC/GEM

-K4RF  Ea

s

y Me

nu Dr

iv

en Pr

ogr

am 

Mode

 

 

 

29 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

 

INTERIOR  BYPASS  FIRE/TBL  SYS TBL  CHIME 

KEY FOB ZONE ASSIGNMENT: 

 Key fobs can also be assigned to zones to allow multiple wireless panic buttons on 

one alarm system, each reporting to a central station, a pager or having a description on the keypad that describes the 
person holding the key fob, the location where the person holding the key fob is stationed, or the special purpose of the 
key fob button being depressed.  

See the next page on key fob Zone Assignment. 

Summary of Contents for Gemini GEM-P1664EX

Page 1: ...Quick Start for GEM K3DGTL 1 Refer to the wiring diagram connect Siren Aux Power PGM Output Remote Bus Earth Ground Zone and Tele phone Wiring NOTE See Installation Instructions WI1388 2 Connect AC power first and then the battery 3 Configure the keypad see page 55 4 Access the Easy Menu Driven Dealer Program Mode Press 456789 R Press NO until 17 appears on the keypad display Press NEXT YES to ent...

Page 2: ...ity along with the new MENU and ENTER buttons While the instructions in this manual are depicted using the K Se ries keypads the manual applies to both the classic and the K Series keypads Program Mode is the same for both keypads only the button names have changed as follows The A button and the R button operate identically in Program Mode for both keypads The D button and the U button operate id...

Page 3: ...ber 16 Central Station Receiver 1 Account Number 16 Central Station Receiver 1 Format 16 Enter User Codes 16 RF Transmitter Points 17 Key Fob Transmitters 18 Dealer Code 19 Clear Program 19 DIRECT ADDRESS PROGRAM MODE 20 Keypad Programming Overview 20 Accessing Direct Address Program Mode 20 Keypad Address Program Mode Display 21 Direct Address Program Mode Keypad Commands 21 Direct Address Progra...

Page 4: ...he Direct Address Program Mode is an extension of the Dealer Program Mode wherein data is entered at the keypad by specific location This mode is accessed from the Easy Menu Driven Program Mode by pressing the C button at any time User Program Mode Keypad programming The User Program Mode is intended for authorized users and is limited to keypad programming of User Codes DOWNLOADING FROM A COMPUTE...

Page 5: ...al Station Reporting System Exit Entry Zones in Area 1 Interior Zones in Area 1 24 Hour Zones in Area 1 Chime Zones in Area 1 Chime 2 Zones in Area 1 Exit Entry2 Zones in Area 1 50mS Loop Response Zones Aux Output Activated on Alarm Zones Sensor Watch Zones Keypad Sounder on Alarm Zones Auto Bypass re entry Zones Enable no EOLR Zones Enable Telco Line Fault Test Enable Burg Output Chirp on Keyfob ...

Page 6: ... Fire Zones in Area 1 Appears for New Panel Only Enter the zone number of any zones which are to be used as Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 64 Directly enter each zone number including leading zeros and press U to save and then repeat for any additional zone s Press NEXT YES button to proceed NOTE If you are programming a multiple Area system enter all the zo...

Page 7: ...rammed Chime 2 zones give a distinct pulsating tone when zone is faulted Exit Entry2 Zones in Area 1 New Program Only Enter the zone numbers of zones to be used as Exit Entry 2 zones Valid entries are from 01 to 64 Directly enter each zone number including leading zeros Press U to save and repeat for any additional zone s press the NEXT YES button to proceed NOTE An Exit Entry 2 Entry Time of 30 s...

Page 8: ...ss the PRIOR NO button to continue The SIA CP 01 Features are designed to reduce the incidence of false alarms See WI1388 Installer Pro gramming Quick Reference Chart SIA False Alarm Reduction and GEM P1664 Factory Default Description for more information NOTE Do not enable unless reporting otherwise system trouble Fail to Communi cate may occur Number of Keypads in Area 1 Directly enter the total...

Page 9: ... User Codes with Area 1 4 Options Press R once to set the cursor to the User Code Use the number buttons 1 through 9 to enter a code from 3 to 6 digits Enter up to 6 digits 4 digits is recommended in the first six boxes from left to right for each user code Valid entries are 0 9 NOTE Press 0 for a zero and press G0 for a blank space No blank spaces in between leave blank any trailing boxes If Enab...

Page 10: ...his is normally used to activate a door strike while an area is disarmed Also program Access Control on PGM2 Output Address 0719 and PGM2 Output Access Control Timeout Address 0711 Ambush There are two types of Ambush Codes 1 A 2 digit code prefix that is entered immediately prior to and as part of the regular User Code and 2 A separate and unique User Code Disarming with an Ambush Code will cause...

Page 11: ...ttons on a system each reporting to a Central Station or a pager and or annunciating on a keypad the key fob zone number with description location To assign a key fob to a zone program the keyfob as you would a transmitter entering the keyfob s ID code check sum and point number at the appropriate zone The Quick Method is not allowed The zone may be hardwired to an electrical sensor as well as ass...

Page 12: ...ress the U button Data entry is not allowed NOTE Enter Easy Menu Driven Program Mode to program system again Cold Start Erases Entire Program This erases the entire program including Dealer Program by erasing Program Data Zone Description Data and System Status Data similar to a new panel Access address 2286 then press the U button Data entry is not allowed NOTE Some features schedules can only be...

Page 13: ...tructions Fire Zones Appears for New Panel Only Enter the zone number of any Fire Zones both 2 wire 4 wire or wireless Valid entries are from 01 to 64 Directly enter each zone number including leading zeros and press U to save and then repeat for any additional zone s Press the NEXT YES button to proceed NOTE If you are programming a multiple Area system enter the zone number of zones required for...

Page 14: ...s in Area 1 New Program Only Enter the zone numbers of zones to be used as Exit Entry zones Valid entries are from 01 to 64 Directly enter each zone number including leading zeros Press U to save and repeat for any additional zone s press the NEXT YES button to proceed NOTE An Exit Entry 2 Entry Time of 30 sec will automatically be programmed 50 mS Loop Response Zones New Program Only Enter the zo...

Page 15: ...ram Only Press the NEXT YES button to program all zones except 24 Hr fire zones for No End Of Line Resistor Press the PRIOR NO button to continue Enable Telco Line Fault Test Press the NEXT YES button to enable Telco Line Fault Test Press the PRIOR NO button to continue NOTE There is a preset 60 second Telco Line Fault Test Delay Enable Burg Output Chirp on KeyFob Press the NEXT YES button to enab...

Page 16: ...r Options for each code Refer to the tables below for available data entries for User Options Press R once to set cursor to the User Number and enter the desired User Number Press R once again to set the cursor to the User Code Use the number buttons 1 through 9 to enter a code from 3 to 6 digits Enter up to 6 digits 4 digits are recommended in the first six boxes from left to right for each user ...

Page 17: ...ons and U save Notes 1 For User Code press G 0 for Blank Space 2 For User Options press 0 for Blank Space 28 INTERIOR BYPASS FIRE TBL SYS TBL CHIME INTERIOR BYPASS FIRE TBL SYS TBL CHIME Quick Enroll Method If a receiver is already installed in the panel Napco transmitter wireless points can be programmed automatically enrolled using the following procedure NOTE The transmitter point will be enrol...

Page 18: ...ones can be assigned providing multiple wireless panic buttons on a system each reporting to the Central Station or a pager and or annunciating on a keypad the key fob zone number with description location To assign a key fob to a zone program the key fob as you would a transmitter entering the key fob s ID code check sum and point number at the appropriate zone The Quick Method is not allowed The...

Page 19: ...ss C to silence the keypad Direct Entry 33 INTERIOR BYPASS FIRE TBL SYS TBL CHIME INTERIOR BYPASS FIRE TBL SYS TBL CHIME rE ZONE DESCRIPTIONS GEM K3DGTL cannot be used to enter Zone Descriptions To enter Zone Descriptions you must use the GEM K1CA Keypad or the Napco Quickloader Software DATE ENTRY GEM K3DGTL cannot be used to enter the date To enter Date you must use the GEM K1CA Keypad Version 5...

Page 20: ...u to change all the options It consists of multiple address locations with two data entry locations each left and right as shown in the adjacent diagram ACCESSING DIRECT ADDRESS PROGRAM MODE LEFT DIGIT RIGHT DIGIT 3 C DATA ENTRY LOCATIONS ADDRESS LOCATIONS 0000 0000 TO 2287 HEXADECIMAL DATA BLANK No Options 1 to 9 Entries 1 to 9 0 Entry of 10 B to F Entries 11 to 15 1 Press EEEEEE R 2 Press the PR...

Page 21: ...3DGTL GEM K3DGTL Keypads To access press C in Dealer Program Mode 1 Toggle Cursor to 4 digit ad dress field using the R button 2 Enter address Number directly using number buttons 0 9 3 Enter Data directly using num ber buttons 4 Press the U button to save To exit press C NOTE Press 0 button to clear character at cursor Select NEXT PRIOR Address Press GP to jump to next programming block Press G0 ...

Page 22: ...our program ENTRY TOTAL PRESS N KEYPAD DISPLAYS 8 4 2 1 blank 0 8 4 2 1 1 1 8 4 1 2 2 2 8 4 3 3 3 8 2 1 4 4 4 8 2 5 5 5 8 1 6 6 6 8 7 7 7 4 2 1 8 8 8 4 2 9 9 9 4 1 10 G 0 0 4 11 G 1 B 2 1 12 G 2 C 2 13 G 3 D 1 14 G 4 E 15 G 5 F DATA ENTRY SELECTIONS BINARY VALUE CIRCLED Table 1 Determining data entry for a location each nibble Numbers in parentheses indicate data for selected zones or features See...

Page 23: ...s of each address CONVENTIONS USED IN THIS MANUAL The Keypad Programming Worksheets in the back are provided as an address programming reference to help the installer modify his custom default program or to make minor field alterations to an existing panel program It is recommended that the panel be uploaded to NAPCO s PCD Windows software following any keypad programming and that the PCD Windows ...

Page 24: ... shown 3 Enter the selected data entry in the boxes shown 4 For more information on a programming option refer to the Glossary at the end of this manual EXIT ADDRESS 0000 DELAY LEFT RIGHT sec Default 3 C ENTRY ADDRESS 0001 DELAY 1 LEFT RIGHT sec Default 1 E ENTRY ADDRESS 0002 DELAY 2 LEFT RIGHT sec Default 1 E PGM2 Output ADDRESS 1413 Access Cntrl LEFT RIGHT Timeout sec Default blank blank ABORT A...

Page 25: ...TIONS ADDRESS 0546 0547 LEADING DIGITS FOR PAGER FORMAT In Pager Format reporting the message typically begins with 00 However for some pager services this will cause the Pager s Voice Mail feature to activate This option allows you to program these digits to any number desired A typical Pager report is 003 22 1234 where 3 is the Event 22 is the zone and 1234 is the Subscriber ID number For exampl...

Page 26: ...d Alarm Output 8 4 2 1 0837 8 4 2 1 PGM1 Output 8 4 2 1 0838 8 4 2 1 PGM2 Output 8 4 2 1 0839 8 4 2 1 Report Event Telco 1 8 4 2 1 0840 8 4 2 1 Report Restore Telco 1 8 4 2 1 0841 8 4 2 1 Report Event Telco 3 8 4 2 1 0842 8 4 2 1 Report Restore Telco 3 8 4 2 1 0843 8 4 2 1 GLOBAL SYSTEM EVENT TROUBLE RIGHT DATA VALUES CIRCLE Default blank blank from address 0856 0863 SYSTEM RESPONSE ACTIVATED BY A...

Page 27: ...IC AMBUSH Pulsed Alarm Output 8 4 2 1 0872 8 4 2 1 Alarm Output 8 4 2 1 0873 8 4 2 1 PGM1 Output 8 4 2 1 0874 8 4 2 1 PGM2 Output 8 4 2 1 0876 8 4 2 1 Report Event Telco 1 8 4 2 1 0877 8 4 2 1 Report Event Telco 3 8 4 2 1 0879 8 4 2 1 AREA 3 SYSTEM EVENT TROUBLE RIGHT DATA VALUES CIRCLE Default blank blank from address 0880 0887 SYSTEM RESPONSE ACTIVATED BY AREA 4 AREA 4 SYSTEM EVENT TROUBLE LEFT ...

Page 28: ...bling Zones 9 16 2 Wireless Trouble Activates Telco 1 4 Wireless Trouble Activates Telco 3 8 Enable Alarm Output on Telco Fail only when Armed RIGHT DATA VALUES CIRCLE SYSTEM OPTIONS 1 Automatic Interior Bypass Easy Exit 2 Veri phone Zones Trip PGM2 Output 4 Veri phone Audio Priority Over Alarms 8 Resound on Wireless Smoke Low Battery SYSTEM OPTIONS LEFT DATA VALUES CIRCLE Disable Keypad Function ...

Page 29: ...ired option by circling the data values for each digit left and right 2 Add the data values ex F 15 1 2 4 8 from the selected options See page 23 3 Enter in address location left and right digits NOTE Dark shaded data value box shows option not available 4 Press U or D to save Default blank blank LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES ADDRESS 2054 SYSTEM OPTIONS LEFT DATA VAL...

Page 30: ...ber depends on Easy Menu Question CENTRAL PHONE Default blank across digits 1 20 for CS Receiver Telephone Numbers 2 and 3 CS Receiver 1 LEFT RIGHT Format blank ADDRESS 0460 CS Receiver 2 LEFT RIGHT Format blank ADDRESS 0482 CS Receiver 3 LEFT RIGHT Format blank ADDRESS 0504 CS RECEIVER TELCO 1 OPTIONS LEFT DATA VALUES CIRCLE Sum Check 1 3 1 with Extended Restores 2 RESERVED 4 RESERVED 8 CS RECEIV...

Page 31: ...GHT DIGITS 1 4 0664 0665 0666 0667 CS Telco 1 Sub scriber Opening Closing ID Number Area 4 ADDRESS 0572 0575 RIGHT DIGITS 1 4 0572 0573 0574 0575 CS Telco 1 Sub scriber Opening Closing ID Number Area 3 ADDRESS 0568 0571 RIGHT DIGITS 1 4 0568 0569 0570 0571 CS Telco 3 Sub scriber Opening Closing ID Number Area 2 ADDRESS 0636 0639 RIGHT DIGITS 1 4 0636 0637 0638 0639 CS Telco 3 Sub scriber Opening C...

Page 32: ...ow Battery 0705 CS SYSTEM REPORTING OPTIONS ADDRESS 0670 0705 CS AREA SYSTEM REPORTING OPTIONS ADDRESS 0785 0786 0788 Default blank blank LEFT DIGIT SUM RIGHT DIGIT SUM ADDRESS 0788 CS AREA SYSTEM REPORTING OPTIONS 1 Select the desired option by circling the data values for each digit left and right 2 Add the data values ex F 15 1 2 4 8 from the selected options See page 23 3 Enter in address loca...

Page 33: ... A Choose a desired delay timeout ex 20 sec B Divide it by 16 4 Press U or D to save EXIT ENTRY DELAYS Apply only to zones programmed with the following options Exit Entry 1 Exit Entry 2 Exit Entry Follower NOTE Sensor Watch Time Options are similar to above table except in hours Either use the tables provided or calculate your own timeout using the steps indicated WARNING Timers have uncertainty ...

Page 34: ...1455 1468 to enable EZM Group Options PULSE EVENT CODE will be the first digit of the 2 digit reporting code The second digit will be the second digit of the reporting zone For example for zone 9 address 0728 if the right digit is 3 then the reporting code is 39 For example for zone 15 address 0734 if the right digit is 4 then the re porting code is 45 MODEM CODES determine the zone types reported...

Page 35: ...r 28 User 27 User 26 User 25 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUES ADDRESS 0804 User Opening Telco 1 User 40 User 39 User 38 User 37 LEFT RIGHT User 36 User 35 User 34 User 33 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0805 User 48 User 47 User 46 User 45 LEFT RIGHT User 44 User 43 User 42 User 41 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0809 User Openi...

Page 36: ...r 28 User 27 User 26 User 25 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUES ADDRESS 0822 User Opening Telco 3 User 40 User 39 User 38 User 37 LEFT RIGHT User 36 User 35 User 34 User 33 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0823 User 48 User 47 User 46 User 45 LEFT RIGHT User 44 User 43 User 42 User 41 8 4 2 1 8 4 2 1 RIGHT DATA VALUES LEFT DATA VALUE ADDRESS 0827 User Openi...

Page 37: ...14 Groups will be automatically enabled If 64 Zones are used and Zone Doubling is enabled then only Groups 1 12 will be automatically enabled NOTE If Zone Doubling Address 1423 option 1 is not enabled then Zones 1 8 are included in the control panel and Zones 9 64 Groups 1 14 are EZM Zones If Zone Doubling is enabled then Zones 1 16 are included in the control panel and Zones 17 64 Groups 1 12 are...

Page 38: ... VALUES CIRCLE RESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 Burglary Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1475 RIGHT DATA VALUES CIRCLE Disarming Area 3 1 Area 1 Burg Output Silenced 2 Area 2 Burg Output Silenced 4 Area 3 Burg Output Silenced 8 Area 4 Burg Output Silenced RESERVED LEFT DATA VALUES CIRCLE RESERVED 1 R...

Page 39: ...ALUES CIRCLE RESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 Pulsed Burg Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1479 RIGHT DATA VALUES CIRCLE Disarming Area 3 1 Area 1 Pulsed Burg Output Silenced 2 Area 2 Pulsed Burg Output Silenced 4 Area 3 Pulsed Burg Output Silenced 8 Area 4 Pulsed Burg Output Silenced RESERVED LEFT DA...

Page 40: ...A VALUES CIRCLE RESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 PGM1 Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1483 RIGHT DATA VALUES CIRCLE Disarming Area 3 1 Area 1 PGM1 Output Silenced 2 Area 2 PGM1 Output Silenced 4 Area 3 PGM1 Output Silenced 8 Area 4 PGM1 Output Silenced RESERVED LEFT DATA VALUES CIRCLE RESERVED 1 RESE...

Page 41: ...A VALUES CIRCLE RESERVED 1 RESERVED 2 RESERVED 4 RESERVED 8 Default blank one 1 PGM2 Output Turns Off upon Disarm LEFT DIGIT SUM OF DATA VALUES RIGHT DIGIT SUM OF DATA VALUES 1 ADDRESS 1487 RIGHT DATA VALUES CIRCLE Disarming Area 3 1 Area 1 PGM2 Burg Output Silenced 2 Area 2 PGM2 Burg Output Silenced 4 Area 3 PGM2 Burg Output Silenced 8 Area 4 PGM2 Burg Output Silenced RESERVED LEFT DATA VALUES CI...

Page 42: ...and left digit address locations above 3 Press U or D to save KEYPAD OPTIONS ADDRESS 1425 1431 1440 1446 RIGHT OPTION blank Disabled 1 Active Keypad KEYPAD ASSIGNMENT KEYPAD NO KEYPAD OPTIONS LEFT DATA VALUES CIRCLE ADDRESS 1440 1446 KEYPAD OPTIONS RIGHT DATA VALUES CIRCLE RSRVD PANEL ACCESS EASY ARMING AMBUSH LEFT ADDR RIGHT RSRVD KEYPAD PANIC KEYPAD AUX KEYPAD FIRE 1 8 4 2 1 1440 8 4 2 1 2 8 4 2...

Page 43: ...ature out of limits and restore If the G key is depressed and held down for 2 seconds the date will display for 5 seconds In addition three addresses must be enabled either via Quickloader or via direct address programming in order for the Tempera ture Display at Keypad feature to operate The following features must be enabled In Quickloader or in direct address programming 1 Keypad Assignment Tem...

Page 44: ...will display 000 to request a re entry Note Only the panel zones integration times are programmable EZM s will continue to use either 50 or 750 ms as selected by jumpers on the EZM In addition zone responses are en abled only when armed Direct Address Program Mode PRIORITY ARMING AREA 1 OPTION LEFT RIGHT blank blank Not Used blank 1 Enabled DATA ENTRIES PRIORITY ARMING AREA 2 OPTION LEFT RIGHT bla...

Page 45: ...4 2 1 0996 8 4 2 1 8 4 2 1 0932 8 4 2 1 No EOL Resistor 8 4 2 1 0997 8 4 2 1 8 4 2 1 0933 8 4 2 1 Trouble on Open 8 4 2 1 0998 8 4 2 1 8 4 2 1 0934 8 4 2 1 Trouble on Short 8 4 2 1 0999 8 4 2 1 8 4 2 1 0935 8 4 2 1 Zone Area 1 8 4 2 1 1000 8 4 2 1 8 4 2 1 0936 8 4 2 1 Zone Area 2 8 4 2 1 1001 8 4 2 1 8 4 2 1 0937 8 4 2 1 Interior Stay Bypass 8 4 2 1 1004 8 4 2 1 8 4 2 1 0940 8 4 2 1 Keypad Sounder...

Page 46: ...1 Entry Exit 2 8 4 2 1 1107 8 4 2 1 8 4 2 1 1043 8 4 2 1 Exit Entry Follower 8 4 2 1 1108 8 4 2 1 8 4 2 1 1044 8 4 2 1 Auto Reset 8 4 2 1 1109 8 4 2 1 8 4 2 1 1045 8 4 2 1 Swinger Shutdown 8 4 2 1 1110 8 4 2 1 8 4 2 1 1046 8 4 2 1 Chime 8 4 2 1 1111 8 4 2 1 8 4 2 1 1047 8 4 2 1 Abort Delay 8 4 2 1 1112 8 4 2 1 8 4 2 1 1048 8 4 2 1 Power up Delay 8 4 2 1 1113 8 4 2 1 8 4 2 1 1049 8 4 2 1 Day Zone O...

Page 47: ... 4 2 1 1186 8 4 2 1 Trouble Telco 3 8 4 2 1 1251 8 4 2 1 8 4 2 1 1187 8 4 2 1 Trouble Restore 3 8 4 2 1 1252 8 4 2 1 8 4 2 1 1188 8 4 2 1 No EOL Resistor 8 4 2 1 1253 8 4 2 1 8 4 2 1 1189 8 4 2 1 Trouble on Open 8 4 2 1 1254 8 4 2 1 8 4 2 1 1190 8 4 2 1 Trouble on Short 8 4 2 1 1255 8 4 2 1 8 4 2 1 1191 8 4 2 1 Zone Area 1 8 4 2 1 1256 8 4 2 1 8 4 2 1 1192 8 4 2 1 Zone Area 2 8 4 2 1 1257 8 4 2 1 ...

Page 48: ...1 Entry Exit 2 8 4 2 1 1363 8 4 2 1 8 4 2 1 1299 8 4 2 1 Exit Entry Follower 8 4 2 1 1364 8 4 2 1 8 4 2 1 1300 8 4 2 1 Auto Reset 8 4 2 1 1365 8 4 2 1 8 4 2 1 1301 8 4 2 1 Swinger Shutdown 8 4 2 1 1366 8 4 2 1 8 4 2 1 1302 8 4 2 1 Chime 8 4 2 1 1367 8 4 2 1 8 4 2 1 1303 8 4 2 1 Abort Delay 8 4 2 1 1368 8 4 2 1 8 4 2 1 1304 8 4 2 1 Power up Delay 8 4 2 1 1369 8 4 2 1 8 4 2 1 1305 8 4 2 1 Day Zone O...

Page 49: ... ADDRESS 1544 1548 RELAY EVENT 12 1544 1545 1546 1547 L R L R L R L R L R 1548 RELAY AREA Timeout Event ID COND ADDRESS 1549 1553 RELAY EVENT 13 1549 1550 1551 1552 L R L R L R L R L R 1553 RELAY AREA Timeout Event ID COND ADDRESS 1554 1558 RELAY EVENT 14 1554 1555 1556 1557 L R L R L R L R L R 1558 RELAY AREA Timeout Event ID COND ADDRESS 1559 1563 RELAY EVENT 15 1559 1560 1561 1562 L R L R L R L...

Page 50: ...ocations left and right digit STEP 5 RELAY EVENT CONDITION OPTIONS Each relay event can be assigned an alarm type and an activation condition also select a timeout type for each 5A Select Alarm Type and Timeout Type from Table 5A shown on next page enter in corresponding address location left digit 5B Select Activation from from Table 5B shown on next page enter in corresponding address location r...

Page 51: ...d Fail D 1 EZM Fail D 2 Quickloader Device Control D 5 General System Alarm D 8 Area 1 General System Alarm D 9 Area 2 General System Alarm D 0 Area 3 General System Alarm D B Area 4 General System Alarm F blank Relay Control Group 1 F 1 Relay Control Group 2 F 8 Entry Relay Area 1 F 9 Entry Relay Area 2 F 0 Entry Relay Area 3 F B Entry Relay Area 4 7 E Area 3 Fail to Close 7 F Area 4 KP Ambush 8 ...

Page 52: ... D to save NOTE These timers apply only to Supervised RF Transmitters see RF Transmitters in Easy Menu Driven Mode Programming Default blank blank from address 2029 2044 RF SUPERVISORY TIMER RF TRANSMITTER LEFT ADDR RIGHT Type 0 Window Door 2 Pt blank 2029 Type 1 Window Door 2 Pt blank 2030 Type 2 Window Door 2 Pt blank 2031 Type 3 Window Door 2 Pt blank 2032 Type 4 RESERVED blank 2033 Type 5 PIR ...

Page 53: ...power fails time and date restarts at 00 00 00 and a date of 01 01 04 January 1 2004 GEM RP1CAe2 Keypad 2286 XX GEM RP2ASe2 Keypad 2286 XX USER PROGRAM MODE PRELIMINARY INFORMATION The User Program Mode is covered in detail in the operating instructions for the keypad in use The Program Mode cannot be accessed while the communicator is transmitting except during the first three minutes after power...

Page 54: ... 6 digits directly using number buttons 0 9 4 Press the U button to save each code NOTE Press G 0 button to clear character at cursor To continue press P or Q button G E M I N I ARMED COMPUTERIZED SECURITY SYSTEM STATUS R 1 2 3 B 4 5 6 C 7 8 9 0 U NEXT YES P PRIOR NO Q AREA G UP INTERIOR BYPASS FIRE TBL SYS TBL CHIME Flashing GEM K3DGTL Keypad User Program Mode User Number User Code Direct Entry U...

Page 55: ... K4RF Keypads Up to 7 GEM RP2ASe2 GEM K2AS GEM RP3DGTL GEM K3DGTL and or GEM RP4RFC GEM K4RF keypads may be connected to the panel Keypads 1 7 Each must be configured for a keypad address In addition the keypad may be configured to disable a touchpad backlight b LCD backlight and c entry sounder Keypads are configured by the proper selection of jumpers Refer to the label on the circuit board insul...

Page 56: ...RAM MENU 10 AUTO BELL TEST ON ARMING ADDRESS 1421 28 AUTO BYPASS RE ENTRY ZONES EASY PROGRAM MENU 8 14 15 AUTO RESET AFTER BURGLARY OUTPUT TIMEOUT ADDRESS 1421 28 AUTO RESET ZONE OPTION 45 46 47 48 AUTO BYPASS RE ENTRY ZONE OPTION 45 46 47 48 AUTO BYPASS ZONE OPTION 45 46 47 48 AUTOMATIC INTERIOR BYPASS EASY EXIT ADDRESS 1424 28 AUX 1 AUX 2 OPTIONS EASY PROGRAM MENU 11 AUX OUTPUT ACTIVATED ON ALAR...

Page 57: ... DISABLE ZONE FAULT SCROLLING ADDRESS 1420 28 DON T CLEAR PGM2 OUTPUT WITH DISARM ADDRESS 1424 28 DOWNLOAD CALLBACK OPTIONS ADDRESS 2059 0526 0545 25 DOWNLOADING FROM A COMPUTER 4 DOWNLOADING FROM A COMPUTER 4 E EASY ARMING KEYPAD OPTIONS 42 EASY MENU DRIVEN PROGRAM MODE 5 EASY MENU DRIVEN PROGRAM MODE 4 EASY PROGRAM MENU GEM RP2ASE2 GEM K2AS KEYPAD 6 GEM RP3DGTL GEM K3DGTL AND GEM RP4RFC GEM K4RF...

Page 58: ... ARM DISARM CONTROL DEVICES EASY PROGRAM MENU 11 KEY FOB TRANSMITTERS AS ZONE INPUT DEVICES 18 19 EASY PROGRAM MENU 11 KEY FOB ZONE ASSIGNMENT 18 EASY PROGRAM MENU 11 KEYFOB LOW BATTERY 26 27 KEYFOB LOW BATTERY REPORTING OPTIONS ADDRESS 0705 32 KEYPAD ADDRESS 55 KEYPAD ADDRESS PROGRAM MODE DISPLAY 21 KEYPAD AUX 26 27 KEYPAD AUX KEYPAD OPTIONS 42 KEYPAD CONFIGURATION MODE 55 KEYPAD FIRE 26 27 KEYPA...

Page 59: ...AST RECEIVER FORMAT 16 RADIONICS FORMAT 30 RADIONICS MODEM 2 RECEIVER FORMAT 16 RADIONICS RECEIVER FORMAT 16 RELAY EVENT OPTIONS ADDRESS 1489 1608 49 RELAY EVENT OPTIONS ADDRESS 1609 1648 50 REMOTE DOWNLOADING 4 REPORT CANCEL WINDOW ADDRESS 2055 24 REPORT EVENT TELCO 1 ADDRESS 0840 26 REPORT EVENT TELCO 1 ADDRESS 0861 26 REPORT EVENT TELCO 1 ADDRESS 0869 26 27 REPORT EVENT TELCO 1 ADDRESS 0877 27 ...

Page 60: ... 3 ZONE OPTION 45 46 47 48 U UNIVERSAL HIGH SPEED FORMAT 30 UNIVERSAL HIGH SPEED RECEIVER FORMAT 16 USER CODES PROGRAMMING 54 USER OPTIONS 17 USER PROGRAM MODE 4 USER PROGRAM MODE 53 V VERI PHONE AUDIO PRIORITY OVER ALARMS ADDRESS 1424 28 VERI PHONE ZONES TRIP PGM2 OUTPUT ADDRESS 1424 28 VERTEX RECEIVER FORMAT 16 W WIRELESS TROUBLE ACTIVATES TELCO 1 ADDRESS 1423 28 WIRELESS TROUBLE ACTIVATES TELCO...

Page 61: ...NG OPTIONS 32 ADDRESS 0680 CONDITIONAL CLOSE REPORTING OPTIONS 32 ADDRESS 0681 CANCEL REPORTING OPTIONS 32 ADDRESS 0682 TEST TIMER REPORTING OPTIONS 32 ADDRESS 0683 TELCO FAIL REPORTING OPTIONS 32 ADDRESS 0684 RF REC TROUBLE REPORTING OPTIONS 32 ADDRESS 0685 MEMORY FAIL REPORTING OPTIONS 32 ADDRESS 0686 LOW BATTERY REPORTING OPTIONS 32 ADDRESS 0687 PANEL AC FAIL REPORTING OPTIONS 32 ADDRESS 0688 E...

Page 62: ...ND CLOSE STATUS 28 ADDRESS 1420 OPENING REPORT ONLY AFTER ALARM REPORT 28 ADDRESS 1420 STATUS REPORT 28 ADDRESS 1421 ACCESS CONTROL ON PGM2 OUTPUT 28 ADDRESS 1421 AUTO BELL TEST ON ARMING 28 ADDRESS 1421 AUTO RESET AFTER BURGLARY OUTPUT TIMEOUT 28 ADDRESS 1421 DISABLE KEYPAD INSTANT MODE 28 ADDRESS 1421 ENABLE LOCAL ALARM ON FIRST ZONE AND TRIP 28 ADDRESS 1421 ENABLE MANAGER S MODE 28 ADDRESS 1421...

Page 63: ...BLE GEM PRINT MODULE 29 ADDRESS 2051 ENABLE KEYPAD SET TIME DATE MESSAGE 29 ADDRESS 2052 LUG E15 AREA 1 ARMED AWAY ONLY 29 ADDRESS 2052 PGM ON RF TRANSMITTER TAMPER 29 ADDRESS 2053 DIGITAL DIALER RPT ENTER EXIT TEST MODE 29 ADDRESS 2053 DISABLE CALL WAITING ON 1ST ATTEMPT 29 ADDRESS 2053 ENABLE CP 01 EGRESS TONES ONLY 29 ADDRESS 2053 ENABLE CP 01 LIMITS 29 ADDRESS 2053 ENABLE KEYPAD 1 ONLY PROGRAM...

Page 64: ...X GEM P1664EX Programming Instructions L NAPCO Security Systems Page 64 WI1387 7 05 GEM P1664EX WIRING DIAGRAM ...

Reviews: