NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2
Page 4 Installation Instructions, Volume 2
TBL #
FIRE KEYPAD DISPLAY
BURG KEYPAD DISPLAY
KEYPAD TROUBLE DESCRIPTION
KEYPAD
TYPE
(GEMC-FK1 FIRE
KEYPAD OR GEMC-
BK1 BURG KEYPAD
FIRE
TROUBLE
TYPE
KEYPAD TROUBLE MESSAGES
E01-00
SYStrbl E01 xxx
MM/DD/YY HH:MM
'AC Power Failure'
'E01-000 SERVICE '
System AC Power failure/outage.
Check blown fuse or circuit breaker.
Fire & Burg
Keypads
'AC POWER FAIL '
'E01-00 SERVICE'
E02-00
SYStrbl E02 xxx
MM/DD/YY HH:MM
'Battery Trouble '
'E02-000 SERVICE '
System Battery Trouble.
Generated when there is either a depleted or damaged battery and/or
the battery charging circuit is not working.
If there has been a recent power failure, the battery may be partially depleted and must be re-
charged by the control panel. The control panel performs an automatic test of the battery every
100 seconds, at which time the trouble will clear if the battery has been recharged and the charging
circuit is functioning correctly. See also E63 below, the description for the GEMC-BM/PS low bat-
tery.
Fire & Burg
Keypads
'BATTERY TROUBLE '
'E02-00 SERVICE'
E03-00
SYStrbl E03 xxx
MM/DD/YY HH:MM
' Comm Failure '
'E03-000 SERVICE '
Communication Failure:
The system was not able to report to central station. If this is due to a
temporary interruption in the telephone service, the trouble can be cleared when the service is
restored by performing a Communication Test:
Fire Keypads
1. Enter code to unlock keypad and press MENU.
2. Press
MENU
until "
ACTIVATE DIALER TEST
" appears in the window.
3. Press
ENTER
to send a test signal to the central station.
4. Allow a minute or 2 for the call to reach the Central Station then press
RESET
.
Burg Keypads:
1. While disarmed, enter your User Code followed by
MENU
.
2. Answer
NO
until "
ACTIVATE DIALER TEST
" appears in the window.
3. Press
YES
to send a test signal to the central station.
Note:
Will also display if panel improperly programmed to report (Report Alarm, Report Codes,
Subscriber ID Numbers, etc. must be programmed correctly).
Fire & Burg
Keypads
E04-
NNNNNN
SYStrbl E04 xxx
MM/DD/YY HH:MM
'RFPnt Supv Trbl'
'E04-NNN XXXXXX'
Wireless Transmitter or SLC Point Supervision Failure.
A problem has been detected either in
a wireless transmitter or a burglary SLC Point. "XXXXXX" = The wireless/SLC device 6-digit ID
map number. NNN = associated zone number
Fire & Burg
Keypads
'WL/SLC TROUBLE'
'E04-NNN #XXXXXX'
E05-NN
SYStrbl E05 xxx
MM/DD/YY HH:MM
'RFPnt LowBattery'
'E05-NNN XXXXXX'
Wireless Transmitter Low Battery.
The battery in a wireless transmitter is low and should be
replaced. This transmitter is on the zone corresponding to the number NN.
Warning:
Replace
batteries only with the same type as specified on the sticker mounted on the device or in the instal-
lation instructions. Use of another battery may present a risk of fire or explosion. Do not recharge
or disassemble battery, or dispose of in fire. "XXXXXX" = The wireless device 6-digit ID map num-
ber. NN or NNN = Zone number.
Fire & Burg
Keypads
'WireLessLOW BATT'
'E05-NNN #XXXXXX'
E06-NN
SYStrbl E06 xxx
MM/DD/YY HH:MM
'RFRec NoResponse'
'E06-000 SERVICE '
RF Receiver or SLC Module response trouble.
NN = Receiver or SLC Module address (1-4).
Check connection to receiver/SLC module, check Receiver wiring is on correct bus Fire or Burg
and/or correct SLC connector SLC1 or SLC2, check to make sure address jumper on receiver or
SLC Module is correct. Make sure no duplicate addresses are used.
For Burglary keypads, NNN = receiver number (1-4).
Fire & Burg
Keypads
'RECrf/slc N0-RES'
'E06-NNN SERVICE'
E07-00
'Download Failure'
'E07-00 SERVICE'
Download attempt failure.
Fire & Burg
Keypads
'DOWNLOAD FAIL '
'E07-00 SERVICE'
E08-NN
SYStrbl E08 xxx
MM/DD/YY HH:MM
'Telco Line Fail '
'E08-NNN SERVICE '
Telephone line failure
(system trouble displays after a programmed delay of low on hook voltage
and no off hook line current from connected phone line). NN = Telco line number 1 or 2.
Fire & Burg
Keypads
'TELCO LN TROUBLE'
'E08-NN SERVICE'
E09-00
SYStrbl E09 xxx
MM/DD/YY HH:MM
' COLD START '
'E09-000 SERVICE '
A system cold start was performed
, erasing all programmed data in the control panel such as
the Dealer Program, Zone Description Data and Schedules.
Fire & Burg
Keypads
' NOT PROGRAMMED '
'E09-00 SERVICE'
E10-NN
'KPD/ACM TROUBLE '
'E10-NN SERVICE'
Burglary keypad or ACM response failure.
NN is keypad number (address 001-015). Check to
make sure correct Keypad address configured (no duplicates) and wired to Burg bus (not Fire bus).
Burg Keypad
Only
Auto-Reset
Auto-Reset
Auto-Reset
Auto-Reset
Auto-Reset
Auto-Reset
Auto-Reset
Auto-Reset
Latching