background image

NAPCO Security Systems

 

GEM-P1632 Installation Instructions

WI808B 8/98

Page 11

The GEM-P1632M can be used as part of a UL Central
Station Grade C, B, or A installation. Normally, a digital
communicator is classified as Grade C and may be classi-
fied Grade B if used with the specified Grade-A Local bell
and bell housing. A UL Central Station Grade-A installation
requires the use of a Napco RM3008 Relay Board and
Ademco 7720 Radio System. Refer to the installation
instructions furnished with each component for respective
installation requirements.
For a UL Commercial Grade-A Police Station Connection,
refer to GRADE-A LOCAL MERCANTILE INSTALLA-
TIONS, which follows. Use the M278 Line-Reversal Moni-
tor to provide basic line security; refer to the instructions
accompanying the M278 for other installation require-
ments.
For UL Commercial safe and vault applications, use a
UL-listed shock sensor suitable for metal enclosures. In-
stall tamper switches on front and rear of control-panel
enclosure.
Grade-A Local Mercantile Installations
A Grade-A Local Mercantile installation must use at least a
6.0AH standby battery. Programming must include Auto
Bell Test on Arming. Trouble on Night Open may not be
programmed for any zone.
The minimum requirements for a listed Grade-A Local
system include:

Low-Battery Annunciation.

An Ademco AB-12 Bell and Box (12-volt).

Program Auto Bell Test on Arming.

a maximum Entrance and Exit Delay of 60 seconds.

Interfacing to the Ademco 7720 Long-Range Wireless System

The RM3008 may be used to interface the GEM-P1632M control panel to the Ademco 7720 transmitter in order to meet
UL Central Station Grade-A or Grade-B requirements by using a digital communicator combined with one-way wireless.
(Normally, a digital communicator is Grade C, and may be Grade B if the specified Grade-A local bell is used.) Refer to
the wiring diagram which follows, and to the instructions furnished with the Napco and Ademco equipment for further
information concerning the DACT, listed compatible receiver and formats, Grade-A local bell and bell housing. Enable
Line Fault Test must be programmed.

Central Station Grade-B Requirements (Pending)

Wiring to the Ademco 7720 transmitter must be enclosed in rigid conduit when outside walls, or in flexible conduit when
inside walls or above ceilings, for the entire length up to the transmitter room. The transmitter room must be protected by
a UL listed intrusion detection unit that is connected to one of the input channels of the Ademco 7720. Relays must be
programmed to trip the Ademco 7720 for alarms on all protective circuits, including tampers, telco phone failure, 24-hour
test timer, transmitter low battery and ac loss. (See PCD3000 External Relay Control screen.) One zone on the
GEM-P1632M, programmed as a 24-Hour Zone, must supervise the radio.

Central Station Grade-A Requirements (Pending)

In addition to Grade-B Requirements (above), one relay on the RM3008 must be programmed to trip the Ademco 7720
when the telephone line fails. Daily openings and closings are required to be transmitted by the Napco panel along with
the 24-hour DACT test signal and DACT trouble conditions.

IN

STA

LLA

TI

ON

Summary of Contents for Gemini P1632

Page 1: ...WI808B 8 98 Napco 1998 R HARDWIRE WIRELESS...

Page 2: ...ity Systems Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service call toll free 800 645 9440 Internet http www napcos...

Page 3: ...17 KEYPAD CONFIGURATION MODE 18 Keypad Installation 18 Configuring the Keypads 18 BASIC OPERATION 21 User Codes Zone Descriptions 21 Arming and Disarming the System 22 Bypassing Zones 24 Alarm Indica...

Page 4: ...may be quickly and easily downloaded to the control panel using a PC compatible computer with Napco s PCD3000 Quickloader software and PCI2000 computer interface Or the panel may be programmed using...

Page 5: ...tary dial and TouchTone TM with Rotary backup Three 20 digit telephone numbers Backup Reporting Double Reporting Split Reporting 32 User Codes with Opening Closing Reporting by user AC Failure Reporti...

Page 6: ...IAL FIRE 16 5VAC TRANSFORMER BATTERY 12 VDC STANDBY CURRENT ALARM CURRENT STANDBY TIME 40VA 50VA 7 AH 120 mA 520 mA 1 24 Hours 40VA 50VA Two 7 AH 360 mA 280 mA 1 24 Hours 20VA 7 AH 120 mA 360 mA 1 24...

Page 7: ...78 Line Reversal Module PS3002 Power Supply Module 13 2Vdc 1 9A EOL2 2K End of Line Resistor Assy 2 2kW for Fire Circuit FT2200 End of Line Relay Resistor Supervisory Module RB1000 Relay Board RBATH1...

Page 8: ...anic connect only to UL listed holdup devices All zones must be programmed for Priority Do not program any zones for Keyswitch Arming System must be serviced at least once every 3 years Residential Fi...

Page 9: ...es for the machine screws it may be discarded after use Keypad A keypad should be located near each exit entry door The keypad features a handy pull up reference label Before mounting the keypad onto...

Page 10: ...tility room furnace room and hallways Heat detec tors rather than smoke detectors are recommended in kitchens attics and garages due to conditions that may result in false alarms and improper operatio...

Page 11: ...Range Wireless System The RM3008 may be used to interface the GEM P1632M control panel to the Ademco 7720 transmitter in order to meet UL Central Station Grade A or Grade B requirements by using a dig...

Page 12: ...transmitters proceed as follows Note Wireless systems have not been investigated by UL 1 Enter the Fault Find Mode 2 Fault a point of the transmitter to be tested by opening the loop If the signal st...

Page 13: ...e connected When connecting a mechanical bell it must be supervised using a 2 2k Ohm resistor To connect 8 Ohm Speakers use a Siren Driver with the proper polarity observed NOTE Refer to the GEM P1632...

Page 14: ...ted if the longest cable run from the panel to the farthest keypad daisy chained or home run is less than 1000 feet The maximum distance for seven keypads is 300 feet using 22 AWG wire NOTE When runni...

Page 15: ...the use of EZM Modules To do so simply select EZ Zone Doubling in programming refer to the GEM P1632 Programming Instructions and connect zones as shown above NOTE If both zones in a zone pair configu...

Page 16: ...ire smoke detectors are connected to zones 7 8 If Fire Alarm Verification is desired to reset the smoke detectors select this option for the desired fire zone zone 7 or 8 WIRING CONNECTIONS 4 WIRE SMO...

Page 17: ...nto an approved USOCRJ31X jack or a CA31A jack for Canadian installations The Telco Line is used by the control panel to dial the central station and for downloading This line should not be connected...

Page 18: ...er e EZM address and f zone response To enter the GEM RP1CAe2 Configuration Mode 1 Move jumper JP1 located at the upper right corner of the control panel board from Pins 1 2 top two to Pins 2 3 bottom...

Page 19: ...to continue or press the button to exit Zone Response The normal loop response of each keypad expansion zone is 750mS however the response time of any zone can be reduced to 50mS as follows 1 Of the f...

Page 20: ...ed that a GEM RP1CAe2 be selected as Keypad 1 Assign the keypad address number by selecting Jumpers J1 3 in accor dance with the table at left Note 1 Keypads are factory supplied with no jumpers insta...

Page 21: ...ay be programmed or it may be programmed as a two digit code for the purposes of quick arming Arm Only Code Programmable in Dealer Program Mode only An Arm Only Code may only be used to arm the area i...

Page 22: ...r disarm an Arm Only Code may only be used to arm Arming To arm enter a valid User Code then press the button If a wrong code is entered the keypad will display The green STATUS LED will go off the re...

Page 23: ...n be armed The display will read then automatically scroll through all unsecured zones If a system trouble is indicated display the system trouble Area Arming Manager s Mode In a partitioned system ei...

Page 24: ...forward or backward using the and the buttons respectively To return to normal keypad operation press the button The keypad will automatically return to its normal operating mode if no activity is de...

Page 25: ...nd a 2 second warning and the keypad will begin a 15 minute countdown with the sounder pulsing The sounder may be silenced by pressing the button but it will come back on one minute before arming With...

Page 26: ...Y Battery below 11 volts If not recharged within 24 hours replace it E03 00 COMM FAIL Unsuccessful communication to central station Note Will also display if panel improperly programmed to report i e...

Page 27: ...lighting disabled cut Jumpers W1 W2 W3 2 Backlighting disabled cut Jumpers A B C 3 Add 0 010A for each energized relay 4 Standby Time in Hours 1 STANDBY CURRENT X Amps AH STANDBY CURRENT Amps DEVICE Q...

Page 28: ...board be necessary use this wiring legend to relocate wire leads to their proper terminals Enter wire identification number or color code in WIRE NUMBER column and enter wire function in DESCRIPTION...

Page 29: ...RT FUNCTION MODE Keypad Commands NEXT YES PRIOR NO AREA Scroll Down Scroll Up Exit Yes No Press Bell Test Activated Chime Toggle On Off Exit Automatically No Yes Yes System to Arm in number of hours e...

Page 30: ...Bypassed Display Activated Bell Test Activated Chime Toggle On Off Exit Automatically Reset System Trouble Exit Automatically Activate Fault Find Download Activated Keypad Commands No No No No No No N...

Page 31: ...Zone Numbers in Area 1 Enter Entry Exit Zone Numbers in Area 1 Enter Central Station 1 Telephone Number No No Yes Yes Enter Number of Keypads in Area 1 Enter of Zones in Area 1 Press at any time Go to...

Page 32: ...er Program Option Enabled Bell Test Activated Chime Toggle On Off Exit Automatically No No Yes Yes System to Arm in number of hours entered w delay Exit Automatically Download Activated No No No Yes Y...

Page 33: ...1 ALARM CURRENT CAN BE INCREASED BY REDUCING STANDBY CURRENT BY THE SAME AMOUNT 2 THE FOLLOWING DEVICES MAY BE PLACE ON THE REMOTE BUS GEM RP1CAe2 GEM RP2ASe2 GEM EZM816 GEM X10 GEM RECV8 GEM RECV16...

Page 34: ...GEM P1632 Installation Instructions NAPCO Security Systems WI808B 8 98 Page 34 NOTES...

Page 35: ...ary the user should consult the dealer or an experienced radio television technician for additional suggestions The user may find the following booklet prepared by the Federal Communications Commissio...

Page 36: ...ssumes nor autho rizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be liabl...

Reviews: