LIBRA LIB-P432EX Series Programming Instructions 

NAPCO Security Systems 

Page 32

 

ZONE OPTIONS - ZONES 17 TO 32 (ADDRESS 1029-1144) 

 

 

 

ZONES 17 

 24 

 

ZONES 25 

 32 

 

ZONE FEATURES 

ADDR  Z17  Z18  Z19  Z20  Z21  Z22  Z23  Z24  ADDR  Z25  Z26  Z27  Z28  Z29  Z30  Z31  Z32 

 

 

 

 

 

Priority 

1029 

 

 

 

 

 

 

 

 

1093 

 

 

 

 

 

 

 

 

 

Priority with Bypass 

1030 

 

 

 

 

 

 

 

  1094 

 

 

 

 

 

 

 

 

 

Auto-Bypass 

1031 

 

 

 

 

 

 

 

  1095 

 

 

 

 

 

 

 

 

 

Selective Bypass 

1032 

 

 

 

 

 

 

 

  1096 

 

 

 

 

 

 

 

 

 

Keyswitch Arming 

1033 

 

 

 

 

 

 

 

  1097 

 

 

 

 

 

 

 

 

 

Auto-Bypass Re-entry 

1034 

 

 

 

 

 

 

 

  1098 

 

 

 

 

 

 

 

 

 

Pre-Alarm Warning 

1035 

 

 

 

 

 

 

 

  1099 

 

 

 

 

 

 

 

 

 

Never Arm 

1036 

 

 

 

 

 

 

 

  1100 

 

 

 

 

 

 

 

 

 

24-Hour Zone 

1037 

 

 

 

 

 

 

 

  1101 

 

 

 

 

 

 

 

 

 

Alarm Output 

1038 

 

 

 

 

 

 

 

  1102 

 

 

 

 

 

 

 

 

 

 

Pulsed Alarm Output 

1039 

 

 

 

 

 

 

 

  1103 

 

 

 

 

 

 

 

 

 

PGM1 Output 

1040 

 

 

 

 

 

 

 

  1104 

 

 

 

 

 

 

 

 

 

PGM2 Output 

1041 

 

 

 

 

 

 

 

  1105 

 

 

 

 

 

 

 

 

 

 

Entry/Exit 1 

1042 

 

 

 

 

 

 

 

  1106 

 

 

 

 

 

 

 

 

 

Entry/Exit 2 

1043 

 

 

 

 

 

 

 

  1107 

 

 

 

 

 

 

 

 

 

 

Exit/Entry Follower 

1044 

 

 

 

 

 

 

 

  1108 

 

 

 

 

 

 

 

 

 

Auto Reset 

1045 

 

 

 

 

 

 

 

  1109 

 

 

 

 

 

 

 

 

 

Swinger Shutdown 

1046 

 

 

 

 

 

 

 

  1110 

 

 

 

 

 

 

 

 

 

 

Chime 

1047 

 

 

 

 

 

 

 

  1111 

 

 

 

 

 

 

 

 

 

Abort Delay 

1048 

 

 

 

 

 

 

 

  1112 

 

 

 

 

 

 

 

 

 

Power-up Delay 

1049 

 

 

 

 

 

 

 

  1113 

 

 

 

 

 

 

 

 

 

Day Zone Open 

1050 

 

 

 

 

 

 

 

  1114 

 

 

 

 

 

 

 

 

 

Day Zone Short 

1051 

 

 

 

 

 

 

 

  1115 

 

 

 

 

 

 

 

 

 

Alarm on Day Zone 

1052 

 

 

 

 

 

 

 

  1116 

 

 

 

 

 

 

 

 

 

 

Alarm Telco 1 

1053 

 

 

 

 

 

 

 

  1117 

 

 

 

 

 

 

 

 

 

Alarm Restore 1 

1054 

 

 

 

 

 

 

 

  1118 

 

 

 

 

 

 

 

 

 

Trouble Telco 1 

1055 

 

 

 

 

 

 

 

  1119 

 

 

 

 

 

 

 

 

 

Trouble Restore 1 

1056 

 

 

 

 

 

 

 

  1120 

 

 

 

 

 

 

 

 

 

Alarm Telco 3 

1057 

 

 

 

 

 

 

 

  1121 

 

 

 

 

 

 

 

 

 

Alarm Restore 3 

1058 

 

 

 

 

 

 

 

  1122 

 

 

 

 

 

 

 

 

 

Trouble Telco 3 

1059 

 

 

 

 

 

 

 

  1123 

 

 

 

 

 

 

 

 

 

Trouble Restore 3 

1060 

 

 

 

 

 

 

 

  1124 

 

 

 

 

 

 

 

 

 

No EOL Resistor 

1061 

 

 

 

 

 

 

 

  1125 

 

 

 

 

 

 

 

 

 

Trouble on Open 

1062 

 

 

 

 

 

 

 

  1126 

 

 

 

 

 

 

 

 

 

Trouble on Short 

1063 

 

 

 

 

 

 

 

  1127 

 

 

 

 

 

 

 

 

 

 

Zone Area 1 

1064 

 

 

 

 

 

 

 

  1128 

 

 

 

 

 

 

 

 

 

Zone Area 2 

1065 

 

 

 

 

 

 

 

  1129 

 

 

 

 

 

 

 

 

 

Interior (Stay) Bypass 

1068 

 

 

 

 

 

 

 

  1132 

 

 

 

 

 

 

 

 

 

Keypad Sounder on Alarm 

1069 

 

 

 

 

 

 

 

  1133 

 

 

 

 

 

 

 

 

 

 

Fire 

1071 

 

 

 

 

 

 

 

  1135 

 

 

 

 

 

 

 

 

 

Fire Alarm Verification 

1072 

 

 

 

 

 

 

 

  1136 

 

 

 

 

 

 

 

 

 

Zone ANDing Group 1 

1074 

 

 

 

 

 

 

 

  1138 

 

 

 

 

 

 

 

 

 

Zone ANDing Group 2 

1075 

 

 

 

 

 

 

 

  1139 

 

 

 

 

 

 

 

 

 

Zone ANDing Group 3 

1076 

 

 

 

 

 

 

 

  1140 

 

 

 

 

 

 

 

 

 

Zone ANDing Group 4 

1077 

 

 

 

 

 

 

 

  1141 

 

 

 

 

 

 

 

 

 

Sensor Watch 

1078 

 

 

 

 

 

 

 

  1142 

 

 

 

 

 

 

 

 

 

RESERVED 

1079 

 

 

 

 

 

 

 

 

1143 

 

 

 

 

 

 

 

 

 

Chime 2 

1080 

 

 

 

 

 

 

 

  1144 

 

 

 

 

 

 

 

 

  

When the Easy Program Menu is used, these features are enabled by default. 

  

Enabled when "Enable SIA CP-01 Features?" is activated (Answer YES (

p

) in the EZ Programming Menu). 

  

Disabled when "Enable SIA CP-01 Features?" is activated (Answer YES (

p

) in the EZ Programming Menu).  Disable Auto-Reset on non-fire zones for SIA CP-01 installations. 

 

Zone Area 3 

1066 

 

 

 

 

 

 

 

  1130 

 

 

 

 

 

 

 

 

 

Zone Area 4 

1067 

 

 

 

 

 

 

 

  1131 

 

 

 

 

 

 

 

 

DEFAULTS: 

The zone options indicated are automatically set after exiting the Easy Menu Driven Mode.  

Priority, Selective By-

pass, Alarm Output, Auto Reset, Swinger Shutdown

 and 

Zone Area 1

 are enabled for the total number of zones entered in "

OF ZONES IN AREA1 ENTER # ZONES

".  

Alarm Telco 1

 is enabled for the zone number(s) entered in "

REPORT ALL ZONES TO CENTRAL ZONES? 

Y/N

".  

Entry/Exit 1

 and 

Chime

 are enabled for the zone number(s) entered in "

ENTRY/EXIT ZONES ENTER ZONE #

".  

Exit/Entry Follower 

and 

Interior Bypass

 are enabled for the zone number(s) entered in "

INTERIOR ZONES ENTER ZONE #

".  

Pulse Alarm Output

 is enabled 

for the zone number(s) entered in "

FIRE ZONES ENTER ZONE #

".  

Fire 

is enabled for the zone number(s) entered in "

FIRE ZONES ENTER 

ZONE #

".    

Summary of Contents for LIBRA-P432EX Series

Page 1: ...he battery 3 Configure the keypad see page 42 4 Access the Easy Menu Driven Dealer Program Mode Press 456789 w Press NO q until ACTIVATE PROGRAM Y N appears on the keypad display Press YES p to Enter...

Page 2: ...s manual as well The Instant z button and the AWAY q button operate identically in Program Mode for both keypads These buttons are also used to answer NO or PRIOR to questions that appear on the keypa...

Page 3: ...ormat 8 Enter User Codes 8 RF Transmitter Points 9 Key Fob Transmitters as Arm Disarm Control Devices 9 Key Fob Transmitters as Zone Input Devices 10 Enter Zone Descriptions 10 Enter Date 10 Enter Tim...

Page 4: ...the Dealer Program Mode wherein data is entered at the keypad by location This mode is accessed from the Easy Menu Driven Program Mode by pressing the y button at any time User Program Mode Keypad Pr...

Page 5: ...nes in Area 1 50mS Loop Response Zones Aux Output Activated on Alarm Zones Sensor Watch Zones Keypad Sounder on Alarm Zones Auto Bypass re entry Zones Enable no EOLR Zones Enable Telco Line Fault Test...

Page 6: ...ectly enter each zone number including leading zeros Press u to save and repeat for any additional zone s press p to proceed NOTE Exit Entry Entry time of 30 seconds will automatically be programmed I...

Page 7: ...leading zeros Press u to save and then repeat for any additional zone s Press p to proceed NOTE A PGM2 Timeout of 15 minutes will automatically be programmed Sensor Watch Zones New Program Only Enter...

Page 8: ...or p to proceed Enter User Codes Press w to set cursor For default program enter up to 64 User Codes with Area 1 2 3 4 Options Press the w button once to set the cursor to the User Code Press 0 throu...

Page 9: ...ammed Transmitter 287613 1 point 1 will be mapped to Zone 6 5 Enter Zone 09 6 Close point 1 loop and open point 2 loop 7 Remove the transmitter battery then re install it The keypad will beep once to...

Page 10: ...on Press u to save Press NEXT r or p to proceed Dealer Code Directly enter the Dealer Code default 456789 using 0 through 9 buttons Press u to save Re enter the Dealer Code to verify the previous code...

Page 11: ...splay and accept data in number format For example Zone Features are turned on by the pressing of keypad buttons 1 through 8 with the activated Zone s displaying the corresponding decimal digit replac...

Page 12: ...automatically moving to the right upon each key press EXAMPLE DECIMAL Format with the GEM DXRP1 DXK1 Program Abort Delay to be 15 seconds DETERMINE THE DATA ENTRIES 1 Referring to SYSTEM DELAYS TIMEOU...

Page 13: ...1 Referring to SYSTEM DELAYS TIMEOUTS in the Programming Worksheets that follow the Chime Timeout is located at address 1418 In the Chime Timeout Options table the data entries needed to assign a time...

Page 14: ...ws software following any keypad programming and that the PCD Windows s error check feature be utilized to reduce the possibility of programming omissions or conflicts 3 Keep the Keypad Programming Wo...

Page 15: ...is page and on the following pages are automatically set after exiting the Easy Menu Driven Mode 1 Enter delay timeout in corresponding address locations above Note All entries for address 1418 are in...

Page 16: ...AT In Pager Format reporting the message typically begins with 00 However for some pager services this will cause the Pager s Voice Mail feature to activate This option allows you to program these dig...

Page 17: ...Ambush Code is selected and Address 2045 is not left blank then the 2 digit Global Ambush Code is the two digits entered in address 2045 Enter in address location both 1st and 2nd digits valid entries...

Page 18: ...FIRE KEYPAD AUX KEYPAD TAMPER FAIL TO OPEN FAIL TO CLOSE Keyfob Low Batt 1 2 3 4 5 6 7 8 Pulsed Alarm Output 0872 Alarm Output 0873 PGM1 Output 0874 PGM2 Output 0876 Report Event Telco 1 0877 Report...

Page 19: ...F 3 Reset Day Zone with Arm Disarm Only OFF 3 Wireless Trouble Activates Telco 3 OFF 4 Enable Residential Fire OFF 4 Enable Alarm Output on Telco Fail only when Armed OFF 5 Disable Keypad Function Mod...

Page 20: ...for dial tone F Ignore location Default for CS Receiver 1 Tele phone Number depends on Easy Menu Question C E N T R A L PHONE Default blank across digits 1 20 for CS Receiver Telephone Num bers 2 and...

Page 21: ...RIGHT DIGITS 1 4 0596 0597 0598 0599 CS Telco 3 Sub scriber Event ID Number Area 1 ADDRESS 0648 0651 RIGHT DIGITS 1 4 0648 0649 0650 0651 CS Telco 3 Sub scriber Opening Closing ID Number Area 3 ADDRES...

Page 22: ...0 0705 CS AREA SYSTEM REPORTING OPTIONS ADDRESS 0785 0786 0788 Default blank blank DISABLE OPENING REPORTS LEFT DIGIT RIGHT DIGIT SUM OF DATA VALUES blank ADDRESS 0785 NOTE If neither Touch tone Diali...

Page 23: ...al requires a Set Unset code Enter level 2 3 4 to come alive The keypad will stay alive Normal for 128 seconds default or for a time in a programma ble EEProm location in seconds This location 2060 co...

Page 24: ...ZONE 22 ZONE 23 ZONE 24 0740 0741 0742 0743 NOTE If Zone Doubling Address 1423 is not enabled then Zones 1 4 are included in the control panel and Zones 5 32 are wireless Zones If Zone Doubling is en...

Page 25: ...n not available 3 Press u to save USERS 49 56 USERS 57 64 Enable Users to Report Opening and Closings ADDR U49 U50 U51 U52 U53 U54 U55 U56 ADDR U57 U58 U59 U60 U61 U62 U63 U64 1 2 3 4 5 6 7 8 1 2 3 4...

Page 26: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 26 This page left blank intentionally...

Page 27: ...sarm Default Option Disarming Area 1 ON 1 Area 1 Pulsed Burg Output Silenced OFF 2 Area 2 Pulsed Burg Output Silenced OFF 3 Area 3 Pulsed Burg Output Silenced OFF 4 Area 4 Pulsed Burg Output Silenced...

Page 28: ...eypad Area Assignment KEYPAD TYPE Up to 7 key pads may be programmed if they are connected NOTE See Keypad Configura tion Mode 1 Select keypad type for each keypad from the tables shown 2 Enter data i...

Page 29: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 29 This page left blank intentionally...

Page 30: ...d to a new global value Address 2062 accepts three decimal digits which are multiplied by 10 milli seconds to get a new value that replaces the default value of 750ms If the loca tion is set to 000 th...

Page 31: ...98 Trouble on Short 0935 0999 Zone Area 1 0936 1000 Zone Area 2 0937 1001 Zone Area 3 0938 1002 Keypad Sounder on Alarm 0941 1005 2 Wire Smoke Detectors 0942 1006 Fire 0943 1007 Fire Alarm Verificatio...

Page 32: ...1129 Interior Stay Bypass 1068 1132 Keypad Sounder on Alarm 1069 1133 Fire 1071 1135 Fire Alarm Verification 1072 1136 Zone ANDing Group 1 1074 1138 Zone ANDing Group 2 1075 1139 Zone ANDing Group 3...

Page 33: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 33 This page left blank intentionally...

Page 34: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 34 This page left blank intentionally...

Page 35: ...LAY EVENT 15 1559 1560 1561 1562 1563 RELAY AREA TIMEOUT EVENT ID COND ADDRESS 1554 1558 RELAY EVENT 14 1554 1555 1556 1557 1558 RELAY AREA TIMEOUT EVENT ID COND ADDRESS 1574 1578 RELAY EVENT 18 1574...

Page 36: ...and Timeout Type from Table 5A on next page enter in corresponding left address location 5B Select Activation Conditions from Table 5B on next page enter in corresponding right address location STEP 2...

Page 37: ...General System Alarm D 8 Area 1 General System Alarm D 9 Area 2 General System Alarm D 0 Area 3 General System Alarm D B Area 4 General System Alarm F blank Relay Control Group 1 F 1 Relay Control Gr...

Page 38: ...nutes 2 Enter in corresponding address locations below right nibble 3 Press u to save NOTE These timers apply only to Supervised RF Transmitters see RF Transmitters in Easy Menu Driven Mode Programmin...

Page 39: ...chedules can only be programmed again with the Downloading Software If power fails time and date restarts at 00 00 00 and a date of 01 01 04 January 1 2004 2285 XX H 2286 XX H USER PROGRAM MODE PRELIM...

Page 40: ...s The cursor will then advance to the User Code and read the existing code if any Enter the new User Code using the number buttons 0 9 If an old code is displayed program over it To erase the digit at...

Page 41: ...change to uppercase Press u to save To advance to the next zone or to any other zone move the cursor to the displayed zone number i e 01 using w and x Change the zone number using keys 0 through 9 Ent...

Page 42: ...M DXRP1 GEM DXK1 keypad must be configured for a keypad tactile beep b entry sounder c keypad address and d compatibility number To enter the Keypad Configuration Mode 1 Move jumper JP1 located in the...

Page 43: ...press the y button to exit Zone Response THIS FEATURE IS NOT COMPATIBLE WITH THE LIB P432EX CON TROL PANEL DO NOT CHANGE THIS SETTING Press the w button to continue or press the y button to exit Prog...

Page 44: ...ccount Number Central Station Receiver 1 Format blank Ademco Slow Silent Knight Slow 2 Radionics Fast 3 Silent Knight Fast 4 Radionics DCI Franklin Slow 5 Universal High Speed B SIA C Ademco Point ID...

Page 45: ...RF Transmitter Points XMTR ZONE CHECK SUM POINT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 RF ID printed on xmtr box XMTR ZONE CHECK SUM POINT 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 RF ID printe...

Page 46: ...9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 CHARACTERS AVAILABLE See below Dealer Code Charact...

Page 47: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 47 This page left blank intentionally...

Page 48: ...NTROL OPTIONS ADDRESS 1473 1488 27 AREA BURG OUTPUT SILENCED 27 AREA OPTIONS 8 9 AUTO ARMING DISARMING USER 65 25 AUTO BELL TEST ON ARMING 19 AUTO BYPASS RE ENTRY ZONES 7 AUTO RESET AFTER BURGLARY OUT...

Page 49: ...AT 22 DISABLE ZONE FAULT SCROLLING 19 DISARMING AREAS 1 4 BURG OUTPUT SILENCED 27 DON T CLEAR PGM2 OUTPUT WITH DISARM 19 DOWNLOAD FUNCTION OVERVIEW 4 DOWNLOAD CALLBACK OPTIONS ADDRESS 0526 0545 16 DOW...

Page 50: ...KEYPAD ADDRESS 42 KEYPAD AUX 17 KEYPAD AUX KEYPAD OPTION 28 KEYPAD CONFIGURATION MODE 42 KEYPAD ENTRY SOUNDER 42 KEYPAD FIRE 17 KEYPAD FIRE KEYPAD OPTION 28 KEYPAD NUMBER ASSIGNING 42 KEYPAD OPTIONS...

Page 51: ...MING USER 66 25 R RADIONICS FAST 20 RADIONICS DCI 20 RELAY CONTROL EXTERNAL ADDRESS 1489 1648 35 REMOTE DOWNLOADING OVERVIEW 4 REPORT CANCEL WINDOW ADDRESS 2055 15 REPORT EVENT TELCO 1 ADDRESS 0840 17...

Page 52: ...ORT ZONE OPTION 31 32 33 34 TROUBLE RESTORE ADDRESS 0672 22 TROUBLE RESTORE 1 ZONE OPTION 31 32 33 34 TROUBLE RESTORE 3 ZONE OPTION 31 32 33 34 TROUBLE TELCO 1 ZONE OPTION 31 32 33 34 TROUBLE TELCO 3...

Page 53: ...ERVISION 22 ADDRESS 0675 XMITTER TAMPER 22 ADDRESS 0677 OPENING 22 ADDRESS 0678 CLOSING 22 ADDRESS 0679 OPENING AFTER ALARM 22 ADDRESS 0680 CONDITIONAL CLOSE 22 ADDRESS 0681 CANCEL 22 ADDRESS 0682 TES...

Page 54: ...ESS 0872 0887 SYSTEM OPTIONS 18 ADDRESS 0873 ALARM OUTPUT 18 ADDRESS 0874 PGM1 OUTPUT 18 ADDRESS 0876 PGM2 OUTPUT 18 ADDRESS 0877 REPORT EVENT TELCO 1 18 ADDRESS 0879 REPORT EVENT TELCO 3 18 ADDRESS 0...

Page 55: ...Y CONTROL EXTERNAL 35 ADDRESS 2029 2044 RF RECEIVER SUPERVISORY TIMER OPTIONS 38 ADDRESS 2045 GLOBAL AMBUSH CODE 17 ADDRESS 2045 SYSTEM OPTIONS 17 ADDRESS 2050 SENSOR WATCH TIME 15 ADDRESS 2050 SYSTEM...

Page 56: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 56 LIB P432EX WIRING DIAGRAM...

Page 57: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 57 LIB P432EXT WIRING DIAGRAM...

Page 58: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 58 LIB P432EXT 230 WIRING DIAGRAM...

Page 59: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 59 NOTES...

Page 60: ...60 R Publicly traded on NASDAQ Symbol NSSC NAPCO Security Group Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service...

Reviews: