14
WI1372 XP-600 Installation Instructions
[15]Line Cut Time-to-Fail
Enable this feature by programming the
delay time required to declare a line cut
failure. Programming 000 will disable line
cut detection.
[16]Wireless Supervisory Timer
A transmitter will send a transmission every
time it is tripped; when there is no activity,
the transmitter sends a supervisory
transmission about once an hour. If the
receiver does not receive any signal (either
a trip or a status) from a transmitter in the
time specified, a system trouble ‘RF
Supervisory Failure' will be indicated at the
keypad. Timer is programmable from 1-26
hours; 0 means NO supervision.
[17]Wireless Smoke Supervisory Timer
A smoke detector will send a transmission
every time it is tripped; when there is NO
activity, the smoke detector sends a
supervisory transmission about once an
hour. If the receiver does not receive a
signal (either a trip or a status) from a
transmitter in the time specified, a system
trouble ‘RF Supervisory Failure' will be
indicated at the keypad. The Supervisory
timer is programmable from 1-8 hours; 0
means NO supervision.
[18]Test Timer Offset
Enter the time, in hours, that a Test Timer
will be reported after Dealer Mode has been
exited. With the default value of 12, the test
timer will be sent 12 hours after exiting
Dealer Mode. The test timer can also be
offset using NAPCO PCD3000 Downloading
Software. On power up the test timer is sent
immediately. Follow the commands below
to offset the test timer using Quickloader
Software:
From the Status Screen
•
Press
F6
•
Select
M
iscellaneous Control
•
Select
T
est Timer Offset
•
Enter New Test Timer Offset: 12
hours
•
Enter
u
to advance the test timer
due in time by 12 hours.
System Features
[20]Keypad Features 1
(1) Enable Keypad Fire
(
ee
)
Additional Programming required:
Select reporting to Telco 1 [36-1] or Telco 3
[56-1].
(2) Enable Keypad AUX
(
ff
)
Additional Programming required:
Select reporting to Telco 1 [36-2] or Telco 3
[56-2].
(3) Enable Keypad Panic
(
gG
)
Additional Programming required:
Select reporting to Telco 1 [36-3] or Telco 3
[56-3].
(
4) Enable Ambush -
If enabled, the 6th
User Code will send an Ambush report
when entered to disarm the system.
Additional Programming required:
Program User 6 Arm/Disarm Code.
Select reporting to Telco 1 [36-2] or Telco 3
[56-2].
UL Installations:
If Keypad Fire [20-1] is
enabled, the keypad must be mounted
within (3) three feet from the Control Panel.
[21]Keypad Features 2
(1) Audible Panic
- Keypad Panic will not
turn the Bell on unless this option is
programmed.
(2) Exit/Entry with Urgency
- select to give
an audible indication of Exit and Entry times.
During the last 10 seconds of entry and exit
time, the keypad sounds a distinct sound to
indicate the premises must be left or the
panel must be disarmed.
(3) Display Bypassed (Armed)
- Select to
display bypassed zones while the panel is
armed.
(4) Disable Code Entry Beeps -
Program
to disable keypad beeping on valid code and
function entries.