27
-4 +5 +6
XP-600 Terminals
1 2 +3
GEM-RECV-XP8
16 VAC 20 VA
TRANSFORMER
NAPCO TRF12
(OR EQUIVALENT
SEE WI1372).
Class 2
Transformer.
DO NOT
connect to
switched
outlet.
+
RED
(+)
+
BLACK
E1
E2
RECHARGEABLE
BATTERY
12 VDC 4AH OR 7AH
This equipment should be installed in accordance with Chapter
2 of the National Fire Alarm Code, ANSI/NFPA 72-1996
(National Fire Protection Association Batterymarch Park,
Quincy MA 02269). and local codes. Information describing
proper installation, operation, testing, maintenance, evacuation
planning, and repair service is to be provided with this
equipment. UL Listed Energy Cable is required.
ALL OUTPUTS ARE CURRENT LIMITED
WARNING
TO PREVENT RISK
OF ELECTRIC SHOCK
DISCONNECT TELEPHONE
LINES PRIOR TO
SERVICING
EARTH
GROUND
FIRE
BELL
P
ro
gr
am
m
abl
e
Ou
tp
ut
PGM
(-)
12
+PWR
+10 -11 +12 -13 14 15 16 17 18 19
-7 +8 -9
GND +PWR GND GREEN
TIP RING
TIP
RING
PHONE
(Supervised)
To RJ31X
2.2K EOLR
2.2K EOLR
(SUPERVISED)
(E)
+
+
+
+
COLD WATER GROUND CONNECTION
USE ONLY COLD-WATER PIPE OR
BURIED GROUND ROD. USE AT LEAST
#16 AWG WIRE.
TELCO
RE
D
GR
N
GR
AY
BR
N
FIRE
PWR
LO
A
D
50 mA
M
AX
.
REMOTE BUS
ZONE 3
(E)
2.
2K
(E)
2.
2K
ZONE 6
ZONE 5
(Z)
ZONE 1
(E)
2.
2K
ZONE 4
(Z)
(E)
RED
BL
K
GRN
Fire Loop
In
4-Wire Fire Wiring
Power
Out (+)
Power
Out (-)
Power
In (-)
Fire Loop
Out
RED
BLACK
BROWN
BROWN
FT2200
8
7
8
9
Power
In (+)
Fire Power
Ground
Fire Power
Fire
2.2K
2.2K
Normally Open
Zone Wiring
Wire the normally open
contact as shown
(Zone 4). Program
the zone for
Open Circuit
[06]
operation.
ZONE 2
3.
9K
(Z)
ZONE 1
(E)
2.
2K
ZONE 4
A
U
X
P
O
W
E
R O
U
T
P
UT 1
0
-1
2
.5
V
DC
(1) ALL ZONE RESISTORS MUST BE INSTALLED, EVEN IF
ZONE IS NOT USED.
(2) COMBINED STANDBY = KEYPAD C AUX POWER
C FIRE POWER + PGM CURRENT.
(3) RESIDENTIAL FIRE REQUIRES A 7AH BATTERY.
(4) UNIT INTENDED TO BE MOUNTED VERTICALLY ON WALL.
(5) REFER TO WI1372 FOR COMPATIBLE TWO WIRE SMOKE
DETECTORS. DO NOT MIX DIFFERENT MODELS.
(6) THIS PANEL SHALL BE CHECKED BY A QUALIFIED
TECHNICIAN AT LEAST ONCE EVERY THREE YEARS.
(7) THIS PANEL SUPPORTS ONLY ONE SMOKE DETECTOR IN
ALARM.
(8) USE ONLY ONE BELL IN RESIDENTIAL FIRE APPLICATION.
(9) SYSTEM MUST BE TESTED AT LEAST ONCE A WEEK IN THE
AC/BATTERY MODE AND IN THE BATTERY-ONLY MODE.
(CONTACT CENTRAL STATION PRIOR TO TESTING) AC MUST
BE RESTORED AFTER TEST.
XP-600 WIRING DIAGRAM
(REFER TO PROGRAMMING INSTRUCTIONS WI1373)
RESIDENTIAL BURG (4 HOUR STANDBY)
COMBINED STANDBY = 500 mA BELL = 2.0 AMP
RESIDENTIAL FIRE (24 HOUR STANDBY)
(3)
COMBINED STANDBY = 120 mA BELL = 95 mA
(1)
(Z)
3.
9K
3.
9K
3.
9K
RPXP6GT
GOLD
RED
RED
RED
2.2K
(E)
EZ
Zone
Doubling
TM
Resistors
(Z)
GOLD
WHITE
RED
3.9K
ORANGE
DS1
TELE LINE IN USE
RECOMMENDED BATTERIES YUASA
NP4-12 AND NP7-12
REPLACE EVERY FIVE YEARS