6
WI1372 XP-600 Installation Instructions
Installation
Mounting the Panel
Mount the Panel close to an unswitched AC
source, a cold-water pipe ground, and a
telephone line connection.
Mounting the Keypad
A keypad should be located near an exit/entry
door. To remove the keypad from the backplate,
insert a small screwdriver into the square hole at
the bottom of the keypad. Pull up on the
screwdriver to pop off the cover.
Up to 4 keypads can be connected on individual
wire runs with #22 AWG wire with a maximum
total cable length of 1000 feet. Each keypad
draws approximately 65 mA.
Typical Fire Installation
(Where permitted by local codes)
Install smoke detectors outside each sleeping
area and on each floor, including the basement.
Install the living room and basement smoke
detectors near the stairway of the next upper
level. For increased protection, additional
detectors should be installed in areas other than
those required, such as the dining room,
bedrooms and utility room. Heat detectors,
rather than smoke detectors, are recommended
in kitchens, attics, and garages due to
conditions that may result in false alarms and
improper operation.
Refer to NFPA Standard 74 (National Fire
Protection Association, Batterymarch Park,
Quincy, MA 02269) for additional information,
including proper mounting methods.
Wiring
Grounding the Panel
Connect the control-panel EARTH GROUND
screw through a No. 16 AWG or larger wire to a
metal cold-water pipe. Do not use a gas pipe,
plastic pipe or AC ground connections. Use at
least #16 AWG wire. Connect a wire with a
ground lug crimped or soldered onto one end
and connect it to the EARTH GROUND screw in
the cabinet.
AC Power and Battery Wiring
Complete all wiring before connecting the
battery or AC Power. Do not plug the
transformer into a switched outlet.
Telephone Wiring
Wire as shown in the wiring diagram in the back
of this manual.
WARNING
The FCC restricts the use of this equipment on
certain telephone lines. Read the FCC
statement on the back of this manual to ensure
compliance.
FIGURE
3
Typical Fire Installation
Keypad Wire Color
Control Panel Terminal
RED
12 (+PWR)
BLACK
13 (GND)
GREEN
14 (GREEN)
TABLE
1
K
EYPAD
W
IRING