NAPCO StarLink Fire: Getting Started Guide
The following summarizes the minimum required NOC programming (
h
Ʃ
p://NapcoNOC.com
) and system wiring for repor
Ɵ
ng alarm and trouble events trig-
gered by the relays of a Fire Alarm Control Panel (FACP). Check the installa
Ɵ
on and programming instruc
Ɵ
ons for addi
Ɵ
onal wiring and programming op
Ɵ
ons.
Be sure all items in the following checklist are performed:
1.
Central Sta
Ɵ
on Receiver Telephone numbers are programmed in the
"
Dealer
Entered
Programming
" sec
Ɵ
on (see image at right):
2.
UL
Poll
Fail
Timeout
is set (200 seconds NFPA 2007 service plan; 5 min.
for NFPA 2010 plan; 60 min. for NFPA 2013 plan or 24hr backup only):
3.
Set CS Test Timer to 6hr or 24hr.
4.
The central sta
Ɵ
on receiver telephone number ("
Telco
#
for
repor ng
tamper/linecut/parallel
inputs
") and account number ("
Subscriber
Account
Number
") are programmed in the
Advanced
tab:
Note:
The central sta
Ɵ
on receiver telephone number and account
number must be manually entered.
5.
Input 2 (
IN2
) and Input 3 (
IN3
) is set for
Super-
vised
Fire
Alarm/Fire
Trouble
, and the desired
event number and zone numbers are pro-
grammed for Fire Alarm and Fire Trouble (also
programmed for other trouble condi
Ɵ
ons as
required by the local AHJ). Upon loss of power
or trouble, the FACP N/C relay must change
state from closed to open; see wiring diagram below. If necessary,
IN3
may be used for addi
Ɵ
onal troubles. Default Contact ID repor
Ɵ
ng codes: Fire
Alarm =
110
and Trouble =
373
. Default 4/2 repor
Ɵ
ng codes: Fire Alarm =
F3
and Trouble =
22
.
6.
(
PGM1
) is wired to a trouble zone in the FACP. Wire the control panel Listed EOLR in series (terminal 3 PGM Output #1 and ground terminal #8) to
a zone or point programmed to monitor radio trouble.
Notes:
1. For NAPCO control panel downloading or
remote
upgrading
of
radio
fi
rmware
, radio jumper
X5_J1
must be removed.
2.
Note:
Upon ac
Ɵ
va
Ɵ
on of the
fi
re alarm relay (short on black and red harness wires), an alarm signal will be transmi
Ʃ
ed to the central sta
Ɵ
on.
Upon ac
Ɵ
va
Ɵ
on of the
fi
re trouble relay (open between blue and red harness wires), a
fi
re trouble signal will be transmi
Ʃ
ed to the central sta
Ɵ
on.
3. For StarLink models SLECDMA-CFB-PS and SLE3/4G-CFB-PS, connect to charger board terminal labeled
N/O
.
4. If using external relay for radio supervision, relay must be rated for radio input voltage, (12VDC, max current draw=50mA OR 24VDC, max current
draw=25mA). A Listed low current relay, such as
Space Age Electronics
model SSU-MR-311/C/R is recommended.
Installation Quick Start / Checklist for Triggering Radio Inputs from FACP Relays
WI2162A 04/16
6
7
8
15
14
13
12
11
9 10
2
3
4 5
1
17
16
StarLink Radio Terminals
(ST
ARLINK RADIO H
O
USING)
All connections are power limited except AC Mains, Telco
and battery terminals.
Terminals 14-17: No connections permitted.
RED
BLAC
K
9LE10KHARN installed in FACP:
Blue/Red normally closed relay open on trouble
Red/Black normally open relay short on alarm
BLUE
FACP N/C
Trouble
Relay
+V
(12/24V)
(
–
) PGM1 PGM2 PGM3 IN1 IN2 GND IN3
RING
TIP
RTS
(R)
PANEL
TX (B)
PANEL
RX (G)
CTS
Y
PANEL
RING (+)
PANEL
TIP (–)
RED
BLAC
K
FACP N/O
Alarm
Relay
RED
9SLE10KHARN
Wiring Harness
(Install at FACP)
C
N/O**
C
N/O
N/C
N/C**
(Use FACP Listed
EOLR)
To FACP
conventional zone
positive terminal
programmed for
radio trouble
See
Note 3
If using addressable input for
radio supervision, connect
Form C relay as shown below.
–
+
EOLR
EOLR
C
N/C
N/O
See
Note 4
1
2
3
4
To FACP
Ground /Common
Terminal (not
earth ground)
RED
BLUE
FACP N/C
Trouble
Relay
RED
BLAC
K
FACP N/O
Alarm
Relay
RED
C
N/O**
C
N/C**
BLAC
K
9SLE10KHARN
Wiring Harness
(Install at FACP)
N/O
N/C
**FACP Trouble
Relay energized
state depicted
Note: All wiring diagrams and programming depicted in this guide assume the wiring between the radio and the FACP is protected by conduit.
Summary of Contents for StarLink Connect Series
Page 2: ...2 NAPCO StarLink Fire Getting Started Guide...
Page 4: ...4 NAPCO StarLink Fire Getting Started Guide...
Page 5: ...NAPCO StarLink Fire Getting Started Guide 5...
Page 6: ...6 NAPCO StarLink Fire Getting Started Guide...
Page 7: ...NAPCO StarLink Fire Getting Started Guide 7...
Page 8: ...8 NAPCO StarLink Fire Getting Started Guide...
Page 12: ...12 NAPCO StarLink Fire Getting Started Guide...
Page 26: ...26 NAPCO StarLink Fire Getting Started Guide...
Page 30: ...30 NAPCO StarLink Fire Getting Started Guide...
Page 34: ...34 NAPCO StarLink Fire Getting Started Guide...