2.4 INFORMATION SUR LA PLAQUE D’HOMOLOGATION
W385-1959
SERIAL NUMBER / NO. DESERIE
NOT FOR USE WITH SOLID FUEL
GDS/CDVS20
WOLF STEEL LTD.
24 NAPOLEON ROAD, BARRIE, ON, L4M 0G8 CANADA
CERTIFIED UNDER / HOMOLOGUE SELON LES NORMES: ANSI 21.50-2012, CSA 2.22-2012 VENTED GAS FIREPLACE / FOYER À GAS VENTILÉ .
THIS FIREPLACE USES AND REQUIRES A FAST ACTING THERMOCOUPLE. REPLACE ONLY WITH A FAST ACTING
THERMOCOUPLE SUPPLIED BY WOLF STEEL LTD.
APPROVED FOR BEDROOM, BATHROOM & BEDSITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME
INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSA Z240MH SERIES GAS
EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME
CONSTRUCTION AND SAFETY STANDARD, TITLE 24 CFR, PART 3280. WHEN THIS US STANDARD IS
NOTAPPLICABLE USE THE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME
INSTALLATIONS, SITES AND COMMUNITIES, ANSI / NFPA 501A.
FOR USE WITH BARRIER W565-0155. FOLLOW THE
INSTALLATION INSTRUCTIONS LOCATED IN THE INSTALLATION MANUAL.
CE FOYER UTILISE ET REQUIERT UN THERMOCOUPLE À ACTION RAPIDE. REMPLACEZ UNIQUEMENT AVEC UN
THERMOCOUPLE À ACTION RAPIDE DE WOLF STEEL LTÉE.HOMOLOGUE POUR INSTALLATION DANS UNE
CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE
MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE
DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE
SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES, TITRE 24 CFR, SECTION 3280. DANS LE
CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERER A LA NORME RELATIVE AU
CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS
MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.
POUR UNE UTILISER AVEC BARRIÈRE
W565-0155. SUIVEZ LES INSTRUCTIONS D'INSTALLATION SE TROUVENT DANS LE MANUEL D'INSTALLATION
.
9700539 (WSL) 4001657 (NGZ) 4001658 (NAC) 4001659 (WUSA)
GDS20N / CDVS20N
MODEL
GDS20P / CDVS20P
0-4500FT (0-1370m)
ALTITUDE / ELEVATION
0-4500FT (0-1370m)
20,000 BTU/h
INPUT / ALIMENTATION
20,000 BTU/h
13,000 BTU/h
REDUCED INPUT / ALIMENTATION REDUITE
12,000 BTU/h
60%
P4
60%
MANIFOLD PRESSURE:
3.5 INCHES W.C. (NG)
PRESSION AU COLLECTEUR:
3.5" D'UNE
COLONNE D'EAU(GN)
MIN SUPPLY PRESSURE:
4.5" W.C.(NG)
PRESSION D'ALIMENTATION MIN:
4.5" D'UNE
COLONNE D'EAU (GN)
MAX. SUPPLY PRESSURE:
7" W.C. (NG)
PRESSION D'ALIMENTATION MAX:
7" D'UNE
COLONNE D'EAU (GN)
MANIFOLD PRESSURE:
10 INCHES W.C. (LP)
PRESSION AU COLLECTEUR:
10" D'UNE
COLONNE D'EAU(P)
MIN SUPPLY PRESSURE:
11" W.C.(LP)
PRESSION D'ALIMENTATION MIN:
11" D'UNE
COLONNE D'EAU (P)
MAX. SUPPLY PRESSURE:
13" W.C. (LP)
PRESSION D'ALIMENTATION MAX:
13" D'UNE
COLONNE D'EAU (P)
FOR USE WITH GLASS DOORS CERTIFIED WITH
THIS UNIT ONLY.
WARNING:
DO NOT ADD ANY MATERIAL TO THE
APPLIANCE, WHICH WILL COME IN CONTACT
WITH THE FLAMES, OTHER THAN THAT SUPPLIED
BY THE MANUFACTURER WITH THE APPLIANCE.
DECORATIVE PRODUCT:
NOT FOR USE AS A
HEATING APPLIANCE
ELECTRICAL RATING:
115V 1.5AMP 60HZ
THE APPLIANCE MUST BE VENTED USING THE
APPROPRIATE WOLF STEEL VENT KITS. SEE
OWNERS INSTALLATION MANUAL FOR VENTING
SPECIFICS.
MINIMUM AND MAXIMUM VERTICAL VENT
LENGTHS ARE 3 FEETAND 40 FEET
RESPECTIVELY.
MINIMUM AND MAXIMUM HORIZONTAL VENT
LENGTHS ARE 12 INCHES AND 20 FEET
RESPECTIVELY.
PROPER REINSTALLATION AND RESEALING IS
NECESSARY AFTER SERVICING THE VENT-AIR
INTAKE SYSTEM.
MINIMUM CLEARANCE TO COMBUSTIBLE MATERIAL:
A
4”
B
2”
C
2”
VENT TOP
2”
TO CEILING FROM
VENT BOTTOM 1”
STOVE TOP
48”
VENT SIDES
1”
UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET APPAREIL.
UTILISER AVEC LES PORTES VITREES
HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.
AVERTISSEMENT:
N'AJOUTEZ PAS A CET APPAREIL
AUCUN MATERIAU DEVANT ENTRER EN CONTACT
AVEC LES FLAMMES AUTRE QUE CELUI QUI EST
FOURNI AVEC CETAPPAREIL PAR LE FABRICANT.
PRODUIT DÉCORATIF:
NE PAS UTILISER COMME
APPARIEL DE CHAUFFAGE.
CLASS.:
115V 1.5AMP 60HZ
L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT
L'ENSEMBLE D'EVACUATION PROPRE A WOLF
STEEL.
REFERER AU MANUEL D'INSTALLATION DE
PROPRIETAIRE POUR L'EVACUATION PRECISE. LES
LONGUEURS VERTICALES MINIMALES ET
MAXIMALES SONT3 PIEDS ET 40 PIEDS
RESPECTIVEMENT.
LES LONGUEURS HORIZONTALES MINIMALES
ET MAXIMALES SONT 12 POUCES ET 20 PIEDS
RESPECTIVEMENT.
IL EST IMPORTANT DE BIEN REINSTALLER ET
RESCELLER L'EVENT APRES AVOIR ASSURE LE
MAINTIEN DU SYSTEME DE PRISE D'AIR.
DEGAGEMENTS MINIMAUX DES MATERIAUX
COMBUSTIBLES:
A
4”
B
2”
C
2”
EVENT SUPERIEUR 2” ENTRE LE DESSUS DU FOYER
EVENT INFERIEUR 1” ET LE PLAFOND
48”
COTES DE L'EVENT 1”
ÉCHANTILL
ON
ÉCHANTILL
ON
UEL
ÉCHANTILL
O
HA
HHHHHHAAAAAAA
HA
HA
HA
HA
HA
HA
HA
HHAAA
H
EL LTD.
LTD.
AD, BARRIE, ON, L4M
AD, BARRIE, ON, L4
AS FIREPLACE / FOYER À GAS VENT
E / FOYER À GAS VE
QUIERT UN THERMOCOUPLE À ACTION
RMOCOUPLE À ACTIO
E À ACTION RAPIDE DE WOLF STEEL LT
ION RAPIDE DE WOLF STEEL LT
COUCHER, UNE SALLE DE BAIN ET UN
ER, UNE SALLE DE BAIN ET UN
OBILE SI SON INSTALLATION CONFORME
SON INSTALLATION CONFO
SONS MOBILES EQUIPEES AU GAZ, EN V
EQUIPEES AU GAZ, EN
URITE ET DE CONSTRUCTION DE MAISO
RUCTION DE MAISO
AS OU CETTE NORME D'ETATS-UNIS NE
CETTE NORME D'ETATS-UNIS NE
CRITERE DE MESURES DE SECURITE
RE DE MESURES DE SECURITE
MANUFACTURES, LES SITES ET LE
NUFACTURES, LES SITES ET
W565-0155. SUIVEZ LES
W565-0155. SUIVEZ LE
4001658 (NAC) 4001659 (W
658 (NAC) 4001659 (W
TTIL
MODEL
L
GDS
GDS
UDE / ELEVATION
ELEVATIO
0-4
0
UT / ALIMENTATION
LIMENTATIO
INPUT / ALIMENTATION REDUITE
/ ALIMENTATION REDUITE
P4
P4
IL
NG
T
UM HORIZONTAL VENT
L VENT
NCHES AND 20 FEET
AND 20
STALLATION AND RESEALING IS
ON AND RESEALING IS
Y AFTER SERVICING THE VENT-AI
VICING THE VENT-A
YSTEM.
M.
M CLEARANCE TO COMBUSTIBLE MA
RANCE TO COMBUSTIBL
4”
B
2”
2”
C
2”
VENT TOP
2”
VENT TOP
2”
VENT BOTTOM 1”
VENT BOTTOM 1”
VENT SIDES
1”
VENT SIDES
1”
UN CO
UN C
UTIL
UTI
H
INSTALLATEUR : Il est de votre responsabilité de cocher les cases appropriées sur la plaque
d'homologation correspondant au modèle, au type d'évacuation et au type de gaz de l'appareil.
Pour l’emplacement de la plaque d’homologation, voir la section « VUE D’ENSEMBLE DE L’INSTALLATION ».
Cette illustration est à titre de référence seulement. Consultez la plaque d’homologation pour obtenir
l’information précise.
NOTE :
La plaque d'homologation doit rester avec l'appareil à tout le temps. Il ne doit pas être enlevé.
FR
W415-1326 / 05.26.14
51