2.4 GENERAL
INFORMATION
4.12A
pp
g
• The
fl exible connector must not be longer than 36 inches (914mm).
•
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
•
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
The installation must conform with local codes or, in
absence of local codes, the National Gas and Propane
Installation Code CSA B149.1 in Canada, or the National
Fuel Gas Code, ANSI Z223.1 / NFPA 54 in the United
States. Suitable for mobile home installation if installed in
accordance with the current standard CAN/CSA Z240MH
Series, for gas equipped mobile homes, in Canada or
ANSI Z223.1 and NFPA 54 in the United States.
Some appliances have optional fans or blowers. If an optional fan or blower is installed, the junction box must
be electrically connected and grounded in accordance with local codes, use the current CSA C22.1 Canadian
Electrical Code in Canada or the ANSI/NFPA 70 National Electrical code in the United States.
We suggest that our gas
hearth products be installed
and serviced by professionals
who are certified in the U.S.
by the National Fireplace
Institute
® (NFI) as NFI Gas
Specialists
www.nficertified.org
FOR YOUR SATISFACTION, THIS APPLIANCE HAS BEEN TEST-FIRED TO ASSURE ITS OPERATION AND
QUALITY!
RATES AND EFFICIENCIES
NG
LP
Max. Input (BTU/HR)
24,000
22,000
Max. Output (BTU/HR)
15,900
16,000
Min. Inlet Gas Supply Pressure
4.5" (11mb) Water Column
11" (27mb) Water Column
Max. Inlet Gas Supply Pressure
7" (17mb) Water Column
13" (34mb) Water Column
Manifold Pressure (Under Flow Conditions)
3.5" (9mb) Water Column
10" (25mb) Water Column
No external electricity (110 volts or 24 volts) is required for the gas system operation.
Under extreme vent confi gurations, allow several minutes (5-15) for the fl ame to stabilize after ignition.
Altitudes greater than 4000ft. (1219m) require a minimum vent run of 12ft (4m).
When the appliance is installed at elevations above 4,500ft (1372m), and in the absense of specifi c
recommendations from the local authority having jurisdiction, the certifi ed high altitude input rating shall be
reduced at the rate of 4% for each additional 1,000ft (305m).
Expansion / contraction noises during heating up and cooling down cycles are normal and to be expected.
This appliance is not approved for closet or recessed installations. It is approved for bathroom, bedroom and bed-
sitting room installations.
This appliance must be connected to any accepted lined chimney system listed to ULC-S635M (in Canada)
or UL-1777 (in USA). The venting connection must be in compliance with the vent manufacturers installation
instructions.
The draft hood must be installed so it is in the same atmospheric pressure zone as the combustion air inlet to
the appliance.
Provide adequate ventilation and combustion air. Provide adequate accessibility clearance for servicing and
operating the appliance. Never obstruct the front opening of the appliance.
A barrier designed to reduce the risk of burns from the hot viewing glass is provided with the appliance
and must be installed.