W415-1789 / C / 01.29.19
EN
28
electrical information
On/Off Switch
in Blower
Housing
SIT
Proflame 2
Control Board
Blower
Ground Connection =
Legend:
14/2 power source
(not supplied)
(factory installed)
(supplied)
Field Connection =
On/Off
Switch
L
N
9.1.1 wiring diagram
9.2
wiring to wall switch & remote control (in series)
1. Determine the location for the wall switch. Install an electrical box (not supplied) at the location.
2. Ensure the hot and neutral wires from the Proflame 2 are properly connected to the wall switch box.
3. Connect the hot wire from the on/off switch to the wall switch.
4. Connect the neutral wires to each other from the blower to the power source neutral (N).
5. Connect the all ground from the SIT Proflame 2 control board to the blower.
On/Off Switch
in Blower
Housing
Blower
Gr
ound Connection =
Legend:
Field Connection =
On/Off
Switch
L
N
Wall
Switch
G
Neutral =
L1 (120VAC) =
Ground Wire =
SIT
Proflame 2
Control Board
9.2.1 wiring diagram
note:
Check the blower specifications (see “blower specifications” section) before choosing a suitable wire size.