background image

 13

WS-415-63 / 11.24.98

ADJUSTMENTS

PILOT BURNER ADJUSTMENT

PILOT BURNER ADJUSTMENT

PILOT BURNER ADJUSTMENT

PILOT BURNER ADJUSTMENT

PILOT BURNER ADJUSTMENT

Adjust the pilot screw to provide properly
sized flame. Turn in a clockwise direc-
tion to reduce the gas flow.

FIGURES 26 & 27.

VENTURI ADJUSTMENT

VENTURI ADJUSTMENT

VENTURI ADJUSTMENT

VENTURI ADJUSTMENT

VENTURI ADJUSTMENT

To access the venturi, remove the four screws securing the burner to the
base; slide to the left, lift up and out. Natural gas models have air shut-
ters set at 3/16 (.188) inch open. Propane gas models have air shutters
set at 1/4 (.250) inch open. Closing the air shutter will cause a more
yellow flame, but can lead to carboning. Opening the air shutter will cause
a more blue flame, but can cause flame lifting from the the burner ports.
The flame may not appear yellow immediately; allow 15 to 30 minutes for
the final flame colour to be established.

P

I

PI

PILOT SCREW

LOT

N

O

L

O

T

H I

LO

FF

O

FIGURE 26

FLAME MUST ENVELOP

UPPER 3/8" TO 1/2" OF

THERMOCOUPLE & 

THERMOPILE

THERMOPILE

THERMO-
COUPLE

FIGURE 27

FIGURE 28

Air shutter adjustment must only be done by a qualified gas installer!

OPTIONAL BLOWER INSTALLATION

Provision has been made on the Napoleon stove to install an optional blower on
the rear wall. Because the blower is thermally activated, when turned on, it will
automatically start after approximately 30 minutes from a cold start (pilot off) or
15 minutes from a warm start (pilot on) and will run for approximately 30 minutes
after the stove has been turned off. Use of the fan in-
creases the output of heat.

1.

 Mount the variable speed switch: insert the rheostat

stem through the 3/8" diameter hole in the pedestal
and from the front secure with the pal nut. Add the knob.

2.

 Remove the blower housing located at the rear of the

stove. Attach the bracket holding the heat sensor as shown to the weld stud and
secure using one of the #6 nuts. 

FIGURE 24.

3.

 Attach the bare end of the wire (with one bare lead / one flag connector end) to

the 

black 

wire of the speed switch using a nut connector. Attach the flag connec-

tor at the other end to one of the prongs of the heat sensor.

4. 

Thread the leads of the power cord through the slot located at the bottom left

of the blower housing. Attach the terminal of the ground wire 

(green)

 to the

threaded weld stud and secure with a nut.

5.

 Connect one of the two bare leads of the other wire to the 

white

 wire of the

speed switch using a nut connector. Connect the other end to the bare lead wire
of the blower cord using a nut connector.

6.

 Attach the other terminal of the wire

 (already at-

tached to the blower)

 to the heat sensor.

7. 

Mount the cord terminal to the other blower prong.

8.

 Using the holes shown, attach the blower to the

blower housing.

9. 

Bring out any slack in the blower cord. Place the cord into the split strain relief bushing,

just at the point where the cord enters the slot. Clamp the two pieces together and insert
the bushing securely into the slot. 

FIGURE 25.

VARIABLE SPEED

SWITCH

H

I

L

P

O

FF

N

T

I

O

O

LO

GROUND
WELD STUD

FIGURE 25

white

black

ground

FIGURE 23

SENSOR

BLOWER
HOUSING

HEAT

FIGURE 24

Summary of Contents for GDS 3700-P

Page 1: ...722 6031 Email ask napoleon on ca Web www napoleon on ca Wolf Steel Ltd RR 1 9 Napoleon Rd Barrie ON Canada L4M 4Y8 705 721 1212 R 2000 Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department W W W W WARNING ARNING ARNING ARNING ARNING If the information in these instructions is not followed e...

Page 2: ...rtical Venting Installation Stove Vent Connection 10 10 10 10 10 GAS INST GAS INST GAS INST GAS INST GAS INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION 11 11 11 11 11 FINISHING FINISHING FINISHING FINISHING FINISHING Log Placement Charcoal Embers PG PG PG PG PG 12 12 12 12 12 OPERA OPERA OPERA OPERA OPERATION MAINTENANCE TION MAINTENANCE TION MAINTENANCE TION MAINTENANCE TION MAINTENANCE Ope...

Page 3: ...pproval of an authorized company official Labour costs work however requires the prior approval of an authorized company official Labour costs to the account of to the account of to the account of to the account of to the account of NAPOLEON NAPOLEON NAPOLEON NAPOLEON NAPOLEON are based on a predetermined rate schedule and any repair are based on a predetermined rate schedule and any repair are ba...

Page 4: ... or the ANSI NFPA 70 1990 NATIONAL ELECTRICAL CODE in the United States The blower power cord must be connected into a properly grounded receptacle The grounding prong must not be removed from the cord plug Provide adequate ventilation and combustion air Provide adequate accessibility clearance for servicing and operating the stove Never obstruct the front opening of the stove GENERAL INFORMA GENE...

Page 5: ...nts burners and circulating blower and its passageway in the stove and venting system are kept clean The stove and its venting system should be inspected before use and at least annually by a qualified service person More frequent cleaning may be required due to exces sive lint from carpeting bedding material etc The stove area must be kept clear and free from combustible materials gasoline and ot...

Page 6: ...SE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI A A A A ATEL TEL TEL TEL TELY ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET Y ABOVE THE STOVE IS 20 FEET IF VERTICAL RISES GREA IF VERTICAL RISES GREA...

Page 7: ...LA ALLA ALLA ALLATION EXAMPLE TION EXAMPLE TION EXAMPLE TION EXAMPLE TION EXAMPLE If a first run of 48 inches is required using the First Vent Run chart shows that a 51 inch vertical rise is necessary and a maximum second run of 32 inches is allowable IF NECESSAR IF NECESSAR IF NECESSAR IF NECESSAR IF NECESSARY Y Y Y Y THE FIRST RUN AND THE SECOND RUN MA THE FIRST RUN AND THE SECOND RUN MA THE FIR...

Page 8: ... as illustrated in FIGURE 9 FIGURE9 G Seven feet above public walkways unless fitted with heat shield kit GD301 H One foot below windows that open I One foot from the side of doors and windows that open J One foot from permanently closed windows K One foot above grade L NOT above a regulator meter assembly or within three feet horizontally from the vertical centre line of the assembly M Six feet f...

Page 9: ... 12 3 Slip the first section of 7 diameter stove pipe a minimum of 2 over the outer sleeve of the air terminal Secure to the sleeve using 3 screws Seal the joint and screw heads using high temperature sealant 4 Install the firestop wall plate to the finished interior wall maintain ing a 1 clearance to combustibles Insert the liners through the firestop Holding the air terminal lettering in an upri...

Page 10: ...E INSTALLA ALLA ALLA ALLA ALLA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORATIVE BRASS BAND IS A TIVE BRASS BAND IS A TIVE BRASS BAND IS A TIVE BRASS BAND IS A TIVE BRASS BAND IS AV V V V VAILABLE FOR THIS AILABLE FOR THIS AILABLE FOR THIS AILABLE FOR THIS AILA...

Page 11: ...cated on the rear wall of the combustion chamber The notch situated at the lower left of the back log should be centered evenly above the pilot assembly FIGURE 21 3 While supporting the back log to prevent it from falling forward set the three smaller logs into the pockets and grooves of the front and back logs respectively Log colours may vary During the initial use of the fireplace the colours w...

Page 12: ...s supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FOR YOUR SAFETY READ BEFORE OPERATING A This fireplace is equipped with a pilot which must be lit by hand while following these instructions exactly B Before operating smell all around the fireplace area for gas and next to the floor because some gas is heavier ...

Page 13: ...d will run for approximately 30 minutes after the stove has been turned off Use of the fan in creases the output of heat 1 Mount the variable speed switch insert the rheostat stem through the 3 8 diameter hole in the pedestal and from the front secure with the pal nut Add the knob 2 Remove the blower housing located at the rear of the stove Attach the bracket holding the heat sensor as shown to th...

Page 14: ...ISCOPE TERMINAL KIT GD180 PERISCOPE TERMINAL KIT GD180 PERISCOPE TERMINAL KIT PART PART PART PART PART DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION PART PART PART PART PART DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION BM6790 90 ELBOW 7 DIAMETER GD201 PERISCOPE BM67ADJ 30 TO 53 ADJUSTABLE PIPE 7 DIAMETER GDS 500 77 FIRESTOP WALL PLATE GDS 020 32 HARDWARE BRTC7 BRASS TR...

Page 15: ...15 WS 415 63 11 24 98 included with GD180 included with GD175 I H L O L F F N T I O O P O ...

Page 16: ...cooled Allow approximately 60 seconds for the thermocouple to cool Pilot flame is not large enough turn up the pilot flame Pilot flame is not engulfing the thermocouple turn up pilot flame replace pilot assembly Thermocouple shorting loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple replace valve Faultly thermocouple replace Faulty valve replace System is...

Page 17: ...emoved as required refer to Figure 16 to ensure correct location of storm collars Incorrect installation Main burner goes out pilot goes out REFER TO MAIN BURNER GOES OUT PILOT STAYS ON Thermocouple shorting or faulty check joint seals and installation Vent re circulating loosen and tighten thermocouple clean thermocouple and valve connection replace thermocouple replace valve PROBLEM PROBLEM PROB...

Page 18: ...18 WS 415 63 11 24 98 NOTES ...

Reviews: