background image

16

WS-415-63 / 11.24.98

TROUBLE SHOOTING GUIDE

B

EFORE

 

ATTEMPTING

 

TO

 

TROUBLESHOOT

PURGE

 

YOUR

 

UNIT

 

AND

 

INITIALLY

 

LIGHT

 

THE

 

PILOT

 

AND

 

THE

 

MAIN

 

BURNER

 

WITH

 

THE

 

GLASS

 

DOOR

 

REMOVED

.

PROBLEM

PROBLEM

PROBLEM

PROBLEM

PROBLEM

TEST SOLUTION

TEST SOLUTION

TEST SOLUTION

TEST SOLUTION

TEST SOLUTION

SYMPTOM

SYMPTOM

SYMPTOM

SYMPTOM

SYMPTOM

PILOT

THERMOPILE

BURNER

ELECTRODE

THERMO-
COUPLE

Pilot will not light.

-   check if pilot can be lit by a match
-  check that the wire is connected to the push button ignitor.
-  check if the push button ignitor needs tightening.
-  replace the wire if the wire insulation is broken or frayed.
-  replace the electrode if the ceramic insulator is cracked or broken.
-  replace the push button ignitor.

No spark at pilot burner

Spark gap is incorrect

-  check that the manual valve is turned on.
-  check the pilot orifice for blockage.
-  replace the valve.
-  call the gas distributor.

No gas at the pilot burner

-  spark gap should be 0.150" to 0.175" (5/32" to 11/64" approx.)
from the electrode tip and the pilot burner. To ensure proper
electrode location, tighten securing nut (finger tight plus 1/4
turn).

-  fill the tank.

Out of propane gas.

The gas valve has an
interlock device
which will not allow
the pilot burner to be
lit until the thermo-
couple has cooled.
Allow approximately
60 seconds for the
thermocouple to
cool.

Pilot flame is not large enough

-  turn up the pilot flame.

Pilot flame is not engulfing the
thermocouple.

-  turn up pilot flame.
-   replace pilot assembly.

Thermocouple shorting.

-  loosen and tighten thermocouple.
-  clean thermocouple and valve connection.
-  replace thermocouple.
-  replace valve.

Faultly thermocouple.

-  replace.

Faulty valve.

-  replace.

System is not correctly purged.

-  purge the gas line.

-  fill the tank.

Out of propane gas

Pilot goes out when
the gas knob is re-
leased.

Pilot burning; no gas
to main burner; gas
knob is on 'HI'; wall
switch / thermostat is
on.

Main burner orifice is plugged.

-  remove stoppage in orifice.

Faulty thermopile.

Faulty themostat or switch.

-  ensure proper connection.

-  replace.

Faulty valve.

-  replace.

-  turn on all gas appliances and see if pilot flame flutters,
diminishes or extinguishes, especially when main burner ig-
nites. Monitor supply pressure.
-  check if supply piping size is to code. Correct all undersized
piping.

Gas piping is undersized.

Pilot goes out while
standing; Main burner
is in 'OFF' position.

Main burner goes out;
pilot stays on.

-  turn up pilot flame.
- replace pilot assembly.

-  clean thermopile and thermopile connection to valve.

- shorten wire to correct length or wire gauge.

Pilot flame is not large enough
or not engulfing the thermopile.

Thermopile shorting

Remote wall switch wire is too
long, too much resistance in the
system

Faulty thermostat or switch

- replace

Summary of Contents for GDS3700-N

Page 1: ...22 6031 Email ask napoleon on ca Web www napoleon on ca Wolf Steel Ltd RR 1 9 Napoleon Rd Barrie ON Canada L4M 4Y8 705 721 1212 R 2000 Immediately call your gas supplier from a neighbour s phone Follo...

Page 2: ...tical Venting Installation Stove Vent Connection 10 10 10 10 10 GAS INST GAS INST GAS INST GAS INST GAS INSTALLA ALLA ALLA ALLA ALLATION TION TION TION TION 11 11 11 11 11 FINISHING FINISHING FINISHIN...

Page 3: ...proval of an authorized company official Labour costs work however requires the prior approval of an authorized company official Labour costs to the account of to the account of to the account of to t...

Page 4: ...or the ANSI NFPA 70 1990 NATIONAL ELECTRICAL CODE in the United States The blower power cord must be connected into a properly grounded receptacle The grounding prong must not be removed from the cord...

Page 5: ...ts burners and circulating blower and its passageway in the stove and venting system are kept clean The stove and its venting system should be inspected before use and at least annually by a qualified...

Page 6: ...E IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI AL RUN WITH A 57 INCH VERTICAL RISE IMMEDI A A A A ATEL TEL TE...

Page 7: ...A ALLA ALLA ALLATION EXAMPLE TION EXAMPLE TION EXAMPLE TION EXAMPLE TION EXAMPLE If a first run of 48 inches is required using the First Vent Run chart shows that a 51 inch vertical rise is necessary...

Page 8: ...as illustrated in FIGURE 9 FIGURE9 G Seven feet above public walkways unless fitted with heat shield kit GD301 H One foot below windows that open I One foot from the side of doors and windows that ope...

Page 9: ...12 3 Slip the first section of 7 diameter stove pipe a minimum of 2 over the outer sleeve of the air terminal Secure to the sleeve using 3 screws Seal the joint and screw heads using high temperature...

Page 10: ...INSTALLA ALLA ALLA ALLA ALLA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN OPTIONAL DECORA TION IS COMPLETED AN O...

Page 11: ...ated on the rear wall of the combustion chamber The notch situated at the lower left of the back log should be centered evenly above the pilot assembly FIGURE 21 3 While supporting the back log to pre...

Page 12: ...supplier from a neighbour s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department FOR YOUR SAFETY READ BEFORE OPERATING A This fireplace is equip...

Page 13: ...will run for approximately 30 minutes after the stove has been turned off Use of the fan in creases the output of heat 1 Mount the variable speed switch insert the rheostat stem through the 3 8 diame...

Page 14: ...SCOPE TERMINAL KIT GD180 PERISCOPE TERMINAL KIT GD180 PERISCOPE TERMINAL KIT PART PART PART PART PART DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION DESCRIPTION PART PART PART PART PART DESCRIPTION D...

Page 15: ...15 WS 415 63 11 24 98 included with GD180 included with GD175 I H L O L F F N T I O O P O...

Page 16: ...ooled Allow approximately 60 seconds for the thermocouple to cool Pilot flame is not large enough turn up the pilot flame Pilot flame is not engulfing the thermocouple turn up pilot flame replace pilo...

Page 17: ...moved as required refer to Figure 16 to ensure correct location of storm collars Incorrect installation Main burner goes out pilot goes out REFER TO MAIN BURNER GOES OUT PILOT STAYS ON Thermocouple sh...

Page 18: ...18 WS 415 63 11 24 98 NOTES...

Reviews: