INSTALLATION

The log set and the burner assembly are shipped together.
Remove the gas log set and burner assembly and check
for damage. DO NOT install damaged components. The
logs are fragile use care when handling.
Place the Patioflame on a level/secure surface in desired
location. This location must be adjacent to the gas supply
cylinder.
NOTE:Minimum clearances to combustible construction
must be maintained. ( See Page 5)
You must have clear and easy access to the on/off valve
AFTER the appliance is installed and connected to the gas
supply in order to safely turn off the burner.

THE ON/OFF G

THE ON/OFF G

THE ON/OFF G

THE ON/OFF G

THE ON/OFF GAS V

AS V

AS V

AS V

AS VAL

AL

AL

AL

ALVE IS USED T

VE IS USED T

VE IS USED T

VE IS USED T

VE IS USED TO TURN THE

O TURN THE

O TURN THE

O TURN THE

O TURN THE

B

B

B

B

BURNER ON AND OFF

URNER ON AND OFF

URNER ON AND OFF

URNER ON AND OFF

URNER ON AND OFF.....

Connect the incoming gas supply line to the on/off gas
valve of the appliance. Make certain ALL gas connections
are tight, turn the on/off valve at the unit slowly to the on
position and use soap water to test for leaks.
DO NOT USE AN OPEN FLAME.

1.

 Place the cylinder in the ring on the base. Base should

be on level surface.

2.

 Make sure tank valve is in its full off position. (Turn clock-

wise to stop).

3.

 Check tank valve features to ensure it has proper exter-

nal mating threads. (Tank Valve Marked: USE WITH TYPE
1)

4.

 Inspect hose shipped with the unit for damage. Never

attempt to use damaged or plugged equipment. See your
local LP Gas Dealer for repairs.

5.

 After inspecting the LP hose shipped with the unit, con-

nect the end with the female fitting on the hose to the male
fitting on the on/off gas valve at the end of the flex tube.
Tighten fittings using 2 wrenches.

6.

 When connecting regulator assembly to the tank valve,

hand tighten black QCC1 nut clockwise to a positive stop.
DO NOT use a wrench to tighten. Use of a wrench may
damage the quick closing coupling nut and result in a haz-
ardous condition.

7.

 Locate the hose out of pathways where people may trip

over it or in areas where the hose may be subject to acci-
dental damage.

8

. Open tank valve fully (counter-clockwise). Turn the on/off

valve at the unit slowly to the on position and use a soapy
water solution to check all connections for leaks before
attempting to light the appliance. If a leak is found, turn
tank valve off and do not use the appliance until repairs
can be made.

NATURAL GAS

LP GAS

ENCLOSURES FOR LP GAS SUPPLY SYSTEMS

If you build an enclosure for an LP gas cylinder, follow
these recommended specifications. You must also follow
local codes.
Enclosures for LP gas supply cylinders shall be ventilated
by openings at the level of the cylinder valve and at floor
level. The effectiveness of the opening(s) for purposes of
ventilation shall be determined with the LP gas supply
cylinder(s) in place. This shall be accomplished by one of
the following:

1.

 One side of the enclosure shall be completely open;

or

2. 

For an enclosure having four sides, a top and bottom:

a)

 At least two ventilation openings at cylinder valve level

shall be provided in the side wall, equally sized, spaced at
180 degrees (3.14 rad), and unobstructed. Each opening
shall have a total free area of not less than ½ square inch
per pound (3.2 sq. cm/kg) of stored fuel capacity and not
less than a total free area of 10 square inches (64.5 sq. cm).

b)

 Ventilation opening(s) shall be provided at floor level

and shall have a total free area of not less than ½ inch per
pound (3.2 sq. cm/kg) of stored fuel capacity and not less
than a total free area of 10 square inches (64.5 sq. cm). If
ventilation openings at floor level are in a side wall, there
shall be at least two openings. The bottom of the openings
shall be at floor level and the upper edge no more than 5
inches (127mm) above the floor. The openings shall be
equally sized, spaced at 180 degrees (3.14 rad) and unob-
structed.

c)

 Every opening shall have minimum dimensions so as

to permit the entrance of a 1/8 inch (3.2mm) diameter rod.

3.

 Cylinder valves shall be readily accessible for hand op-

eration. A door on the enclosure to gain access to the cylin-
der valve is acceptable, provided it is non-locking and can
be opened without the use of tools.

4.

 There shall be a minimum clearance of 2 inches

(50.8mm) between the lower surface of the floor of the LP
gas supply cylinder enclosure and the ground.

5. 

The design of the enclosure shall be such that (1) the LP

gas supply cylinder(s) can be connected, disconnected
and the connections inspected and tested outside the cyl-
inder enclosure; and (2) those connections which could
be disturbed when installing the cylinder(s) in the enclo-
sure can be leak tested inside the enclosure.

6.

 Be certain to mount or set the LP gas cylinder on a flat

surface and restrain it to prevent it from tipping.
Purge the gas supply line of any trapped air prior to the first
firing of the unit.

WARNING: During the initial purging and subsequent
lightings, NEVER allow gas valve to remain in the "Open"
position without first placing and igniting the firestarter.

Summary of Contents for GPFN

Page 1: ...pours and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your build ing...

Page 2: ...or ore installing or ser e installing or ser e installing or ser e installing or ser e installing or servicing this equipment vicing this equipment vicing this equipment vicing this equipment vicing t...

Page 3: ...t pride in their work The burner and valve assembly are leak and test fired at a quality test station Once assembled the complete appliance is thoroughly inspected by a qualified technician before pac...

Page 4: ...e Clothing or other flammable materials should not Clothing or other flammable materials should not Clothing or other flammable materials should not Clothing or other flammable materials should not Cl...

Page 5: ...iling 72 1830 Natural LP Propane Minimum Inlet Pressure 4 5 w c 11 0 w c Maximum Inlet Pressure 14 0 w c 14 0 w c Model Fuel Max Input Btu Hr GPFN Natural Gas 60 000 GPFP Propane Gas 60 000 INPUT MINI...

Page 6: ...repairs can be made NATURAL GAS LP GAS ENCLOSURES FOR LP GAS SUPPLY SYSTEMS If you build an enclosure for an LP gas cylinder follow these recommended specifications You must also follow local codes E...

Page 7: ...t base log onto burner ensuring stud and bracket fit into hole and notch Base log should sit flat on Patioflame base 2 Place Y end of log 1 into Y notch on the base log 3 Place pocket on log 2 onto th...

Page 8: ...trol valve 2 Place the firestarter near the burner ports on top of the burner Light the firestarter For a Natural Gas unit turn on the ON OFF valve slowly at the unit For a LP unit turn the valve in t...

Page 9: ...build up To clean the logs be sure the fire is out the gas supply is turned off and the logs are cool to the touch The soot can then be brushed off with a dry bristle brush or cloth Take care while c...

Page 10: ...an be ordered through your Napoleon dealer or distributor When ordering replacement parts always give the follow ing information 1 MODEL SERIAL NUMBER OF APPLIANCE 2 INSTALLATION DATE OF APPLIANCE 3 P...

Page 11: ...W415 0372 02 12 03 11...

Page 12: ...W415 0372 02 12 03 12 Wolf Steel Appliance Service History This appliance must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...