Air Shutter Openings both Burners
LP
F 7/16" R 1/4”
NG
F 1/16" R 1/16”
2.8 VERMICULITE
33.1
Sprinkle vermiculite around the charcoal embers.
NOTE: Vermiculite is not to be placed on the burner.
2.9 GLOWING
EMBERS
Tear the embers into pieces and place along the front row of ports covering all of the burner area. Care should
be taken to shred the embers into thin, small irregular pieces as only the exposed edges of the fi bre hairs will
glow. The ember material will only glow when exposed to direct fl ame; however, care should be taken to not
block the burner ports.
Blocked burner ports can cause an incorrect fl ame pattern, carbon deposits and delayed ignition. Phazer™
logs glow when exposed to direct fl ame. Use only certifi ed “glowing embers” and Phazer™ logs available from
your Authorized dealer.
3.0 ADJUSTMENT
3.1 FLAME
CHARACTERISTICS
3.2 VENTURI
ADJUSTMENT
This appliance has air shutters that have been factory set open according to
the chart below:
Regardless of venturi orientation, closing the air shutter will cause a more
yellow flame, but can lead to carbonization. Opening the air shutter will
cause a more blue flame, but can cause flame lifting from the burner ports.
The flame may not appear yellow immediately; allow 15 to 30 minutes for
the final flame colour to be established.
AIR SHUTTER ADJUSTMENT MUST ONLY BE DONE BY A QUALIFIED
INSTALLER!
AIR
SHUTTER
OPENING
VENTURI
BURNER
ORIFICE
49.2
It’s important to periodically perform a visual check of the pilot and burner fl ames. Compare them to the
illustration provided. If any fl ames appear abnormal call a service person.
FLAME MUST ENVELOP
UPPER 3/8” (9.5mm) TO 1/2”
(12.7mm) OF FLAME SENSOR
PILOT
BURNER
ELECTRODE
FLAME
SENSOR
3/8” - 1/2”
(9.5mm - 12.7mm)
54.1B
8
W415-1632 / A / 05.02.16