W415-0910 / A / 09.16.10
26
STEP #8
○
Remove the access panel from the rear of the blower box module.
○
Route the harness from the rear of the lower electrical box of the main
electric harness to access the hole on the side of blower box.
○
Match and connect the harness connectors "B" inside the lower
electrical box and snap the
fl
ex conduit connector into the side of the
electrical box.
○
Wires from the other end of the harness should pass through the hole
in side of the blower module. The 90°
fl
ex connector should also be
passed through and secured by the connector nut on the inside of box.
ENSURE THE ELECTRICAL WIRING INSIDE THE BLOWER BOX IS ADEQUATELY SECURED AND
PROTECTED FROM SHARP EDGES. FAILURE TO DO SO COULD RESULT IN DAMAGE TO THE
WIRING INSULATION, RESULTING IN POSSIBLE SHORT CIRCUITING TO THE FURNACE CHASSIS.
THIS COULD RESULT IN POSSIBLE INJURY OR PROPERTY DAMAGE.
ALL 115 VOLT ELECTRICAL PRE ASSEMBLED HARNESSES MUST BE INSTALLED AS PER
INSTRUCTIONS AND ELECTRICAL CODES.
NO 115V ELECTRIC CIRCUIT HARNESS OR FIELD WIRING MAY PASS THROUGH CLEARANCE
SPACE BETWEEN HMF150 FURNACE BOTTOM AND FLOOR.
FAILURE TO COMPLY MAY RESULT IN ELECTRIC SHOCK, FIRE, PROPERTY DAMAGE OR
PERSONAL INJURY.
STEP #10
○
See SECTION 7.0 - ELECTRICAL CONNECTIONS AND SCHEMATICS.
STEP #9
○
See SECTION 6.0 - PLENUM AND VENTING INSTALLATION.
STEP #11
○
See SECTION
8.0
- OPERATING INSTRUCTIONS.
"B" HARNESS LENGTH: ADJUSTMENT WHEN NOT
USING ELECTRIC FURNACE MODULE
○
The length of "B" harness has been made to allow for
installation of an Electric Furnace Module (HMFK-EF20).
If Electric Furnace Module (HMFK-EF20) is not being
installed, the length of
fl
ex conduit needs to be reduced
by 12". Remove the 90° bulk head connector from end
of
fl
ex conduit, slide the liner off wires far enough that the
wiring will not be damaged when adjusting the length of
fl
ex conduit. Measure 12" off end of the
fl
ex conduit and
put small break/kink in the conduit at this point using side
cutters or hacksaw blade. The conduit can then be
fl
exed
back and forth over this break until it breaks completely
apart, and the 12” section can be removed. Feed the
wires back through the
fl
ex conduit and relocate the 90°
head connector bracket to the new end of the
fl
ex conduit.
○
Copy the wire, marking number, located near the end of
each wire, onto a piece of masking tape and stick this
marker 14" away from wire end. The wire can now be
shortened by 12".
ACCESS
HOLES
Summary of Contents for HYBRID 150
Page 6: ...W415 0910 A 09 16 10 6 AIR FLOW CIRCULATION AND HEAT TRANSFER COMBUSTION AIR FLOW...
Page 64: ...W415 0910 A 09 16 10 64 13 0 SERVICE HISTORY...
Page 65: ...W415 0910 A 09 16 10 65 14 0 NOTES...
Page 66: ...W415 0910 A 09 16 10 66 14 0 NOTES...
Page 72: ...W415 0910 A 09 16 10 6 CIRCULATION D AIR ET CHANGE DE CHALEUR CIRCULATION DE L AIR COMBURANT...
Page 131: ...W415 0910 A 09 16 10 65 14 0 NOTES...
Page 132: ...W415 0910 A 09 16 10 66 14 0 NOTES...