EN
W415-1710 / B / 08.17.18
27
installation planning
4.1 installation option 1 - open enclosure (enclosure stops short of the ceiling)
NOT Suitable for Dynamic Heat Control™ Plus
ceiling
2-4”
6” min
DYNAMIC HEAT
CONTROL™ AIR
OUTLET OPEN-
ING IS HOT WHEN
APPLIANCE IS
OPERATING!
Air outlet opening
must
be located out of reach of
the user. Air outlet
must
not be
restricted by furnishings or decor.
RECOMMENDED
Wall mounted
object (picture
frame, appliance,
etc.)
It is one option not to finish or close in the top of the enclosure to provide the necessary air circulation path for the
Dynamic Heat Control™
system. Leaving a complete air outlet opening above the enclosure has been found to
be well accepted with respect to final appearance and offer minimal distraction. It also allows for efficient circulation
of air within the room. This option offers the simplest method for framing and installation. (If installing
Dynamic Heat
Control™
Plus
, refer to option 2 or 3 -
DHC™ Plus cannot be used with option 1
). Limit the air outlet opening
height to 4” to reduce the risk of items inadvertly falling into the enclosure.
The air outlet opening must extend
around the entire perimeter, or the entire front face of the enclosure, where the enclosure runs from wall
to wall.