19
W415-1606 / 09.09.16
EN
FIG.5
4.3 USING FLEXIBLE VENT COMPONENTS
For safe and proper operation of the appliance, follow the venting
instructions exactly.
All inner fl ex pipe and outer fl ex pipe joints may be sealed using high
temperature red RTV silicone W573-0002 (not supplied) or the high
temperature sealant W573-0007 Mill Pac (not supplied). However, the high
temperature sealant W573-0007 Mill Pac (not supplied) must be used on
the joint connecting the inner fl ex pipe and the exhaust fl ue collar.
Use only approved fl exible vent pipe kits marked:
“Wolf Steel Approved Venting” as identifi ed by
the stamp only on the outer fl ex pipe.
22.1A
ELBOW
SPACERS
DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND ELBOWS.
KEEP IT PULLED TIGHT.
SPACERS ARE ATTACHED TO THE INNER FLEX PIPE AT PREDETERMINED INTERVALS TO MAINTAIN AN EVEN
AIR GAP TO THE OUTER FLEX PIPE. THIS GAP IS REQUIRED FOR SAFE OPERATION. A SPACER IS REQUIRED
AT THE START, MIDDLE AND END OF EACH ELBOW TO ENSURE THIS GAP IS MAINTAINED. THESE SPACERS
MUST NOT BE REMOVED.
!
WARNING
A.
Install the inner fl ex pipe to the fi replace. Secure with a
minimum 3 screws and fl at washers. Seal the joint and
screw holes using
Mill Pac sealant (W573-0007)
(not
supplied).
B.
Install the outer fl ex pipe to the fi replace. Secure with a
minimum of 3 screws and fl at washers. Seal the joints
using
red RTV silicone (W573-0002)
(not supplied).
28.4B
HIGH
TEMPERATURE
SEALANT
SCREWS
1 1/2” OVERLAP
(38.1mm)
4.3.1 APPLIANCE VENT CONNECTION
I.
Look through slotted holes on the mounting
plate for pre-marked stud locations and
secure mounting plate using a minimum of 4
screws (minimum 1 screw per corner must be
mounted to a wall stud) (Fig. 5).
J.
See the following sections up to the
“FINISHING” section for venting and
mounting instructions.