25
W415-1606 / 09.09.16
EN
MINIMUM CLEARANCES TO COMBUSTIBLES (FROM THE APPLIANCE):
-
15" (38.1cm) to top/ceiling
-
7" (17.8cm) to sides
-
6”
(15.2cm) to bottom
-
1/2" (13mm) to rear
* A minimum of 1" (25mm) all around the vent pipe on all vertical runs to combustibles is required.
MINIMUM CLEARANCE TO COMBUSTIBLE CONSTRUCTION FROM APPLIANCE AND VENT
SURFACES:
-
1/2" (13mm) to wall mounting plate
-
1" (2.5cm) to bottom and sides of vent pipe*
-
3" (7.6cm) to top of vent pipe*
15" (38.1 cm)
MIN.
36"
(91.4 cm)
MAX.
7"
(17.8 cm)
MIN.
7"
(17.8 cm)
MIN.
36"
(91.4cm)
MAX.
4.5" (11.4 cm) MIN.
15" (38.1 cm)
MIN.
6" (15.2 cm) MIN.
4.5" (11.4 cm) MIN.
6" (15.2 cm) MIN.
TYPICAL
INSTALLATION
ALCOVE
INSTALLATION
SIDE VIEW
ALCOVE
INSTALLATION
TOP VIEW
4.7 MINIMUM CLEARANCE TO COMBUSTIBLES AND NON-COMBUSTIBLES