4. Using the sauna 

heater

4.1 Firewood

Both  hardwood  and  softwood  can  be  used  to  heat  the 
sauna  heater.  The  use  of  chipboard,  fibreboard,  painted 
or  impregnated  wood,  waste  or  plastic  is  prohibited.  To 
ensure  clean  burning  and  the  largest  possible  efficiency, 
the wood must be dry. The moisture content of the wood 
must be less than 20%. 

Usually good firewood is sticks 

of wood the diameter of which is around 5 cm, length 
around 33 cm and weight around 0.5 kg.

Use of liquid fuel is strongly forbidden, also during firing!

4.2 Heating

Before  heating,  make  sure  that  there  is  no  combustible 
material within the safety clearances. Also make sure that 
the  ash  drawer  and  fire  grate  are  clean  and  if  the  sauna 
heater  is  provided  with  a  water  tank,  that  it  is  filled  with 
clean water. Check if there is sufficient draft in the smoke 
flue. If you hesitate regarding the draft, check it by burning 
a small quantity of water in the firebox first. During heating 
the door of the firebox must be closed and the water tank 
must  be  filled  with  water.  The  sauna  heater  must  not  be 
covered with anything. 

To start heating pile firewood over a sufficiently wide area 
and  ignite  it  from  above.  For  ignition  you  may  use  birch 
bark or paper. Ignition aid should be placed between the 
upper  firewood  and  it  can  be  topped  with  some  thinner 
wood  sticks  or  firewood  (see  drawing  9).  Igniting  from 
above reduces pollution and ensures cleaner burning.

The power of the sauna heater can be regulated by the ash 
drawer. If the ash drawer is closed, the power of the sauna 
heater is at its lowest and the burning time is longer. If it 
soughs too much in the sauna heater, reduce the draft. To 
do this close the ash drawer halfway or completely. This 
way  heat  reaches  better  in  the  sauna  heater,  stones  can 
store heat and you do not just heat up the flue. A calm 
flame is a sign of a correct draft. Avoid heating the sauna 
heater so that the channels of the stone compartment glow 
red for a long time because this will overload the firebox 
and  the  service  life  of  the  sauna  heater  will  be  reduced. 
Overheating  may  also  cause  excessive  heating  of  the 
smoke flue and cause a fire hazard. The connective flue 
pipe must not be glowing red.

Figure 9.

 Properly stacked firewood. 

The  following  table  shows  the  recommended  quantities 
of  firewood  for  different  types  of  sauna  heaters  and  po-
sitions  of  the  ash  drawer.  The  values  shown  in  the  table 
meet the values of the nominal power pursuant to standard 
EN15821. In the test the size of the sauna was determined 
based  on  the  maximum  area  for  the  given  sauna  heater 
and temperature of 90 °C was achieved in the sauna.

 Dur-

ing first times we recommend using less firewood for 
achieving the desired temperature than values present-
ed in the table. maximum quantity of firewood per hour 
(max kg/h) indicated in the table must not be exceeded.

Do not stack firewood in the firebox over 2/3 of its height. 
Quantities of firewood are shown in clause 4.1. In the igni-
tion  phase  the  ash  drawer  can  be  kept  open  by  10  mm 

Heating of the sauna:

* sticks of firewood with a diameter around 5 cm, length 

around 33 cm and weight around 0.5 kg

Velvet sauna heater

20

1. firebox of firewood*

quantity of firewood (kg)

4,5

opening of the ash drawer (mm)

25

1. addition

quantity of firewood (kg)

2,5

opening of the ash drawer (mm)

10

1. addition

quantity of firewood (kg)

2,5

opening of the ash drawer (mm)

10

1. addition

quantity of firewood (kg)

2,5

opening of the ash drawer (mm)

10

max kg/h

8

Summary of Contents for Velvet

Page 1: ...DE GB SE FI FI Narvi Velvet Installations Betriebs und Wartungsanleitung Narvi Velvet Installation user and maintenance instructions Narvi Velvet Monterings bruks och sk tselanvisning Narvi Velvet As...

Page 2: ...g av luckan och ndring av luckh ngning 15 3 5 Bastustenar 15 3 6 Bastuugnens luftriktarplattor 16 4 Anv ndning av bastuugnen 17 4 1 Eldningsmaterial 17 SE Inneh ll 1 1 Technische Daten 28 2 Vor der In...

Page 3: ...ornstein 30 2 5 L ftung 30 3 Installation und Vorheizen des Saunaofens 31 3 1 Vorheizen 31 3 2 Regulierung der H he 31 3 3 Anschlie en an den Schornstein 31 3 4 Anbringen der T r und ndern der ffnungs...

Page 4: ...ja lis varusteita Kiukaan mukana toimitettava tuotekilpi tu lee liimata kiinni kiukaaseen suositeltu paikka on kiukaan vaipan alaosa l k yt kiuasta jos ep ilet kiukaank ytt taitojasi tervey dentilasi...

Page 5: ...ly nti aiheuttaa palovaaran Tarvittaessa lis tietoja saat paikallisilta paloviranomaisilta 2 3 1 Palava aineinen rakenne Suojaet isyydet ilmoittavat pienimm n sallitun et isyyden kiukaasta palava aine...

Page 6: ...lla riitt v n tehokas ja sellainen ett raitis tuloilma johdettaisiin mahdollisimman l helle kiuasta Varmista my s l ylyhuoneen kunnollinen ilmankierto kylpemisen aikana siten ett ilma poistuu ulos lau...

Page 7: ...s vuodot hormissa heikent v t kiukaan vetoa ja siksi hormiliitos pit aina tiivist tulen kest v ll tiivistysmateriaalilla Jos hormiliitos vuotaa vaarana voi olla ett kiukaan tuottamat palokaasut sytty...

Page 8: ...Lappi tel 358 0207 416 740 fax 358 0207 416 743 www narvi fi 8 FI 3 6 Kiukaan ilmanohjauslevyt NARVI VELVET ILMANOHJAUSLEVYT Levyjen asento ja kunto on hyv tarkistaa s nn llisesti Kiuasta ei saa k yt...

Page 9: ...l mmit ainoastaan hormia Rauhallinen liekki on merkki sopivasta vedosta Kiuasta ei saa l mmitt siten ett kivitilassa olevat kana vat ovat pitk n punahehkuisia t ll in tulipes kuormittuu liikaa ja kiu...

Page 10: ...ita l mmitt minen hyvin varovasti ja hitaasti pienell m r ll puita ettei hormi vaurioidu 4 3 L ylyvesi K ytett v l ylyveten puhdasta talousvett Talousveden laatuvaatimukset humuspitoisuus 12 mg l raut...

Page 11: ...istuksen mukaisia Takuuaika alkaa siit kun tavara on luovutettu loppuk yt t j lle Toimittaja ei kuitenkaan takuun puitteissa eik muu toinkaan vastaa virheist jotka ilmenev t yli kahden 2 vuoden kulutt...

Page 12: ...aren f r anslutas till bastuugnen Typskylten som medf ljer leveransen m ste f stas p bastuugnen helst l ngst ner p bastuugnens mantel Elda inte i bastuugnen om du inte har tillr cklig kunskap f r det...

Page 13: ...Vid behov kontakta ditt lokala r ddningsverk f r n rmare information 2 3 1 Konstruktion av ant ndligt material S kerhetsavst nd anger minsta till tna avst nd fr n bas tuugnen till konstruktionen av a...

Page 14: ...nen Bastuugnen b r helst anslutas till en egen r kg ng En murad skorsten m ste vara minst en s k halvstensskorsten 2 5 Ventilation Basturummet m ste ha tillr cklig ventilation som leder den friska til...

Page 15: ...s vid ppningen Anslutningskanalen f r inte skjutas f r djupt in i skorste nen det f rs mrar draget ven l ckande r kr rsanslut ningar f rs mrar draget d rf r m ste alla anslutningar alltid t tas med et...

Page 16: ...i tel 358 0207 416 740 fax 358 0207 416 743 www narvi fi se 16 SE 3 6 Bastuugnens luftriktarplattor NARVI VELVET luftriktarplattor Kontrollera luftriktarnas l ge och skick regelbundet Bastuugnen f r i...

Page 17: ...skl dan st ngs till h lften eller ven helt S v rms bastuugnen och dess stenar mer effektivt eftersom inte all v rme leds direkt till skorstenen En lugnt brinnande l ga r ett tecken p r tt drag Undvik...

Page 18: ...nen r hel och bastuugnen fri fr n rostskador B rja elda mycket f rsiktigt med liten m ngd ved f r att inte skada skorstenen 4 3 Vatten f r badkastning Anv nd vanligt rent hush llsvatten f r badkastnin...

Page 19: ...stuugnen anv nds monteras och underh lls i enlighet med angivna instruktioner Garantitiden b rjar g lla vid varans verl mnande till slut anv ndaren Leverant ren tar inget garanti eller annat ansvar f...

Page 20: ...st be glued on the sauna heater preferably on the lower part of the cover of the sauna heater Do not heat the sauna heater if you lack sufficient knowl edge if you are not allowed to use a sauna becau...

Page 21: ...ccount Ignorance of safety clearances causes a fire hazard If required additional information can be obtained from the regional branch of the rescue board 2 3 1 Structure made of combustible materials...

Page 22: ...ght of the smoke flue must not cause load on the sauna heater The sauna heater should be con nected to a separate smoke flue A smoke flue made of bricks must be at least the so called half brick smoke...

Page 23: ...in the con nective flue also reduce the draft therefore the connections must be sealed with fireproof sealing material Leakage in the connective flue causes combustion gases formed in the sauna heate...

Page 24: ...743 www narvi fi en 24 GB 3 7 Air flow direction adjusting plates of the sauna heater NARVI VELVET Air flow direction adjusting plates The position and condition of the plates must be regularly inspec...

Page 25: ...e is longer If it soughs too much in the sauna heater reduce the draft To do this close the ash drawer halfway or completely This way heat reaches better in the sauna heater stones can store heat and...

Page 26: ...ess toxic gas If you have not used the sauna heater and smoke flue for a longer period or it is cold please check before use that the smoke flue is in proper order and that there are no cor rosion dam...

Page 27: ...ed use installation and maintenance meet the requirements stipulated in the instructions The warranty period starts form the moment that the goods are delivered to the end user The supplier is not lia...

Page 28: ...ens enthaltene Typen schild muss an den Saunaofen geklebt werden vorzugsweise an den unteren Teil der Abdeckung des Saunaofens Verwenden Sie den Saunaofen nicht wenn Sie keine ausrei chenden Fertigkei...

Page 29: ...eise bei Hitzsteinen mit Holzbefeuerung ist Bei Tests lag die Temperatur des Fu bodens unter 50 C Bei Anbringung des Hitzsteins ohne besondere Unterlage ist trotzdem die Hitzebest ndigkeit der f r den...

Page 30: ...s ist 12 Pa Ein Elementschornstein muss ein der Klasse T600 ent sprechender Schornstein mit CE Kennzeichnung sein Bei Installation des Elementschornsteins m ssen die der Installationsanleitung des Sch...

Page 31: ...erbindungskanal auch ein Kota Schornsteintank zur Wassererw rmung oder ein Kota Steinkorb angebracht werden Der Verbindungskanal darf nicht zu tief in den Schornstein geschoben werden weil dies den Zu...

Page 32: ...rch Anheben entfernen Die Steine m ssen vorsichtig aufge schichtet und so platziert werden dass die Beschichtung des Hitzsteins nicht besch digt wird Die empfohlene An zahl an Steinen ist unter Punkt...

Page 33: ...lossen ist dann ist der Zug am schw chsten und die Verbrennungszeit entsprechend lang Wenn der Sau naofen sehr laut rauscht muss der Zug verringert werden indem die Aschenschublade etwas mehr zugescho...

Page 34: ...naofen und der Schornstein f r eine lange Zeit nicht gebraucht worden sind oder die Verh ltnisse kalt sind muss vor dem Einsatz berpr ft werden ob der Schornstein intakt ist und der Saunaofen keine Ko...

Page 35: ...Installation und Wartung des Saunaofens den Anleitungen entsprechen Die Garantiezeit beginnt mit der bergabe der Ware an den Endbenutzer Der Lieferant des Produkts haftet weder auf Grundlage der Garan...

Page 36: ...36 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru Narvi Velvet Narvi NC Narvi Velvet 20 780 15 540 580 119 600 160 89 5 10 100 10 15 60 3 8 20 10 1 1...

Page 37: ...Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 2 2 1 0 8 1 5 1 1 2 2 1 1 50 50 Kota 2 3 2 3 1 1220 mm 500 mm 150 mm 200 mm 1000 50 25 50 300 7 1 30 30 120 30 Kota Su...

Page 38: ...38 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 100 400 2 2 1000 2 3 2 50 2 4 600 12 600 120 2 5 6 10 m3 100...

Page 39: ...39 39 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 3 3 1 1 2 3 2 25 3 3 25 1 1 3 4 7 3 5 Kota 1 1 7...

Page 40: ...40 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 3 6 NARVI VELVET...

Page 41: ...41 41 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 4 4 1 20 5 33 0 5 4 2 9 EN15821 90 C 2 3 4 1 10 5 33 0 5 Narvi Velvet 20 1 4 5 25 1 2 5 10 2 2 5 10 3 2 5 10 8...

Page 42: ...42 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 9 1 2 1 3 10 20 4 3 12 0 2 100 0 05 4 4 4 5 9...

Page 43: ...43 43 RU Yritt j ntie 14 FI 27230 Lappi 358 0207 416 740 358 0207 416 743 www narvi fi ru 4 6 5 6 7 Narvi 2 2 NARVI Oy...

Page 44: ...red safety distances to combustible materials Emission of combustible products Durability Surface temperature Release of dangerous substances Cleanability Flue gas temperature Mechanical resistance Th...

Reviews: