Installation Guide for NCPE Split-System Condensing Units
21
Service
Clearance 30
"
SPECIFICATIONS CHART - 5000 SERIES
MODEL NO.
NCPE-418
NCPE-424
NCPE-430
DIMENSIONS
26-7/8
"
38-7/8
"
18- 1/2
"
3/8
"
3/4
"
26-7/8
”
38-7/8
”
18- 1/2
”
3/8
"
3/4
"
26-7/8
”
38-7/8
”
18- 1/2
”
3/8
"
3/4
"
Width
Height
Length
Liquid Valve
Vapor Valve
NOMINAL
CAPACITY B/HR
18,400
24,200
28,400
ELECTRICAL
208/230
60
1
12
13.47
20
208/230
60
1
12
15.13
20
208/230
60
1
10
19.08
30
Volts
Hertz
Phase
Min. AWG Wire
Min. Cir. Ampacity
Max. Fuse
COMPRESSOR
9.0
56.3
10.3
61.6
13.50
72.5
RLA (Amps)
LRA (Amps)
FAN MOTOR
1/5
1650
1.8
1/5
1650
1.8
1/5
1650
1.8
HP
RPM
Amps (Full Load)
COIL
4.59
16
4.59
14
4.59
14
Face Area
FPI
1 17/32"
BACK VIEW
26 27/32"
8 1/16"
FRONT VIEW
10 13/16"
21"
3 11/32"
15 15/16"
10 3/8"
1 3/8"
1 1/4"
3 5/32"
1 3/32"
15 1/32"
10 5/8"
SIDE VIEW
10 3/8"
18 13/32"
38 15/16"
15 1/32"
DIMENSIONAL DRAWING FOR 5000 SERIES