piping system at test pressures equal to or less than 1/2 

PSI (3.5KPA).

 If the furnace is installed in a residential garage, it must be 

3. 

installed so the burner and the ignition source are located 

not less than 18 inches (457 mm) above the floor and the 

furnace must be located or protected to avoid physical 

damage by vehicles.

Provisions for adequate combustion and ventilation air 

4. 

in accordance with section 5.3, air for combustion and 

ventilation, of the National Fuel Gas Code, ANSI Z223.1, 

or sections 7.2, 7.3, or 7.4 of CAN/CGA-B149, installation 

codes, or applicable provisions of the local building codes.

The furnace uses outside air for combustion. Excessive 

5. 

exposure to contaminated combustion air will result in 

safety and performance related problems. Avoid installing 

the unit near sources or vents that may contain the 

following contaminants:

a.  Permanent Wave Solutions

b.  Chlorinated Waxes and Cleaners

c.  Chlorine-Based Swimming Pool Chemicals

d.  Water Softening Chemicals

e.  De-Icing Salts or Chemicals

f.   Carbon Tetrachloride

g.  Halogen Type Refrigerants

h.  Cleaning Solvents (such as Perchloroethylene)

i.   Printing Inks, Paint Removers, Varnishes, etc.

j.   Hydrochloric Acid

k.  Cements and Glues

l.   Antistatic Fabric Softeners for Clothes Dryers

m. Masonry Acid Washing Materials

The Comfort Pack unit shall not be installed directly on 

6. 

carpeting, tile, or other combustible material other than 

wood flooring. 

 The Comfort Pack may be installed with zero clearances 

7. 

on all sides.  It is recommended that a minimum of 29” of 

unobstructed area be provided in front of the access panels 

for routine service and chassis removal.

The grilles on the outside of the units should be kept clear 

8. 

of obstructions to permit proper operation of the furnace 

vent system.

 The vent system is designed for proper operation under 

9. 

all weather conditions and for winds up to 40 mph.  Do not 

alter or extend the vent outlet. 

The furnace venting system is an integral, independent, 

10. 

complete, and tested part of the Comfort Pack unit.  It is not 

intended for field connection to any other venting system.  

Do not modify, alter or connect to the vent system in the 

unit.

The gas furnace comes completely assembled, wired, mounted, 

and factory tested inside the Comfort Pack cabinet. The furnace 

includes an integral venting system that does not require any 

field modification or additions.  The control system includes a 

control board with cooling relay, combination gas valve, direct-

spark ignition electrode, flame sensor, blocked vent switch, 

flame rollout sensor, and high temperature limit. The rating plate 

indicates whether the furnace is equipped and configured for 

natural or L.P. gas.  The furnace includes 

a condensate disposal system.

THE GAS FURNACES ARE CATEGORY III AND ARE 

IDENTIFIED AS FOLLOWS:

Part Numbers

Input (Mbh)

14208309/HS038

38

14208308/HS051

51

14208303/HS064

64

INQUIRIES AND PARTS ORDERS 

SHOULD BE DIRECTED TO:

National Comfort Products

539 Dunksferry Road

Bensalem, PA 19020

Phone: (215) 244-1400

(800) 523-7138

Fax: (215) 639-1674

The installer shall provide approved gas piping to the furnace 

including an external manual shutoff valve with 1/8” NPT 

plugged tapping for test gauge*, external drip leg and external 

ground joint union.  These components and any other require-

ments shall conform to local building codes.  Care must be 

exercised in locating the unit so that hot flue gas from the furnace 

conforms to local codes for proximities to public walkways, gas 

meters, intake vents, etc.  In the absence of local codes, the 

installation must conform with the ANSI Z223.1, National Fuel 

Gas Code, and/or CAN/CGA-B149, Installation Code. 

THE FOLLOWING REGULATIONS APPLY TO THE FURNACE 

INSTALLATION:

 The furnace is 

1. 

NOT

 to be used for temporary heating of 

buildings or structures under construction. 

The furnace and its appliance main gas valve must be 

2. 

disconnected from the gas supply piping system during any 

pressure testing of that system at test pressures in excess 

of 1/2 PSI (3.5 KPA).  The furnace must be isolated from 

the gas supply piping system by closing the equipment 

shut-off valve during any pressure testing of the gas supply 

National Comfort Products

539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579

General

Installation

1

COMFORT PACK - GAS FURNACE INSTRUCTIONS                

* 1/8” NPT plugged tapping for test gauge not permitted in Massachusetts.

Summary of Contents for 14208309/HS038

Page 1: ...539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800 523 7138 Fax 215 244 9579 14299573 03 10 14299575 10 29 2014 National Comfort Products 539 Dunksferry Road Bensalem PA 19020 215 244 1400 1 800...

Page 2: ...FOR MAXIMUM PERFORMANCE IT IS IMPERATIVE THAT THE COOLING CHASSIS AIR DIVIDER BE SEALED TO THE CABINET AIR SEAL ANY LEAKAGE WILL ALLOW OUTSIDE UNCONDITIONED AIR TO INFILTRATE AND MIX WITH THE CONDITIO...

Page 3: ...em Do not modify alter or connect to the vent system in the unit The gas furnace comes completely assembled wired mounted and factory tested inside the Comfort Pack cabinet The furnace includes an int...

Page 4: ...y air duct should be equipped with a removable inspection panel to allow for future inspections of the heat exchanger The Comfort Pack unit contains a 16 x 25 x 1 air filter 12 located on the cooling...

Page 5: ...Integrated Control Board w Cooling Relay High Temperature Limit Thermostat Pressure Switch High Altitude Pressure Switch Combination Gas Valve Venter Tube Assembly Venter Wheel Motor Assembly Heat Ex...

Page 6: ...nd Mtr 230V COIL Fan Herm Compressor C S R Dual Capacitor FLAME SENSOR Roll Out Press Sw To Thermostat Inducer Mtr Contactor RD BK Blue Blue Blue Yellow WT WT BK Y G Red Red White Yellow White Black B...

Page 7: ...ond Mtr 230V COIL Fan Herm Compressor C S R Dual Capacitor FLAME SENSOR Roll Out Press Sw To Thermostat Inducer Mtr Contactor RD BK Blue Blue Blue Blue WT WT BK Y G Red Red White Yellow White Black Bl...

Page 8: ...IZED 7 IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND MUST BE RE 8 SET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT SEE LIGHTING INST...

Page 9: ......

Page 10: ......

Page 11: ......

Page 12: ...COMFORT PACK R 410A Gas Furnace Instructions Rev 14299575 10 29 2014...

Reviews: