piping system at test pressures equal to or less than 1/2
PSI (3.5KPA).
If the furnace is installed in a residential garage, it must be
3.
installed so the burner and the ignition source are located
not less than 18 inches (457 mm) above the floor and the
furnace must be located or protected to avoid physical
damage by vehicles.
Provisions for adequate combustion and ventilation air
4.
in accordance with section 5.3, air for combustion and
ventilation, of the National Fuel Gas Code, ANSI Z223.1,
or sections 7.2, 7.3, or 7.4 of CAN/CGA-B149, installation
codes, or applicable provisions of the local building codes.
The furnace uses outside air for combustion. Excessive
5.
exposure to contaminated combustion air will result in
safety and performance related problems. Avoid installing
the unit near sources or vents that may contain the
following contaminants:
a. Permanent Wave Solutions
b. Chlorinated Waxes and Cleaners
c. Chlorine-Based Swimming Pool Chemicals
d. Water Softening Chemicals
e. De-Icing Salts or Chemicals
f. Carbon Tetrachloride
g. Halogen Type Refrigerants
h. Cleaning Solvents (such as Perchloroethylene)
i. Printing Inks, Paint Removers, Varnishes, etc.
j. Hydrochloric Acid
k. Cements and Glues
l. Antistatic Fabric Softeners for Clothes Dryers
m. Masonry Acid Washing Materials
The Comfort Pack unit shall not be installed directly on
6.
carpeting, tile, or other combustible material other than
wood flooring.
The Comfort Pack may be installed with zero clearances
7.
on all sides. It is recommended that a minimum of 29” of
unobstructed area be provided in front of the access panels
for routine service and chassis removal.
The grilles on the outside of the units should be kept clear
8.
of obstructions to permit proper operation of the furnace
vent system.
The vent system is designed for proper operation under
9.
all weather conditions and for winds up to 40 mph. Do not
alter or extend the vent outlet.
The furnace venting system is an integral, independent,
10.
complete, and tested part of the Comfort Pack unit. It is not
intended for field connection to any other venting system.
Do not modify, alter or connect to the vent system in the
unit.
The gas furnace comes completely assembled, wired, mounted,
and factory tested inside the Comfort Pack cabinet. The furnace
includes an integral venting system that does not require any
field modification or additions. The control system includes a
control board with cooling relay, combination gas valve, direct-
spark ignition electrode, flame sensor, blocked vent switch,
flame rollout sensor, and high temperature limit. The rating plate
indicates whether the furnace is equipped and configured for
natural or L.P. gas. The furnace includes
a condensate disposal system.
THE GAS FURNACES ARE CATEGORY III AND ARE
IDENTIFIED AS FOLLOWS:
Part Numbers
Input (Mbh)
14208309/HS038
38
14208308/HS051
51
14208303/HS064
64
INQUIRIES AND PARTS ORDERS
SHOULD BE DIRECTED TO:
National Comfort Products
539 Dunksferry Road
Bensalem, PA 19020
Phone: (215) 244-1400
(800) 523-7138
Fax: (215) 639-1674
The installer shall provide approved gas piping to the furnace
including an external manual shutoff valve with 1/8” NPT
plugged tapping for test gauge*, external drip leg and external
ground joint union. These components and any other require-
ments shall conform to local building codes. Care must be
exercised in locating the unit so that hot flue gas from the furnace
conforms to local codes for proximities to public walkways, gas
meters, intake vents, etc. In the absence of local codes, the
installation must conform with the ANSI Z223.1, National Fuel
Gas Code, and/or CAN/CGA-B149, Installation Code.
THE FOLLOWING REGULATIONS APPLY TO THE FURNACE
INSTALLATION:
The furnace is
1.
NOT
to be used for temporary heating of
buildings or structures under construction.
The furnace and its appliance main gas valve must be
2.
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of 1/2 PSI (3.5 KPA). The furnace must be isolated from
the gas supply piping system by closing the equipment
shut-off valve during any pressure testing of the gas supply
National Comfort Products
539 Dunksferry Road • Bensalem, PA 19020 • (215) 244-1400 • 1-800-523-7138 • Fax: (215) 244-9579
General
Installation
1
COMFORT PACK - GAS FURNACE INSTRUCTIONS
* 1/8” NPT plugged tapping for test gauge not permitted in Massachusetts.