45
Chassis (Cooling Section)
Electronically Commutated Motor Troubleshooting
Part# 14270048
DC Controlled Constant Torque Motor
230 Volt, 3.0 Amp , 1120 RPM, 1/3HP, CCW LE, 0-10V DC Controlled
To verify motor operations, disconnect all electrical power to the motor.
Wait at least 2 minutes to allow the motor control circuits to discharge.
Visually inspect the motor for any obstructions and carefully remove if any are found.
Turn the power back on to the motor and verify with a voltmeter the voltage at the line voltage
connections from the motor leads. Voltage should read between 197-252 Volts.
Verify DC voltage between the white and red wires on the DC control wiring lead. It should read
between 4.6 & 9.1 Volts. If no voltage is measured, verify the controls operations by following
the DC Motor Check Steps on the next page.