© National Instruments
|
5-15
cDAQ-9185/9189 User Manual
Assume that an input terminal has been low for a long time. The input terminal then changes
from low to high, but glitches several times. When the Filter Clock has sampled the signal high
on
N
consecutive edges, the low-to-high transition is propagated to the rest of the circuit. The
value of
N
depends on the filter setting, as shown in Table 5-1.
On power up, the filters are disabled. Figure 5-7 shows an example of a low-to-high transition
on an input that has a custom filter set to
N
= 5.
Figure 5-7.
PFI Filter Example
Table 5-1.
Selectable PFI Filter Settings
Filter Setting
Filter Clock
Jitter
Min Pulse
Width
*
to Pass
Max Pulse
Width
*
to Not Pass
112.5 ns
(short)
80 MHz
12.5 ns
112.5 ns
100 ns
6.4
μ
s
(medium)
80 MHz
12.5 ns
6.4
μ
s
6.3875
μ
s
2.56 ms (high)
100 kHz
10
μ
s
2.56 ms
2.55 ms
Custom
User-
configurable
1 Filter
Clock
period
T
user
T
user
- (1 Filter
Clock period)
*
Pulse widths are nominal values; the accuracy of the chassis timebase and I/O distortion will affect these