Power Button
The default behavior for the cRIO-9035 is to power on when you apply power to the controller
and power off when you press and release the power button. The behavior of the power button
can be configured in the BIOS.
If the cRIO-9035 becomes unresponsive, you can power it off by holding the power button for
4 seconds.
Related Information
Power/Wake Configuration Submenu
on page 35
RESET Button
Press the RESET button to reset the processor in the same manner as cycling power.
Troubleshooting Network Connectivity
You can use the RESET button to troubleshoot network connectivity.
Complete the following steps to reset the network adapters to default settings.
1.
Hold the RESET button for 5 seconds, and then release it to boot the controller in safe
mode and enable Console Out.
2.
Hold the RESET button again for 5 seconds to boot the controller into safe mode, enable
Console Out, and reset network adapters to default settings.
System Reset
The following figure shows the reset behavior of the cRIO-9035.
Figure 4. Reset Button Behavior
Press and hold RESET button for
≥
5 s
Press and hold RESET button for
<
5 s
Run Mode
Safe Mode
Press and hold RESET button for
<
5 s
Press and hold RESET button for
≥
5 s
Press and hold
RESET button for
≥
5 s
Press and hold
RESET button for
<
5 s
• Console Out enabled
• Network settings reset
• RT Startup App disabled
• FPGA Startup App disabled
• Console Out enabled
• RT Startup App disabled
• FPGA Startup App disabled
Safe Mode
NI cRIO-9035 User Manual
|
© National Instruments
|
15