Figure 7. cRIO-9031 Module Immobilization Accessory Dimensions
94.2 mm
(3.71 in.)
1.6 mm
(0.06 in.)
1.6 mm
(0.06 in.)
220.4 mm (8.68 in.)
Mounting the Device
To obtain the maximum allowable ambient temperature of 70 °C, you must mount the
cRIO-9031 horizontally on a flat, metallic, vertical surface such as a panel or wall. You can
mount the cRIO-9031 directly to the surface or use the NI Panel Mounting Kit. The following
figure shows the cRIO-9031 mounted horizontally.
Figure 8. cRIO-9031 Horizontal Mounting
1
1. Up
You can also mount the cRIO-9031 in other orientations, on a nonmetallic surface, on a
35-mm DIN rail, on a desktop, or in a rack. Mounting the cRIO-9031 in these or other
configurations can reduce the maximum allowable ambient temperature and can affect the
typical accuracy of modules in the cRIO-9031. For more information about typical accuracy
specifications for C Series modules and temperature deratings caused by different mounting
configurations, visit
and enter the Info Code
criotypical
.
Caution
Make sure that no C Series modules are in the cRIO-9031 before
mounting it.
Tip
Before using any of these mounting methods, record the serial number from
the back of the cRIO-9031 so that you can identify the cRIO-9031 in MAX. You
will be unable to read the serial number after you mount the cRIO-9031.
24
|
ni.com
|