Ambient Temperature......................................................................................................16
Mounting the Device Directly on a Flat Surface............................................................ 17
Mounting the Device on a Panel..................................................................................... 18
Mounting the Device on a DIN Rail............................................................................... 19
Mounting the Device on a Rack......................................................................................21
Mounting the Device on a Desktop.................................................................................21
Configuring Startup Options
Complete the following steps to configure the cRIO-9068 startup options in MAX.
1.
In MAX, expand your system under Remote Systems.
2.
Select the
Startup Settings
tab to configure the startup settings.
cRIO-9068 Startup Options
You can configure the following cRIO-9068 startup options.
Table 1. cRIO-9068 Startup Options
Startup Option
Description
Force Safe Mode Rebooting the cRIO-9068 with this setting on starts the cRIO-9068
without launching LabVIEW Real-Time or any startup applications. In
safe mode, the cRIO-9068 launches only the services necessary for
updating configuration and installing software.
Enable Console
Out
Rebooting the cRIO-9068 with this setting on redirects the console output
to the RS-232 serial port. You can use a serial-port terminal program to
read the IP address and firmware version of the cRIO-9068. Use a null-
modem cable to connect the RS-232 serial port to a computer. Make sure
that the serial-port terminal program is configured to the following
settings:
•
115,200 bits per second
•
Eight data bits
•
No parity
•
One stop bit
•
No flow control
Disable RT
Startup App
Rebooting the cRIO-9068 with this setting on prevents any LabVIEW
startup applications from running.