FP-DI-330 and cFP-DI-330

working voltages of 250 V

rms

1

. Safety standards (such as those 

published by UL and IEC) require the use of double insulation 
between hazardous voltages and any human-accessible parts or 
circuits.

Never

 try to use any isolation product between human-accessible 

parts (such as DIN rails or monitoring stations) and circuits that 
can be at hazardous potentials under normal conditions, unless the 
product is specifically designed for such an application, as is the 
[c]FP-DI-330.

Even though the [c]FP-DI-330 is designed to handle applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system:

There is no safety isolation between channels on the 
[c]FP-DI-330. If a hazardous voltage is present on any channel, 
all channels are considered hazardous. Make sure that all other 
devices and circuits connected to the module are properly 
insulated from human contact.

Do 

not

 share the external supply voltages (the V and 

C terminals) with other devices (including other FieldPoint 
devices), unless those devices are isolated from human contact.

For Compact FieldPoint, you 

must

 connect the protective earth 

(PE) ground terminal on the cFP-BP-

x

 backplane to the system 

safety ground. The backplane PE ground terminal has the 
following symbol stamped beside it: 

. Connect the 

backplane PE ground terminal to the system safety ground 
using 14 AWG (1.6 mm) wire with a ring lug. Use the 5/16 in. 
panhead screw shipped with the backplane to secure the ring 
lug to the backplane PE ground terminal.

As with any hazardous voltage wiring, make sure that all 
wiring and connections meet applicable electrical codes and 
commonsense practices. Mount terminal bases and backplanes 
in an area, position, or cabinet that prevents accidental or 
unauthorized access to wiring that carries hazardous voltages.

Do 

not

 use the [c]FP-DI-330 as the only isolating barrier 

between human contact and working voltages higher than 
250 V

rms

.

1  

Working voltage

 is defined as the signal voltage plus the common-mode voltage. 

Common-mode voltage

 is the voltage of the module with respect to ground.

Summary of Contents for FieldPoint cFP-DI-330

Page 1: ... FP DI 330 is a FieldPoint digital input module with the following features Eight digital input channels Universal inputs that work with any voltage from 5 V TTL level up to 250 VDC VAC Compatibility with sourcing sinking or power sensing applications On Off LED indicators 250 Vrms CAT II continuous channel to ground isolation verified by 2 300 Vrms 1 minute dielectric withstand test 40 to 70 C op...

Page 2: ...Compact FieldPoint backplane cFP BP x which provides operating power to the module Installing the cFP DI 330 onto a powered backplane does not disrupt the operation of the bank To install the cFP DI 330 refer to Figure 2 and complete the following steps 1 Align the captive screws on the cFP DI 330 with the holes on the backplane The alignment keys on the cFP DI 330 prevent backward insertion 2 Pre...

Page 3: ...onnector block provides the same connections for the cFP DI 330 You can wire each channel to a switch a sourcing output device a sinking output device or a load Each channel has two input terminals INa and INb a supply terminal VSUP and a common terminal COM All eight COM terminals are internally connected to each other and to the C terminals All eight VSUP terminals are internally connected to ea...

Page 4: ...x connector blocks If you are using the cFP DI 330 in a hazardous voltage application you must use the cFP CB 1 connector block or a suitable hazardous voltage cable A hazardous voltage is a voltage greater than 42 4 Vpeak or 60 VDC Caution Ensure that hazardous voltage wiring is performed only by qualified personnel adhering to local electrical standards Caution Do not mix circuits with hazardous...

Page 5: ...ure 3 Connecting Devices to the c FP DI 330 Sinking Output Device NPN c FP DI 330 VSUP COM V C Input Circuitry INb Ch 1 INa Ch 1 Sourcing Output Device PNP VSUP COM Input Circuitry INb Ch 2 INa Ch 2 Sinking Output Device NPN VSUP COM Input Circuitry INb Ch 3 INa Ch 3 Sourcing Output Device PNP VSUP COM Input Circuitry INb Ch 4 INa Ch 4 Switch VSUP COM Input Circuitry INb Ch n INa Ch n 5 250 V Exte...

Page 6: ...g a Sourcing Output Device to the c FP DI 330 To connect a sourcing output device to the c FP DI 330 connect a power supply to the V and C terminals of the c FP DI 330 Connect the VSUP INa INb and COM terminals to the sourcing output device Figure 5 Wiring the c FP DI 330 to a Sourcing Output Device Switch c FP DI 330 VSUP COM V C Input Circuitry INb INa 5 250 V External Power Supply 2 A Max Sourc...

Page 7: ...ing Output Device to the c FP DI 330 To connect a sinking output device to the c FP DI 330 connect a power supply to the V and C terminals of the c FP DI 330 Connect the VSUP INa INb and COM terminals to the sinking output device Figure 7 Wiring the c FP DI 330 to a Sinking Output Device Sourcing Output Device PNP c FP DI 330 VSUP COM V C Input Circuitry INb INa Sinking Output Device NPN c FP DI 3...

Page 8: ...re 9 Wiring the c FP DI 330 to a Load Universal Input Circuit The c FP DI 330 has eight current limited universal input channels with bi directional optical isolators Each channel has two interchangeable signal inputs INa and INb When you apply a voltage across the INa and INb terminals signal current flows through the input circuitry and turns on the optical isolator registering as an ON conditio...

Page 9: ...0 may or may not register an ON condition Ensure that the devices you connect to the c FP DI 330 have OFF state leakage currents lower than 350 µA Higher leakage currents can cause false ON readings The filter on the c FP DI 330 inputs cause a delay of approximately 1 2 ms between the time a voltage changes from the ON state to the OFF state and the time the c FP DI 330 recognizes the change The d...

Page 10: ...30 it sends initial configuration information to the c FP DI 330 After the c FP DI 330 receives this initial information the green READY indicator lights and the module is in normal operating mode In addition to the green POWER and READY indicators each channel has a numbered green status indicator that lights when the channel is in the ON state Isolation and Safety Guidelines Caution Read the fol...

Page 11: ...nal supply voltages the V and C terminals with other devices including other FieldPoint devices unless those devices are isolated from human contact For Compact FieldPoint you must connect the protective earth PE ground terminal on the cFP BP x backplane to the system safety ground The backplane PE ground terminal has the following symbol stamped beside it Connect the backplane PE ground terminal ...

Page 12: ...he c FP DI 330 at or below Installation Category II Installation Category II is for measurements performed on circuits directly connected to the low voltage installation This category refers to local level distribution such as that provided by a standard wall outlet Specifications The following specifications are typical for the range 40 to 70 C unless otherwise noted Specifications are subject to...

Page 13: ...200 mW Isolation Voltage Channel to ground isolation Continuous 250 Vrms Installation Category II Dielectric withstand 2 300 Vrms 1 minute Channel to channel isolation None Environmental FieldPoint modules are intended for indoor use only For outdoor use they must be mounted inside a sealed enclosure Operating temperature 40 to 70 C Storage temperature 55 to 85 C Humidity 10 to 90 RH noncondensing...

Page 14: ...s designed to meet the requirements of the following standards of safety for electrical equipment for measurement control and laboratory use IEC 61010 1 EN 61010 1 UL 3121 1 UL 61010C 1 CAN CSA C22 2 No 1010 1 For UL hazardous location and other safety certifications refer to the product label or visit ni com hardref nsf search by model number or product line and click the appropriate link in the ...

Page 15: ...gulatory compliance information To obtain the DoC for this product visit ni com hardref nsf search by model number or product line and click the appropriate link in the Certification column Mechanical Dimensions Figure 12 shows the mechanical dimensions of the FP DI 330 installed on a terminal base If you are using the cFP DI 330 refer to your Compact FieldPoint controller user manual for the dime...

Page 16: ... help address your support needs For telephone support in the United States create your service request at ni com support and follow the calling instructions or dial 512 795 8248 For telephone support outside the United States contact your local branch office Australia 1800 300 800 Austria 43 0 662 45 79 90 0 Belgium 32 0 2 757 00 20 Brazil 55 11 3262 3599 Canada Calgary 403 274 9391 Canada Ottawa...

Reviews: