National Instruments Corp.
13
FP-DI-330 and cFP-DI-330
Input current limiting........................ 1.5 mA
Input delay time ................................ 1.2 ms
Physical Characteristics
Indicators .......................................... Green
POWER
and
READY
indicators, 8 green
input state indicators
Weight
FP-DI-330................................... 130 g (4.5 oz)
cFP-DI-330................................. 100 g (3.4 oz)
Power Requirements
Power from network module ............ 200 mW
Isolation Voltage
Channel-to-ground isolation
Continuous ................................. 250 V
rms
, Installation
Category II
Dielectric withstand.................... 2,300 V
rms
, 1 minute
Channel-to-channel isolation ............ None
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature ...................... –40 to 70 °C
Storage temperature .......................... –55 to 85 °C
Humidity ........................................... 10 to 90% RH,
noncondensing
Maximum altitude............................. 2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered
Pollution Degree ............................... 2