FP-CTR-502 and cFP-CTR-502
20
ni.com
Shock and Vibration
These specifications apply only to the cFP-CTR-502.
NI recommends Compact FieldPoint if your application is
subject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64).............................. 10–500 Hz, 5 g
rms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................ 10–500 Hz, 5 g
Operating shock
(IEC 60068-2-27).............................. 50 g, 3 ms half sine,
18 shocks at 6 orientations;
30 g, 11 ms half sine,
18 shocks at 6 orientations
Safety
This product is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement,
control, and laboratory use:
•
IEC 61010-1, EN 61010-1
•
UL 3121-1, UL 61010C-1
•
CAN/CSA C22.2 No. 1010.1
For UL, hazardous location, and other safety certifications, refer to
the product label or to
ni.com
.
Electromagnetic Compatibility
CE, C-Tick, and FCC Part 15 (Class A) Compliant
Emissions.......................................... EN 55011 Class A at 10 m
FCC Part 15A above 1 GHz
Immunity........................................... EN 61326:1997
+
A2:2001,
Table 1
Note
For EMC compliance, you
must
operate this device
with shielded cabling.