Continuous
250 V AC, Measurement Category II
Withstand
1,390 V AC, verified by a 5 s dielectric withstand test
Channel-to-earth ground
Continuous
250 V AC, Measurement Category II
Withstand
2,300 V AC, verified by a 5 s dielectric withstand test
Zone 2 hazardous locations applications in Europe
Channel-to-channel and channel-to-earth ground
60 V DC, Measurement Category I
Safety Guidelines for Hazardous Locations
The NI-9219 is suitable for use in hazardous locations; , and hazardous locations;
and nonhazardous locations only. Follow these guidelines if you are installing the
NI-9219 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
Caution
Substitution of components may impair suitability for Class I,
Division 2, or Zone 2.
Caution
The system must be installed in an enclosure certified for the
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.