Channel-to-channel
None
Channel-to-earth ground
Continuous
60 V DC, Measurement Category I
Withstand
1,000 V RMS, verified by a 5 s dielectric withstand test
Safety Guidelines for Hazardous Locations
The NI-9230 is suitable for use in Class I, Division 2, Groups A, B, C, D, T4 hazardous
locations; Class I, Zone 2, AEx nA IIC T4 Gc and Ex nA IIC T4 Gc hazardous locations;
and nonhazardous locations only. Follow these guidelines if you are installing the
NI-9230 in a potentially explosive environment. Not following these guidelines may
result in serious injury or death.
Caution
Do not disconnect I/O-side wires or connectors unless power has
been switched off or the area is known to be nonhazardous.
Caution
Do not remove modules unless power has been switched off or
the area is known to be nonhazardous.
Caution
Substitution of components may impair suitability for Class I,
Division 2, or Zone 2.
Caution
The system must be installed in an enclosure certified for the
intended hazardous (classified) location, having a tool secured cover/door,
where a minimum protection of at least IP54 is provided.
Caution
For Division 2 and Zone 2 applications, connected signals must
be within the following limits.
Capacitance
0.2 µF maximum
ni.com
4
NI-9230 Getting Started