NI 9425E Operating Instructions and Specifications
|
© National Instruments
|
9
I/O protection
Input voltage
8 channels ............................ 60 VDC max
32 channels .......................... 30 VDC max
Reverse-biased voltage
8 channels ............................ -60 VDC max
32 channels .......................... -30 VDC max
Hold time
1
......................................... 0
μ
s min
Setup time
2
........................................ 1
μ
s min
Update/transfer time ......................... 7
μ
s max
MTBF ............................................... 1,256,699 hours at 25 °C;
Bellcore Issue 2, Method 1,
Case 3, Limited Part Stress
Method
1
Hold time
is the amount of time input signals must be stable after initiating a read
from the module.
2
Setup time
is the amount of time input signals must be stable before reading from the
module.