Tie the encoder cable shield to COM at the encoder side only.
•
Wire encoder signals and their ground connections separately
from all other connections to prevent lost encoder counts.
•
Route wires along the machine frame to reduce high frequency
noise.
•
Add clamp-on ferrites to cables to further reduce emissions.
•
Add a balun to the power cable to attenuate conducted and
radiated emissions.
Using the NI 9505E with Other C Series Modules
Due to additional ambient heating of the NI 9505E when supplying
more than 1 A to the load, the room temperature (25 ºC, ± 5 ºC)
specifications of adjacent modules are not valid. The full operating
temperature (–40 ºC to 85 ºC) specifications for these modules are
still valid.