drive. Refer to the
Measurement & Automation Explorer Help
for more information about
installing software on a controller and reformatting the drive on the controller.
CONSOLE OUT Switch
With a serial-port terminal program, you can use the CONSOLE OUT switch to read the IP
address and firmware version of the controller. Use a null-modem cable to connect the serial
port on the chassis to a computer. Push the switch to the ON position. Make sure that the
serial-port terminal program is configured to the following settings:
•
9,600 bits per second
•
Eight data bits
•
No parity
•
One stop bit
•
No flow control
The serial-port terminal program displays the IP address and firmware version of the chassis.
Keep this switch in the OFF position during normal operation.
IP RESET Switch
Push the IP RESET switch to the ON position and reboot the controller to reset the IP address
and other TCP/IP settings of the controller to the factory defaults. Refer to the
section for more information about resetting the IP address. You also
can push this switch to the ON position to unlock a chassis that was previously locked in
MAX.
NO APP Switch
Push the NO APP switch to the ON position to prevent a LabVIEW RT startup application
from running at startup. If you want to permanently disable a LabVIEW RT application from
running at startup, you must disable it in LabVIEW. To run an application at startup, push the
NO APP switch to the OFF position, create an application using the LabVIEW Application
Builder, and configure the application in LabVIEW to launch at startup. If you already have an
application configured to launch at startup and you push the NO APP switch from ON to OFF,
the startup application is automatically enabled. For more information about automatically
launching VIs at startup and disabling VIs from launching at startup, refer to the
LabVIEW
Help
.
USER1 Switch
You can define the USER1 switch for your application. To define the purpose of this switch in
your embedded application, use the RT Read Switch VI in your LabVIEW RT embedded VI.
For more information about the RT Read Switch VI, refer to the
LabVIEW Help
.
NO FPGA Switch
Push the NO FPGA switch to the ON position to prevent a LabVIEW FPGA application from
loading at startup. The NO FPGA switch overrides the CompactRIO reset options described in
section. After startup you can download to the FPGA from software
regardless of switch position.
14
|
ni.com
|
NI cRIO-9074XT User Manual and Specifications