Caution

 

Do not remove modules unless power has been switched off or the area is

known to be nonhazardous.

Caution

 

Substitution of components may impair suitability for Zone 2.

Caution

 

You must make sure that transient disturbances do not exceed 140% of

the rated voltage.

Caution

 

The system shall only be used in an area of not more than Pollution

Degree 2, as defined in IEC/EN 60664-1.

Caution

 

The system shall be mounted in a CCC-certified enclosure with a

minimum ingress protection rating of at least IP54 as defined in GB3836.1.

Caution

 

The enclosure must have a door or cover accessible only by the use of a

tool.

Power Requirements

These power requirements are for a fully loaded chassis and exclude the power requirements
of the controller and the I/O modules in the chassis.

Chassis power consumption/dissipation

cRIO-9111 and cRIO-9112

+5 VDC

500 mW maximum

+3.3 VDC

2,100 mW maximum

Total chassis power
consumption

2,600 mW maximum

cRIO-9113 and cRIO-9114

+5 V DC

500 mW maximum

+3.3 V DC

2,800 mW maximum

Total chassis power
consumption

3,300 mW maximum

cRIO-9116

+5 V DC

500 mW maximum

+3.3 V DC

4,600 mW maximum

Total chassis power
consumption

5,100 mW maximum

cRIO-9111/9112/9113/9114/9116/9118

  | 

© National Instruments Corporation

  | 

3