Chapter 2
Installation and Configuration
©
National Instruments
2-7
NI PXIe-1071 User Manual
Connecting Safety Ground
Caution
The NI PXIe-1071 chassis is designed with a three-position inlet that connects the
cord set ground line to the chassis ground. To minimize shock hazard, make sure the
electrical power outlet you use to power the chassis has an appropriate earth safety ground.
Connecting to Power Source
Cautions
Do
not
install modules prior to performing the following power-on test.
To completely remove power, you
must
disconnect the AC power cable.
Attach input power through the rear AC inlet using the appropriate
AC power cable supplied. Refer to Figure 1-2,
Rear View of the
NI PXIe-1071 Chassis
, to locate the AC inlet.
Installing a PXI Express System Controller
This section contains general installation instructions for installing a
PXI Express system controller in a NI PXIe-1071 chassis. Refer to your
PXI Express system controller user manual for specific instructions and
warnings. To install a system controller, complete the following steps:
1.
Inspect the slot 1 pins on the chassis backplane for any bending or
damage prior to installation.
2.
Connect the AC power source to the PXI Express chassis before installing
the system controller. The AC power cord grounds the chassis and protects
it from electrical damage while you install the system controller.
3.
Install the system controller into the system controller slot (slot 1,
indicated by the red card guides) by first placing the system controller
PCB into the front of the card guides (top and bottom). Slide the
system controller to the rear of the chassis, making sure that the
injector/ejector handle is pushed down as shown in Figure 2-4.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com